background image

User Guide 

|

 Capacity Controller, AK-PC 651

© Danfoss | ADAP-KOOL® | 2015.10  

2 | RS8HA102 | 

Introduction

Application

The controller is used for capacity regulation of compressors  

and condensers in small refrigeration applications. A maximum of  

10 compressors and one condenser can be regulated. For exam-

ple:
• One suction group + one condenser group (max. 15 steps)
• One compressor group, max. 10 steps
• One condenser group, max. 8 steps

Advantages

• Energy savings via:

- Optimisation of suction pressure

- Night time increase

- Floating condensing pressure

- Load limitation 

Input and output

There are a limited number of available inputs and outputs. 

For each signal type, though, the following can be connected:

• Analogue inputs, max. 10 pcs.

Signal from pressure transmitters, temperature sensors,  

voltage signal, etc.

• Digital inputs, max. 18 pcs.

Signal from automatic safety control, day/night signal, etc.

• Relay outputs, max. 13 pcs.

Connection of compressors, condenser fans

• Solid state outputs, max. 2 pcs.

- Control of capacity valve on a Copeland digital scroll 

- Control of unloaders on a Copeland stream compressor. 

- Control of unloaders on a  Bitzer CRII Ecoline compressor

If the outputs are not used for these functions, they can be used 

as ordinary relay outputs 

• Analogue outputs, max. 4 pcs.

Speed control of compressors or condenser fans.

Operation

The daily operation can be set up directly on the controller or  

via an external display device.

During set-up, the display images will be adjusted so that only  

the relevant images are opened for additional setting and  

end-user operation.

The operation is password protected, and three levels of  

access can be granted. 

The controller contains several languages. Select the preferred 

language at start-up. 

Data communication

The controller has built-in modbus data communication, and it 

can be connected to a system device in the AK-SM 800 serie.

Summary of Contents for ADAP-KOOL AK-PC 651

Page 1: ...Capacity controller AK PC 651 User Guide ADAP KOOL Refrigeration Control System...

Page 2: ...matic safety control day night signal etc Relay outputs max 13 pcs Connection of compressors condenser fans Solid state outputs max 2 pcs Control of capacity valve on a Copeland digital scroll Control...

Page 3: ...one the control ler will cut out or cut in the next compressor in the sequence When further capacity is either cut out or cut in the capacity from the regulating compressor will be modified accordingl...

Page 4: ...of the following functions Fixed reference Variable reference which follows the outdoor temperature When the outdoor temperature drops the reference will drop by a corresponding amount This variable...

Page 5: ...scroll a Copeland stream or Bitzer CRII the capacity will be increased so that the compressor can cool down itself The compressors will be stopped if the temperature reaches the set max temperature va...

Page 6: ...n groups and 1 condenser group Each of the 3 rows above is continued with three additional displays The arrow in the top corner of the display shows the way to the next display in the same area of ope...

Page 7: ...y None Main Menu The first setting is the Plant type When the Plant type has been selected it will al low several settings to be made For example Continue to the next menus All settings are explained...

Page 8: ...s Device for configuration of compressor and condenser Select pressure or saturation temperature Can be set during initial set up and must not be subsequently changed Temp press Fac Saturated Night si...

Page 9: ...suction gas temperature can be read here Superheat The measured superheat can be read here Day Night status The status of the day night function can be read here Load shed The status of the load shed...

Page 10: ...0 s Fac 120 s Configuration Configuration Control sensor Select the regulating sensor for the suction circuit Pressure transmitter Po Media temperature sensor S4 brine regulation Po is used for safety...

Page 11: ...ed AI demand Yes No Fac No Ss suction superheat Monitoring of superheat Define whether a signal from a common Ss sensor on the suction line should be received AI demand Yes No Fac No Injection ON fct...

Page 12: ...Compressor service Compressor service Comp 1 out of service The compressor can be taken out of operation so that the controller regulates without this compressor No Normal regulation Yes Regulating i...

Page 13: ...uency converter Step on off control of fans will be via relays Variable step The signals are parallel so external wiring can switch over to step e g if the frequency converter fails AO demand Step Spe...

Page 14: ...is measured in the suction line by Po and Ss Min 0 K Max 20 K Fac 0 K Superheat Max lim Alarm limit for excess superheating Min 20 K Max 80 K Fac 80 K Superheat delay Delay time before alarm is gener...

Page 15: ...t Set the output to thermostat AI demand Yes No Fac No Thermostat cut in Here set the temperature value at which the thermostat will cut in Min 50 C Max 150 C Fac 5 C Thermostat cut out Here set the t...

Page 16: ...ation value 10 C Pressure sensors Signal type 0 20mA 4 20mA AKS32 1 5V or AKS32R 10 90 ratiometric of 5 V supply voltage Important Current types must be connected to inputs Al 1 6 Current types must b...

Page 17: ...ction is on or off Digital inputs 1 18 Status of on off inputs Here you can see the status of the function alarm Analoge outputs 1 4 Status of analogue outputs Here you can see the size of the output...

Page 18: ...on the next page App no Display Suction group Condenser Speed Digital Scroll Stream CRII 1 step with unloa der Step Speed 17 3C2U FS 3 x 16 2C2U 6F 2 6 15 4C1U FS 4 x 14 3C1U 6F 3 6 13 2C1U 4F 2 4 12...

Page 19: ...gle 8C FS 8 speed C1 C2 C3 C4 C5 C6 C7 C8 Fan VSD Alarm F speed 3 Single 6C FS 6 speed C1 C2 C3 C4 C5 C6 Fan VSD Alarm F speed 2 Single 6C 6F 6 6 C1 C2 C3 C4 C5 C6 Fan 1 Fan 2 Fan 3 Fan 4 Fan 5 Fan 6...

Page 20: ...6 Compressor start and unloaders Fans Injection ON Alarm on DO15 Digital inputs DI1 DI18 Compressor safety inputs Fan safety input External main switch start stop HP safety switch LP safety switch Nig...

Page 21: ...condensing pressure Pc has been violated 3K below safety limit High pressure Pc Critical HP safety switch cutout High safety limit for external high pressure switch has been violated DI input HP switc...

Page 22: ...oid earth fault current Use double insulated transformer The secondary side must not be earthed Obtain 0 10 volts from terminals N and AO1 respectively N and AO2 PAY ATTENTION TO THE POLARITY of N Mod...

Page 23: ...riod times as PWM per 100 capacity is delivered when cooling takes place for the whole period An off time is required by the bypass valve within the period and an on time is also permitted There is no...

Page 24: ...remaining 50 100 for the unloader The unloader is connected to DO5 or DO6 Stream 6 The compressor capacity is distributed by up to 33 for one relay and the remaining 33 100 for the unloader The unload...

Page 25: ...ed Display output For type MMIGRS2 Data communication Modbus for AK SM 800 Environments 20 60 C During operations 40 70 C During transport 20 80 Rh not condensed No shock influence vibrations Enclosur...

Page 26: ...amage poor installation or site conditions can give rise to malfunctions of the control system and ultimately lead to a plant breakdown Every possible safeguard is incorporated into our products to pr...