First step runtime

At start-up, the cooling system must have time to cool down before PI regulation takes over 

the regulation role and can cut in the next compressor.

Set the time before the next compressor may be started here.

Min: 0 s

Max: 300 s

Fac: 120 s

Pump down

Pump-down function

To avoid too many compressor starts/stops at a low load, it is possible to define a pump-

down function for the last compressor. In this case, the compressor will be cut out when the 

current suction pressure is down at the set “Pump-down limit Po”.

(The setting must be greater than the safety limit for low suction pressure “PoA Min Limit”.)

Yes /No

Fac: No

Min: -80°C (-1.0 bar)

Max: 30°C (50.0 bar)

Facb: -40°C (0.3 bar)

Load shed  limit

Capacity limitation at “low shed signal”

Set how much compressor capacity can be cut in when a signal is received from either a DI 

input or a system device via data communication. 

The value must not be set lower than the compressors’ lowest capacity step/”Start speed”.

Min: 0 %

Max: 100%

Fac: 100%

Emergency cap. day 

Emergency capacity in the event of a malfunction of the regulation sensor (suction pressure 

sensor)

Set the desired capacity that will apply during daytime operation.

(If the S4 media temperature sensor becomes damaged/defective, use Po for regulation.)

Min: 0 %

Max: 100%

Fac: 50%

Emergency cap. night Emergency capacity in the event of a malfunction of the regulation sensor (suction pressure 

sensor)

Set the desired capacity that will apply during night operation.

(If the S4 media temperature sensor becomes damaged/defective, use Po for regulation.)

Min: 0 %

Max: 100%

Fac: 25%

Comp. start delay

Delay of compressor start after forced closing of expansion valves (at the end of a forced 

close signal)

The delay will result in the system device receiving a start signal for all the evaporator con-

trols involved before the first compressor is started. 

Min: 0 s

Max: 180 s

Fac: 30 s

Injection OFF delay

Delay of the forced closing of expansion valves, if the controller calls for cut in of compres-

sors, but the compressors are in a locked situation and therefore cannot start.

Min: 0 s

Max: 300 s

Fac: 120 s

Configuration

Configuration

Control sensor

Select the regulating sensor for the suction circuit:

• Pressure transmitter Po 

• Media temperature sensor S4 (brine regulation). (Po is used for safety)

AI-demand

Po / S4

Fac: Po

Compressor mode

Set the type of compressor to be used for regulation:

• CRII6+Multi **

)

 First compressor is CRII6 compressor. The remaining ones are with unloaders

• CRII6+Single **

)

 First compressor is CRII6 compressor. The remaining ones are  

one-step units

• Stream 6+Multi: **

)

  First compressor is a stream 6 compressor. The remaining ones are with 

unloaders

• Stream 6+Single: **

)

 First compressor is a stream 6 compressor. The remaining ones are  

one-step units

• Multi all:****

)

 All compressors have unloaders

• Multi + Single:****

)

  First compressor has unloaders. The remaining ones are one-step units

• Speed+Multi: ***

)

 First compressor is speed-controlled. The remaining ones are with unload-

ers.

• Speed+Single: ***

)

 First compressor is speed-controlled. The remaining ones are  

one-step units

• CRII4+Multi **

)

 First compressor is CRII4 compressor. The remaining ones are with unloaders

• CRII4+Single **

)

 First compressor is CRII4 compressor. The remaining ones are  

one-step units

• Stream 4+Multi: **

)

 First compressor is a stream 4 compressor. The remaining ones are with 

unloaders

•  Stream 4+Single: **

)

 First compressor is a stream 4 compressor. The remaining ones are  

one-step units

• Digital scroll: *

)

 First compressor is a digital scroll. The remaining ones are one-step units

• Single-step only: All are one-step compressors

• None:

DO-demand /

AO-demand

Fac: 

Single step only

No. of compressors

Set the number of compressors on the suction circuit

DO-demand

Min: 1

Max: 8 

Fac: 0

Lead comp. size

Set the nominal compressor capacity for the first compressor (it is defined under  

“Compressor mode”)

That is, the capacity of either a “Digital scroll”, “Stream”, “Variable speed” or  

“First compressor with unloaders”

Min: 1 kW

Max: 100 kW

Fac: 1 kW

Comp. size

Set the nominal compressor capacity of the other compressors

For single-step only:  All are of the same size, including the first.

For unloader all:  All are of the same size, including the first.

Min: 1 kW

Max: 100 kW

Fac: 1 kW

VSD Min. speed

***:  For speed

Min. speed at which the compressor will cut out

Min: 10 Hz

Max: 60 Hz

Fac: 30 Hz

VSD Start speed

***:  For speed

Minimum speed at which the compressor will start (must be set to a higher value than  

“VSD Min. speed”)

Min: 20 Hz

Max: 60 Hz

Fac: 45 Hz

Summary of Contents for ADAP-KOOL AK-PC 651

Page 1: ...Capacity controller AK PC 651 User Guide ADAP KOOL Refrigeration Control System...

Page 2: ...matic safety control day night signal etc Relay outputs max 13 pcs Connection of compressors condenser fans Solid state outputs max 2 pcs Control of capacity valve on a Copeland digital scroll Control...

Page 3: ...one the control ler will cut out or cut in the next compressor in the sequence When further capacity is either cut out or cut in the capacity from the regulating compressor will be modified accordingl...

Page 4: ...of the following functions Fixed reference Variable reference which follows the outdoor temperature When the outdoor temperature drops the reference will drop by a corresponding amount This variable...

Page 5: ...scroll a Copeland stream or Bitzer CRII the capacity will be increased so that the compressor can cool down itself The compressors will be stopped if the temperature reaches the set max temperature va...

Page 6: ...n groups and 1 condenser group Each of the 3 rows above is continued with three additional displays The arrow in the top corner of the display shows the way to the next display in the same area of ope...

Page 7: ...y None Main Menu The first setting is the Plant type When the Plant type has been selected it will al low several settings to be made For example Continue to the next menus All settings are explained...

Page 8: ...s Device for configuration of compressor and condenser Select pressure or saturation temperature Can be set during initial set up and must not be subsequently changed Temp press Fac Saturated Night si...

Page 9: ...suction gas temperature can be read here Superheat The measured superheat can be read here Day Night status The status of the day night function can be read here Load shed The status of the load shed...

Page 10: ...0 s Fac 120 s Configuration Configuration Control sensor Select the regulating sensor for the suction circuit Pressure transmitter Po Media temperature sensor S4 brine regulation Po is used for safety...

Page 11: ...ed AI demand Yes No Fac No Ss suction superheat Monitoring of superheat Define whether a signal from a common Ss sensor on the suction line should be received AI demand Yes No Fac No Injection ON fct...

Page 12: ...Compressor service Compressor service Comp 1 out of service The compressor can be taken out of operation so that the controller regulates without this compressor No Normal regulation Yes Regulating i...

Page 13: ...uency converter Step on off control of fans will be via relays Variable step The signals are parallel so external wiring can switch over to step e g if the frequency converter fails AO demand Step Spe...

Page 14: ...is measured in the suction line by Po and Ss Min 0 K Max 20 K Fac 0 K Superheat Max lim Alarm limit for excess superheating Min 20 K Max 80 K Fac 80 K Superheat delay Delay time before alarm is gener...

Page 15: ...t Set the output to thermostat AI demand Yes No Fac No Thermostat cut in Here set the temperature value at which the thermostat will cut in Min 50 C Max 150 C Fac 5 C Thermostat cut out Here set the t...

Page 16: ...ation value 10 C Pressure sensors Signal type 0 20mA 4 20mA AKS32 1 5V or AKS32R 10 90 ratiometric of 5 V supply voltage Important Current types must be connected to inputs Al 1 6 Current types must b...

Page 17: ...ction is on or off Digital inputs 1 18 Status of on off inputs Here you can see the status of the function alarm Analoge outputs 1 4 Status of analogue outputs Here you can see the size of the output...

Page 18: ...on the next page App no Display Suction group Condenser Speed Digital Scroll Stream CRII 1 step with unloa der Step Speed 17 3C2U FS 3 x 16 2C2U 6F 2 6 15 4C1U FS 4 x 14 3C1U 6F 3 6 13 2C1U 4F 2 4 12...

Page 19: ...gle 8C FS 8 speed C1 C2 C3 C4 C5 C6 C7 C8 Fan VSD Alarm F speed 3 Single 6C FS 6 speed C1 C2 C3 C4 C5 C6 Fan VSD Alarm F speed 2 Single 6C 6F 6 6 C1 C2 C3 C4 C5 C6 Fan 1 Fan 2 Fan 3 Fan 4 Fan 5 Fan 6...

Page 20: ...6 Compressor start and unloaders Fans Injection ON Alarm on DO15 Digital inputs DI1 DI18 Compressor safety inputs Fan safety input External main switch start stop HP safety switch LP safety switch Nig...

Page 21: ...condensing pressure Pc has been violated 3K below safety limit High pressure Pc Critical HP safety switch cutout High safety limit for external high pressure switch has been violated DI input HP switc...

Page 22: ...oid earth fault current Use double insulated transformer The secondary side must not be earthed Obtain 0 10 volts from terminals N and AO1 respectively N and AO2 PAY ATTENTION TO THE POLARITY of N Mod...

Page 23: ...riod times as PWM per 100 capacity is delivered when cooling takes place for the whole period An off time is required by the bypass valve within the period and an on time is also permitted There is no...

Page 24: ...remaining 50 100 for the unloader The unloader is connected to DO5 or DO6 Stream 6 The compressor capacity is distributed by up to 33 for one relay and the remaining 33 100 for the unloader The unload...

Page 25: ...ed Display output For type MMIGRS2 Data communication Modbus for AK SM 800 Environments 20 60 C During operations 40 70 C During transport 20 80 Rh not condensed No shock influence vibrations Enclosur...

Page 26: ...amage poor installation or site conditions can give rise to malfunctions of the control system and ultimately lead to a plant breakdown Every possible safeguard is incorporated into our products to pr...

Reviews: