Parameter list VLT 8000 AQUA
Data
type
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
6
5
6
5
6
6
5
6
6
Conversion
index
0
0
0
0
0
0
0
0
0
-1
-1
0
-1
-1
0
-4
-4
0
0
0
0
0
0
0
0
0
0
0
0
Changes during operation:
"Yes" means that the parameter can be changed,
while the VLT AFD is in operation. "No" means that
the VLT AFD must be stopped before a change can
be made.
4-Setup:
"Yes" means that the parameter can be programmed
individually in each of the four setups, i.e. the same
parameter can have four different data values. "No"
means that the data value will be the same in all four
setups.
Conversion index:
This number refers to a conversion figure to be used
when writing or reading to or from a VLT AFD by
means of serial communication.
Conversion index
Conversion factor
7 4
0.1
2
1 0 0
1
1 0
0
1
- 1
0.1
- 2
0.01
- 3
0.001
- 4
0 . 0 0 0 1
Data type:
Data type shows the type and length of the telegram.
Data type
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string
PNU
Parameter
Factory setting
Range
Changes 4-Setup
#
description
during operation
300
Terminal 16 Digital input
Reset
Yes
Yes
301
Terminal 17 Digital input
No operation
Yes
Yes
302
Terminal 18 Digital input
Start
Yes
Yes
303
Terminal 19 Digital input
Reversing
Yes
Yes
304
Terminal 27 Digital input
Coasting stop, inverse
Yes
Yes
305
Terminal 29 Digital input
Jog
Yes
Yes
306
Terminal 32 Digital input
No operation
Yes
Yes
307
Terminal 33 Digital input
No operation
Yes
Yes
308
Terminal 53, analog
input voltage
No operation
Yes
Yes
309
Terminal 53, min. scaling
0.0 V
0.0 - 10.0 V
Yes
Yes
310
Terminal 53, max. scaling
10.0 V
0.0 - 10.0 V
Yes
Yes
311
Terminal 54, analog
input voltage
No operation
Yes
Yes
312
Terminal 54, min. scaling
0.0 V
0.0 - 10.0 V
Yes
Yes
313
Terminal 54, max. scaling
10.0 V
0.0 - 10.0 V
Yes
Yes
314
Terminal 60, analog input
current
Reference
Yes
Yes
315
Terminal 60, min. scaling
4.0 mA
0.0 - 20.0 mA
Yes
Yes
316
Terminal 60, max. scaling
20.0 mA
0.0 - 20.0 mA
Yes
Yes
317
Time out
10 sec.
1 - 99 sec.
Yes
Yes
318
Function after time out
Off
Yes
Yes
319
Terminal 42, output
0 - I
MAX
⇒
4-20 mA
Yes
Yes
320
Terminal 42, output,
pulse scaling
5000 Hz
1 - 32000 Hz
Yes
Yes
321
Terminal 45, output
0 - f
MAX
⇒
0-20 mA
Yes
Yes
322
Terminal 45, output,
pulse scaling
5000 Hz
1 - 32000 Hz
Yes
Yes
323
Relay 1, output function
No alarm
Yes
Yes
324
Relay 01, ON delay
0.00 sec.
0 - 600 sec.
Yes
Yes
325
Relay 01, OFF delay
2.00 sec.
0 - 600 sec.
Yes
Yes
326
Relay 2, output function
Running
Yes
Yes
327
Pulse reference,
5000 Hz
Depends on
Yes
Yes
max. frequency
input terminal
328
Pulse feedback, max. frequency
25000 Hz
0 - 65000 Hz
Yes
Yes
Parameter list