VLT
®
MICRO
No.
Parameter
Function
Parameter
Factory
Name
Explanation
Value
Setting
66
Master Freq.
d0.1 - 400 Hz
d1.0
67
Frequency
Skip frequency 1
d0.0 - d400. Hz
d0.0
68
Setting
Skip frequency 2
d0.0 - d400. Hz
d0.00
69
Prohibited
Skip frequency 3
d0.0 - d400. Hz
d0.00
70
Freq. Band-
Skip freq. Band
d0.1 - d20.0 Hz
d0.00
width Setting
Prevention
71
PWM Carrier
Carrier frequency
d0.1 - d20.0 Hz
d0.00
Frequency
select
d01 - d18; fc = 1kHz ~ 18kHz
d15
72
Auto Reset/Restart Oper. After Fault d00 - d10
d00
73
Fault Records
Most recent fault
d00: Fault records clear (No
d00
record
errors occurred)
74
2nd most recent
d01: Over-current (oc)
d00
fault record
75
3rd most recent
d02: Over-voltage (ov)
d00
fault record
d03: Overheat (oH)
d04: Overload (oL)
d05: Overload 1 (oL1)
d06:External fault (EF)
d07:CPU failure 1 (CF1)
d08: CPU failure 3 (CF3)
d09:Hardware protect failure (HPF)
d10: O.C. during acceleration (oCA)
d11: O.C. during deceleration (ocd)
d12: O.C. during steady state (ocn)
d13: Ground fault or fuse fail (GFF)
d14:EEROM abnormal 2 (CF2)
d15: Manufacture used diagnostics
d16: Manufacture used diagnostics
d17: External baseblock (bb)
d18: Overload 2 (oL2)
d19: Manufacture used diagnostics
d20: Soft protection efficient (codE)
76
Key
Key
d00: All parameters can always be
d00
Parameter
parameter
set and read
d01: All parameters are read-only
d02 - d09: not used
d10:Resets all parameters to the
factory defaults
77
Auto Decel.
Auto deceleration
d00: Auto deceleration gain key
d00
Gain Key
gain key
d01: Able to adjust the gain value
67
Summary of Contents for 176F7300