60
Pr.101 Auto Acceleration/Deceleration Adjustment Selection
Factory Setting d00
Units None
Settings
d00 Linear acceleration deceleration
d01 Automatic acceleration, linear deceleration
d02 Linear acceleration, automatic deceleration
d03 Automatic acceleration, deceleration
d04 For deceleration and stall due to overvoltage
Auto acceleration/deceleration adjustment selection can reduce the mechanical vibration
resulted from run and stop. When acceleration, the AC motor drive can maintain the
acceleration current to its rated value, making the motor operate to the set frequency by
the fastest acceleration. When decelerating, it can also judge the load regeneration
automatically, and then stop the motor smoothly in the fastest deceleration time.
Using auto acceleration/deceleration selection can avoid complex regulation procedure.
It performs acceleration operation without stall and deceleration stop without braking
resistors. It can also improve operation efficiency effectively and save energy.
This parameter provides five modes from which to choose:
d00 Linear acceleration deceleration
(operation at Pr.10, Pr.11 or Pr.12, Pr.13 acceleration/deceleration time)
d01 Automatic acceleration, linear deceleration
(operation by automatic acceleration, Pr.11 or Pr.13 deceleration time)
d02 Linear acceleration, automatic deceleration
(operation by automatic deceleration time, Pr.10 or Pr.12 acceleration time)
d03 Automatic acceleration deceleration
(acceleration/deceleration time is completely decided by AC motor drive automatic
control)
d04 Linear acceleration/deceleration according to the time setting of parameters Pr.11
and Pr.13 auto deceleration.
The auto deceleration function is not suitable when using braking resistors.
Pr.102 Auto Voltage Regulation (AVR)
Factory Setting d03
Units None
Settings
d00 Enable auto voltage regulation
d01 Disable auto voltage regulation
d02 Disable auto voltage regulation when stop
d03 Disable auto voltage regulation when deceleration