VLT
®
MICRO
No.
Parameter
Function
Parameter
Factory
Name
Explanation
Value
Setting
46
Multi-function
d01:Pre-set frequency attained
d07
RELAY output
d02:Non-zero speed
d03:Over-torque detection
d04:Baseblock indicator
d05:Low-voltage detect
d06:AC drive control mode
d07:Fault indicator
d08:Desired frequency attained
d09:PLC program running
d10:PLC program step complete
d11:PLC completed execution
d12:PLC execution paused
d13:Terminal counter reached
d14:Prelim counter value reached
47
Desired Freq.
Desired frequency
d0.0 - d400.0 Hz
d0.0
Attained
attained
48
Potentiometer
Potentiometer shift
d0.0 - d350 Hz
d0.0
Control
of output frequency
49
Potentiometer bias
d00:Minimum output frequency
d00
control
corresponds to potentiometer
at 0 V or 4 mA
d01:Initial output frequency set
with a potential bias point,
refer to Pr.50
50
Potentiometer out-
d01 - d200%
d100
put freq. gain
51
Reverse motion
d00:Forward motion only
d00
setting
d01:Reverse motion enabled
52
Mtr. Operating Motor rated current d30 - d120%
d100
Specifications
53
Motor no-load
d00 - d99%
d40
54
Torque Comp. Auto torque
d00 - d10
d02
Setting
compensation gain
55
Slip Comp.
Slip compensation
d0.0 - d10.0
d0.0
56
Specific Output Actual mtr. current
d00:Display actual motor current
d00
Display
or DC Bus voltage
d01:Display DC Bus voltage
57
AC Drive Rated Current Indicator
d##.#
58
Electronic
Select motor
d00:Active with standard motor
d02
Thermal
derating vs.
d01:Active with special motor
Overload Relay temperature curves d02:Inactive