7. d06: AC Drive Control Mode – The Multi-function Output Terminal contacts will be
"closed" when the AC drive operation is controlled by the external terminals.
8. d07: Fault Indicator – The Multi-function Output Terminal contacts will be
"closed" when a fault is detected.
9. d08: AC Drive Control Mode – The Multi-function Output Terminal contacts will be
"closed" when the output frequency equals the Desired Frequency attained (Pr.47).
10. d09: PLC Program Running – The Multi-function Output Terminal contacts will be
"closed" the PLC program is executing.
11. d10: PLC Program Step Completed – The Multi-function Output Terminal contacts
will be "closed" within 5 seconds when each multi-step speed is attained.
12. d11: PLC Program Completed Execution – The Multi-function Output Terminal
contacts will be "closed" within 5 secs. after the PLC program completes execution.
13. d12: PLC Program Execution Paused – The Multi-function Output Terminal contacts
will be "closed" when the PLC program execution is paused by a multi-function input
terminal that has been programmed to pause the drive operation.
14. d13: Terminal Count Reached – The Multi-function Output Terminal contacts will be
"closed" when the counter value is equeal to the value programmed by Pr.96.
15. d14: Preliminary Counter Value Reached – The Multi-function Output Terminal
contacts will be "closed" when the counter value equeals the value of Pr.97.
Multi-function terminals wiring example
Pr.47 Desired Frequency Attained
Factory Setting d0.0 Hz
Units 0.1 Hz
Parameter value d0.0 - d400.0 Hz
Used to select a specified frequency in increments of 0.1 Hz.
Multi-Function PHC
output terminals
Multi-Function indication
output terminals
Faults indication
Power indication
RA
RB
RC
MO1
MCM
AC/DC Power Source
AC 250V 2A
DC 30V 2A
PHC
48VDC 50mA
Plus terminal
Power 48VDC
50mA
Minus terminal
BZ
LT
LT
Pre-set freq. attained