46
ERC menu
code
Description
Defrost
dEF
Defrost Settings
Def . type
dFt
no: Defrost function is disabled
EL: Electrical or time defrost
Hgd: Hot gas defrost (contact Danfoss for details)
nat:Off-cycle defrost (natural defrost)
Def terminate temp
dtt
Temperature at which defrost cycle will stop
Def Min Interval
dii
The minimum time in hours between the start of each defrost cycle
Def Max Interval
dAi
The maximum time in hours between the start of each defrost cycle
Def Min Time
dit
The minimum duration of a defrost cycle in minutes
Def Max time
dAt
The maximum duration of a defrost cycle in minutes
Drip off time
dot
The duration in minutes of the drip-off time at the end of a defrost cycle
Fan delay after Defrost
Fdd
The duration in minutes before the fan starts after a defrost cycle
Fan start Temp
Ftd
The temperature at which the fan will start after a defrost
Defrost Fan on
dFA
Whether the fan will run during a defrost cycle
Initial Defrost Interval
idi
The number of hours after power-up before the first defrost cycle starts
Defrost on compressor
time
dCt
Whether the defrost cycles are measured by elapsed time (nO) or compressor run time (yES)
ERC menu
code
Description
Fan
FAn
Fan settings
Fan always On
FAo
nO: fan parameters below active . yES: Fan is always on
Fan On Delay
Fod
Delay in seconds before fan starts after compressor starts
Fan Stop delay
FSd
Delay in seconds before fan stops after compressor stops
Fan On Cycle
FoC
The number of seconds the fan runs when the compressor is off
Fan Stop Cycle
FSC
The number of seconds the fan does not run when the compressor is off
ERC menu
code
Description
Energy management
Eng
Energy Management
Shop Light Day
SLd
When ambient light is above this level, Eco mode is cancelled . Requires light sensor
Shop Light Night
SLn
When ambient light is below this level, Eco mode is enabled . Requires light sensor
Eco Activity delay
EAd
Minutes delay after last door opening until ECO mode is enabled; 0: disable
Eco Light delay
ELd
Delay [min] between detection of shop light on/off and ECO mode activation / suspension
Eco Temperature Offset
Eto
Temperature increase for Eco mode relative to normal mode
ERC
102 Reference manual – APPENDIX I: PARAMETER QUICK LIST