31
7.4 Defrost /
dEF
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
ERC menu
code
Default
Min
Max
Unit
Conv
Unit
Scale
Default Access
Shop Ser OEM
Defrost
dEF
Def type
dFt
no
no
Hgd
no
-- RW RW
Def reset temp
drt
5
0
80
C/F a
°C
1
-- RW RW
Def Min Interval
dii
6
0
96
no
hour
1
-- RW RW
Def Max Interval
dAi
7
0
96
no
hour
1
-- RW RW
Def Min Time
dit
5
0
240
no
min
1
-- RW RW
Def Max time
dAt
30
0
480
no
min
1
-- RW RW
Drip off time
dot
0
0
60
no
min
1
-- -- RW
Fan delay after Defrost
Fdd
0
0
60
no
min
1
-- -- RW
Fan start Temp
Ftd
25 .0/77 .0 -25 .0/13 .0 25 .0/77 .0
C/F a
°C/°F
.1
-- -- RW
Defrost Fan on
dFA
no
no
yES
no
1
-- -- RW
Initial Defrost Interval
idi
3
0
96
no
hour
1
-- -- RW
Initial Defrost Duration
idd
100
0
999
no
1
-- RW RW
Defrost on compressor
time
dCt
no
no
yES
no
1
-- -- RW
ERC
102 Reference manual – 7 PARAMETERS
Note:
ERC controllers feature Safe Defrost
functionality (patents pending) by de-
fault . This function ensures proper defrost
under poor power conditions .
For more details please contact Danfoss .