background image

Danfoss Heating Solutions

 

VIUHM602

 

© Danfoss    03/2011

14

6.1.5.1   2-pipe

Menu 

 Setup 

 Service 

 Heating/Cooling 

 2-pipe: 

Select 

2-pipe

 to configure auto-

matic heating/cooling for a 2-pipe system.

Heating/Cooling

Configuration

2-pipe

Change-over Low

22°C

Change-over High

26°C

Change

Back

Select 

Change-over Low

 or 

Change-over High

 to set change-over temperatures. Settings 

must be between 10 and 50°C with a min. difference of 4°C.

6.1.5.2   3-pipe (4-pipe)

Menu 

 Setup 

 Service 

 Heating/Cooling 

 3-pipe (4-pipe):

 

Select 

3-pipe (4-pipe)

 to 

configure automatic heating/cooling for a 3-pipe (4-pipe) system.

Heating/Cooling

Configuration

3-pipe

Mode

Heating

Master room

Living room

Neutral zone

2K

Number of outputs

2

Change

Back

•  Mode:

 Set the heating/cooling mode to 

Auto

Heating

 or 

Cooling

.

•  Master room:

 Select which room should be the Master room. Only rooms with a CF-RD 

room thermostat are listed and selectable.

•  Neutral zone:

 Set the Neutral zone parameter to 2K or 4K.

•  Number of outputs:

 Set number of outputs to 0, 2 or 4 (options for 2 and 4 outputs are 

only selectable, if all 2/4 outputs are connected to actuators and not already in use).
4 outputs on Master Controller must be configured as outputs for 3- and 4-pipe sys-
tems (if the system contains more Master Controllers, all outputs must be from Master 
Controller 1).
Outputs for 3- or 4-pipe systems are:

•  Output 1:

 Warm water supply (used in 3- and 4-pipe systems).

•  Output 2:

 Cooling water supply (used in 3- and 4-pipe systems).

•  Output 3:

 Warm water return (used in 4-pipe systems).

•  Output 4:

 Cooling water return (used in 4-pipe systems).

Instruction

 

CF-RC  Remote  Controller

Summary of Contents for 088U0221

Page 1: ...088U0221 GB Instruction CF RC Remote Controller...

Page 2: ...Danfoss Heating Solutions VIUHM602 Danfoss 03 2011 2 Instruction CF RC Remote Controller...

Page 3: ...Remote Controller has been installed 6 5 Menus 6 5 1 Rooms 6 5 1 1 Select room 6 5 1 2 Options 7 5 2 Program 7 5 2 1 Period program 7 5 2 2 Setback program 8 5 3 Setup 10 5 4 Alarms 11 6 Service Menu...

Page 4: ...h the up down and left right selectors in combination with the soft keys When the display back light is out the first touch of a button only activates this light 2 Installation 2 1 Preparations Instal...

Page 5: ...ll menu to create other names When the installation is finished a start up screen with actual time and date will be shown in the display The screen also shows actual temperature in the first room on t...

Page 6: ...the docking station to a 230 V power supply outlet by means of the trans former power supply plug Place Remote Controller in the docking station Note To extend the transmission range of the CF2 system...

Page 7: ...able if setback program is activated see chapter 5 2 2 Cooling Disable cooling function for the room option only available when Master Con troller is in cooling mode Heating cooling Set mode Select he...

Page 8: ...t all rooms are as signed to Zone 1 To move a room to a different zone just allocate it to the desired zone Example Kitchen is moved from Zone 1 to Zone 3 Zone 3 Add room Kitchen 1 Bath room 1 Living...

Page 9: ...n and left right selectors Confirm with Ok to activate an overview of the created program the days selected in the program are indicated by bold letters Program 1 S M T W T F S 00 06 12 18 24 Activate...

Page 10: ...nformation about the error causing the alarm and the time for its registration by the system This Alarm log saves the latest alarms for later access and easy system failure identification Start up scr...

Page 11: ...s as indi cated on the start up screen 16 14 Tue 26 July 05 Kitchen 20 0 C Status Alarm Menu This indication of Alarm on Remote Controller and the indication on Master Controller will continue until t...

Page 12: ...ator the system is automatically set to PWM regulation Mixed floor and radiator heating can be selected individually for separate rooms Activate Mode rooms to get a list of rooms and select type mode...

Page 13: ...is 5 min 6 1 5 Heating Cooling Menu Setup Service Heating Cooling Activate Heating Cooling to configure automatic heating cooling mode Select Change to get following configuration options Not used De...

Page 14: ...hange Back Mode Set the heating cooling mode to Auto Heating or Cooling Master room Select which room should be the Master room Only rooms with a CF RD room thermostat are listed and selectable Neutra...

Page 15: ...no delay Wireless delay Wireless no delay Change Back The following table list the relay options for different functions default value in Italic Function Relay Option Function Relay Option MC1 Pump No...

Page 16: ...s with Yes or discard the changes with No 7 Uninstallation Resetting CF RC Remote Controller fig 1 At the same time activate the Soft key 1 the soft key 2 and the down selector Remote Controller reque...

Page 17: ...test Link to Master Controller E12 The room thermostat in the indicated room has lost the wireless connection to Master Controller Low bat in Room T E13 The battery level of the room Thermostat for th...

Page 18: ...Danfoss Heating Solutions VIUHM602 Danfoss 03 2011 18 Instruction CF RC Remote Controller Fig 1 Fig 2...

Page 19: ...19 Danfoss 03 2011 VIUHM602 Danfoss Heating Solutions Instruction CF RC Remote Controller Fig 4 Fig 3...

Page 20: ...Danfoss Heating Solutions VIUHM602 Danfoss 03 2011 20...

Reviews: