![Danaher SERVOSTAR 300 Series Product Manual Download Page 21](http://html1.mh-extra.com/html/danaher/servostar-300-series/servostar-300-series_product-manual_504861021.webp)
6.2.3
Inputs / outputs
Analog inputs 1, 2 (resolution 14/12 bit)
V
±
10
Max. common-mode voltage
V
±
10
Digital control inputs
V
as per EN 61131-2 Type 1, max. 30VDC
Digital control outputs, active high
V
open Emitter, max. 30VDC, 10mA
BTB/RTO output, relay contacts
V
DC max. 30, AC max 42
mA
500
Auxiliary supply voltage, electrically isola-
ted, without brake/fan
V
20 - 30
A
1
Auxiliary supply voltage, electrically isola-
ted, with brake/fan (check voltage drop !)
V
24 (-0% +15%)
A
2.5
Min./max. output current to brake
A
0.15 / 1.5
Connection technology
Control signals
—
Combicon connector
Power signals
—
Combicon connector
Resolver input
—
SubD 9-pin (socket)
Incremental encoder input
—
SubD 15-pin. (socket)
PC interface, CAN
—
SubD 9-pin (plug)
Encoder emulation, ROD/SSI
—
SubD 9-pin (plug)
Connection technology
Control signals
Combicon connector
Power signals
Combicon connector
Resolver input
SubD 9-pin (socket)
Incremental encoder input
SubD 15-pin. (socket)
PC interface, CAN
SubD 9-pin (plug)
Encoder emulation, ROD/SSI
SubD 9-pin (plug)
6.2.4
Recommended tightening torques
Connector
Tightening torque
X0, X8, X9
0.5..0.6 Nm
Grounding bolt
3.5 Nm
6.2.5
Fusing
Internal fusing
Circuit
Internal fuse
Auxiliary voltage 24V
3.15 A (slow)
Regen resistor
electronic
External fusing
Wire fuses or similar
SERVOSTAR
303*, 341*, 343*
SERVOSTAR
306*, 310*, 346*
AC supply feed F
N1/2/3
(X0/1; 2; 3)
6 AT (FRx-6)
10 AT (FRx-10)
24V feed
F
H1/2
max. 8 AF (FRx-12)
Regen resistor F
B1/2
(X8/2; 4)
6 AT (FRS-6)
6 AT (FRS-6)
US fuses in brackets,
x = S or S-R for 480V applications
x = N or N-R for 230V applications
* order code reference see p. 15
20
SERVOSTAR
®
300 Product Manual
Technical description
10/2007
Danaher Motion