AIR CIRCULATION PIPES
Create air recirculation inside the structure that covers the insert for correct operation. This prevents the appliance from over-heating.
To guarantee this, just make one or more openings in the lower and upper parts of the covering.
The following measurements must be respected:
LOWER PART (COLD AIR INLET) WITH TOTAL MINIMUM SURFACE 550 CM².
UPPER PART (HOT AIR OUTLET) WITH TOTAL MINIMUM SURFACE 550 CM².
Reference A
Hot convection air 550 cm²
: The heat accumulated inside the
covering must be vented to prevent excessive overheating of the
insert.
Reference B
Forced ventilation:
The tangential fan distributes the heat developed by the insert
into the environment.
Reference C
Room air inlet 550 cm²:
To allow air recirculation an air inlet point must be envisioned,
which is preferably positioned in the lower part of the structure in
order to encourage convection. The air must be withdrawn from the
machine's working environment.
THE FLUE OUTLET PIPE MUST ALWAYS MAINTAIN A MINIMUM DISTANCE OF 50 MM FROM INFLAMMABLE PARTS.
IMPORTANT: ALL OPENINGS MADE FOR PROPER AIR RECIRCULATION MUST BE MADE INACCESSIBLE BY MEANS
OF APPROPRIATE PROTECTIVE GRILLES OR MESHES, ENSURING THE MINIMUM PASSAGE OF AIR REQUIRED.
Summary of Contents for INSERTO 700 2.0
Page 2: ...2 Applicare etichetta dati technici ...
Page 33: ...A B C E E E F F D F D D 33 ITALIANO ...
Page 64: ...A B C E E E F F D F D D 64 ENGLISH ...
Page 95: ...A B C E E E F F D F D D 95 FRANCAIS ...
Page 126: ...A B C E E E F F D F D D 126 DEUTSCH ...
Page 157: ...A B C E E E F F D F D D 157 ESPAÑOL ...
Page 163: ...163 ...