Operation
www.DaikinApplied.com 57
IOM 1274-3 • CENTRIFUGAL WATER CHILLERS
Table 20: Settings View - Interface
Table 21: Unit Interface Settings
Description
Default
Range
PW
Comments
BAS Network Protocol NONE
NONE, Local, Remote, MODBUS,
LONWORKS, BACnet IP, BACnet
Ethernet, BACnet MS/TP
M
NONE: No BAS network; MODBUS: RTU - RS485; LONWORKS: LONtalk - FTT-10A
BACnet IP: IP - Ethernet; BACnet Ethernet: Ethernet; BACnet MS/TP: RS485
NOTE:
It is likely that the chiller will contain the factory settings for date and time; therefore, it is important to verify or change
these settings when the chiller is first used on the job-site. Failure to do so will result in incorrectly labeled History files.
The version numbers shown are the controllers’ software identification. These numbers may be required by Daikin
Applied to answer questions about unit operation or to assist in possible future upgrades of software.
Figure 72: Trend History Screen