• VRV

®

 Systems • Indoor Units

3

• Indoor Units • SLIM CONCEALED CEILING UNIT • FXDQ-PBVE

1

Specifications

Notes

Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB,  outdoor temperature : 35°CDB,  

equivalent refrigerant piping : 7.5m (horizontal)

Nominal heating capacities are based on : indoor temperature : 20°CDB,  outdoor temperature : 7°CDB, 6°CWB,  

equivalent refrigerant piping : 7.5m (horizontal)

Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

External static pressure is changeable to set by the remote control; this pressure means : high static pressure - 

standard static pressure.

The operation sound levels are conversion values in anechoic chamber.  In practice, sound levels tend to be higher 

than the specified values due to ambient noise or reflection. When the suction place is changed to bottom suction, 

sound level will increase

1-2  ELECTRICAL SPECIFICATIONS 
(50HZ)

FXDQ20PBVE

FXDQ25PBVE

FXDQ32PBVE

Power Supply

Name

VE

Phase

1~

Frequency

Hz

50

Voltage

V

220-240

Current

Minimum circuit amps (MCA)

A

0.8

0.8

0.8

Maximum fuse amps (MFA) A

15

15

15

Full load amps (FLA)

A

0.6

0.6

0.6

Voltage range

Minimum

V

-10%

Maximum

V

+10%

Notes

Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below 

or above listed range limits.

Maximum allowable voltage range variation between phases is 2%.

MCA/MFA : MCA = 1.25 x FLA

MFA is smaller than or equal to 4 x FLA

Next lower standard fuse rating minimum 15A

Select wire size based on the MCA

Instead of a fuse, use a circuit breaker

1-3  ELECTRICAL SPECIFICATIONS 
(60HZ)

FXDQ20PBVE

FXDQ25PBVE

FXDQ32PBVE

Power Supply

Name

VE

Phase

1~

Frequency

Hz

60

Voltage

V

220

Current

Minimum circuit amps (MCA)

A

0.9

0.9

0.9

Maximum fuse amps (MFA) A

15

15

15

Full load amps (FLA)

A

0.7

0.7

0.7

Voltage range

Minimum

V

-10%

Maximum

V

+10%

Notes

Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below 

or above listed range limits.

Maximum allowable voltage range variation between phases is 2%.

MCA/MFA : MCA = 1.25 x FLA

MFA is smaller than or equal to 4 x FLA

Next lower standard fuse rating minimum 15A

Select wire size based on the MCA

Instead of a fuse, use a circuit breaker

1-1  TECHNICAL SPECIFICATIONS

FXDQ20PBVE

FXDQ25PBVE

FXDQ32PBVE

Summary of Contents for VRV-WII Series

Page 1: ...technical data Slim Concealed Ceiling Unit FXDQ PBVE air conditioning systems...

Page 2: ......

Page 3: ...air conditioning systems technical data Slim Concealed Ceiling Unit FXDQ PBVE...

Page 4: ......

Page 5: ...ications 50Hz 3 Electrical Specifications 60Hz 3 2 Safety device settings 4 3 Options 5 4 Capacity tables 6 Cooling capacity tables 6 Heating capacity tables 7 5 Dimensional drawing centre of gravity...

Page 6: ...te Cooling High high m min 8 0 8 0 8 0 High m min 7 2 7 2 7 2 Low m min 6 4 6 4 6 4 Fan External static pressure High Pa 30 30 30 Standard Pa 10 10 10 Motor Output high W 62 62 62 Drive Direct drive C...

Page 7: ...0 8 0 8 0 8 Maximum fuse amps MFA A 15 15 15 Full load amps FLA A 0 6 0 6 0 6 Voltage range Minimum V 10 Maximum V 10 Notes Voltage range units are suitable for use on electrical systems where voltag...

Page 8: ...emote control BRC2C51 Remote control for hotel use BRC3A61 Kit name FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE Central remote control DCS302CA51 Unified on off control DCS301BA5...

Page 9: ...3 6 2 2 16 0 1 9 1 6 2 3 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 4 2 2 3 5 2 2 18 0 1 9 1 6 2 3 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 4 2 2 3 5 2 2 20 0 1 9 1 6 2 3 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 4 2 2 3 4 2 2 21 0 1 9...

Page 10: ...9 16 7 17 0 2 1 2 1 2 0 2 0 2 0 2 0 14 7 15 0 2 2 2 2 2 2 2 2 2 2 2 1 12 6 13 0 2 3 2 3 2 3 2 3 2 3 2 3 10 5 11 0 2 4 2 4 2 4 2 4 2 4 2 4 9 5 10 0 2 5 2 4 2 4 2 4 2 4 2 4 8 5 9 1 2 5 2 5 2 5 2 5 2 5 2...

Page 11: ...500 All around 16 4 7 hole All around Suspension bolt pitch Suspension bolt 4 M8 M10 14 M4 Holes All around 16 M4 Holes 700 Service space of installation box for adaptor PCB NOTES 1 In case of back s...

Page 12: ...Indoor Units SLIM CONCEALED CEILING UNIT FXDQ PBVE 1 5 VRV Systems Indoor Units 8 5 Dimensional drawing centre of gravity 5 2 Centre of gravity FXDQ20 25 32PB 4D049300D...

Page 13: ...ems Indoor Units 9 Indoor Units SLIM CONCEALED CEILING UNIT FXDQ PBVE 6 Piping diagram FXDQ20 25 32PB FXDQ40 50 63NB 4D060927 Gas side Liquid side Electronic expansion valve Filter Filter Indoor heat...

Page 14: ...1C Z2C Noise filter ferrite core C1 Capacitor M1F R2T Thermistor coil 1 Wired remote control F1U Fuse F5A 250V R3T Thermistor coil 2 R1T Thermistor air HAP Light emitting diode service monitor green S...

Page 15: ...WD Heating Return air temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB 3 Measuring place Anechoic chamber 4 Location of microphone 5 The operation condition is external static pressure 1...

Page 16: ...e h i g h E S P Lower limit of external static pressure high ESP Low standard ESP Low high ESP High high ESP Air flow rate m3 min External static pressure NOTES 1 The remote control can be used to swi...

Page 17: ......

Page 18: ...ed therein Specifications are subject to change without prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related...

Reviews: