SiE33-102
Field Wiring
Installation Manual
155
7.4
Power Circuit and Cable Requirements
A power circuit (See table below) must be provided for connection of the unit. This circuit must be protected
with the required safety devices, i.e. a main switch, a slow blow fuse on each phase and an earth leak
detector.
When using residual current operated circuit breakers, be sure to use a high-speed type 200mA rated
residual operating current.
Note:
Select the power supply cable in accordance with relevant local and national regulations.
Phase and
Frequency
Voltage
Recommended
Fuses
Transmission
Line Selection
RSXY16KAY1
3N~50Hz
380-415V
45A
0.75-1.25mm
²
RSXY18KAY1
3N~50Hz
380-415V
50A
0.75-1.25mm
²
RSXY20KAY1
3N~50Hz
380-415V
60A
0.75-1.25mm
²
RSXY24KAY1
3N~50Hz
380-415V
60A
0.75-1.25mm
²
RSXY26KAY1
3N~50Hz
380-415V
70A
0.75-1.25mm
²
RSXY28KAY1
3N~50Hz
380-415V
70A
0.75-1.25mm
²
RSXY30KAY1
3N~50Hz
380-415V
70A
0.75-1.25mm
²
Phase and
Frequency
Voltage
Recommended
Fuses
Transmission
Line Selection
RSXY16KAYAL
3N~60Hz
380V
45A
0.75-1.25mm
²
RSXY18KAYAL
3N~60Hz
380V
50A
0.75-1.25mm
²
RSXY20KAYAL
3N~60Hz
380V
60A
0.75-1.25mm
²
RSXY24KAYAL
3N~60Hz
380V
60A
0.75-1.25mm
²
RSXY26KAYAL
3N~60Hz
380V
70A
0.75-1.25mm
²
RSXY28KAYAL
3N~60Hz
380V
70A
0.75-1.25mm
²
RSXY30KAYAL
3N~60Hz
380V
80A
0.75-1.25mm
²