SiE33-102
Test Operation
General Information
89
4.13
Centralized Control Group No. Setting
BRC1A51·52
If carrying out centralized control by central remote control or unified ON/OFF control, group No. must
be set for each group individually by remote control.
Group No. setting by remote control for centralized control
1. When in the normal mode, push the
button for 4 seconds or more, and operation then enters
the “field setting mode.”
2. Set mode No. “00” with the
button.
∗
3. Push the
button to inspect the group No. display.
4. Set the group No. for each group with the
button (The group No. increases in the manner of 1-00,
1-01, ...,1-15, 2-00,...4-15. However, the unified ON/OFF control displays only the group No. within
the range selected by the switch for setting each address.)
5. Push the timer
button to define the selected group No.
6. Push the
button to return to the normal mode.
Even if not using a remote control, connect the remote control when setting the group No., set the group
No. for centralized control, and disconnect after making the setting.
Set the group No. after turning on the power supply for the central remote control, unified ON/OFF
control, and indoor unit.
BRC7A Type
Group No. setting by infrared remote for centralized control
1. When in the normal mode, push
button for 4 seconds or more, and operation then enters the
“field set mode.”
2. Set mode No. “00” with
button.
3. Set the group No. for each group with
button (advance/backward).
4. Enter the selected group numbers by pushing
button.
5. Push
button and return to the normal mode.
BRC7A Type