SiE33-102
Appendix
General Information
99
Between outdoor unit and first branch kit (C)
Between branches kit (D)
Applicable Model
Pipe Size (out. dia.
×
min. wall thickness)
Liquid Pipe
Gas Pipe (main)
RXY16KA
φ
15.9
×
t1.0
φ
34.9
×
t1.3
RXY18~20KA
φ
19.1
×
t1.0
φ
34.9
×
t1.3
RXY24KA
φ
19.1
×
t1.0
φ
41.3
×
t1.7
RXY26~30KA
φ
22.2
×
t1.2
φ
41.3
×
t1.7
Total Capacity Index of Indoor
Unit after Branch
Pipe Size (out. dia.
×
min. wall thickness)
Liquid Pipe
Gas Pipe
Below 100
φ
9.5
×
t0.8
φ
15.9
×
t1.0
100 to below 160
φ
9.5
×
t0.8
φ
19.1
×
t1.0
160 to below 330
φ
12.7
×
t0.8
φ
25.4
×
t1.2
330 to below 480
φ
15.9
×
t1.0
φ
34.9
×
t1.3
480 to below 640
φ
19.1
×
t1.0
φ
34.9
×
t1.3
640 and over
φ
19.1
×
t1.0
φ
41.3
×
t1.7
Si33-102.book Page 99 Tuesday, June 26, 2001 3:18 PM