background image

English

ii

 CAUTION

• 

Do not touch the switch with wet fingers. Touching a switch 
with wet fingers can cause electric shock.

•  Do not allow children to play on or around the unit to 

prevent injury.

•  Do not touch the refrigerant pipes during and immediately 

after operation as the refrigerant pipes may be hot or 

cold, depending on the condition of the refrigerant flow

-

ing through the refrigerant piping, compressor, and other 
refrigerant cycle parts. Your hands may suffer burns or 
frostbite if you touch the refrigerant pipes. To avoid injury, 
give the pipes time to return to normal temperature or, if 
you must touch them, be sure to wear proper gloves.

• 

Heat exchanger fins are sharp enough to cut. To avoid 
injury wear gloves or cover the fins when working around 

them.

•  Close the front panels when charging refrigerant or during 

operation as the fusible plug may blow off, spewing refrig-
erant.

•  Install drain piping to proper drainage. Improper drain pip-

ing may result in water leakage and property damage.

•  Insulate piping to prevent condensation.
•  Be careful when transporting the unit.
•  Do not turn off the power supply immediately after stop-

ping operation. Always wait for at least 5 minutes before 
turning off the power supply. Otherwise, water leakage 
may occur.

•  Do not use a charging cylinder. Using a charging cylinder 

may cause the refrigerant to deteriorate.

•  Refrigerant R410A in the system must be kept clean, dry, 

and tight.
(a)  Clean and Dry - Foreign materials (including mineral 

oils such as SUNISO oil or moisture) should be pre-
vented from getting into the system.

(b)  Tight - R410A does not contain any chlorine, does 

not destroy the ozone layer, and does not reduce the 
earth’s protection again harmful ultraviolet radiation. 
R410A can contribute to the greenhouse effect if it is 
released. Therefore take proper measures to check 
for the tightness of the refrigerant piping installation. 
Read the chapter Refrigerant Piping and follow the 
procedures.

•  Since R410A is a blend, the required additional refriger-

ant must be charged in its liquid state. If the refrigerant is 
charged in a gaseous state, its composition can change 
and the system will not work properly.

•  The indoor unit is for R410A. See the catalog for indoor 

models that can be connected. Normal operation is not 
possible when connected to other units.

•  Handheld remote controller (wireless kit) transmitting 

distance can be shorter than expected in rooms with 
electronic fluorescent lamps (inverter or rapid start types). 
Install the indoor unit far away from fluorescent lamps as 

much as possible.

•  Indoor units are for indoor installation only. Outdoor units 

can be installed either outdoors or indoors.

•  Do not install the air conditioner or heat pump in the fol-

lowing locations:
(a)  Where a mineral oil mist or oil spray or vapor is pro-

duced, for example, in a kitchen.

Plastic parts may deteriorate and fall off or result in 
water leakage.

(b)  Where corrosive gas, such as sulfurous acid gas, is 

produced.
Corroding copper pipes or soldered parts may result 
in refrigerant leakage.

(c)  Near machinery emitting electromagnetic waves.

Electromagnetic waves may disturb the operation of 

the control system and cause the unit to malfunction.

(d) 

Where flammable gas may leak, where there is car

-

bon fiber, or ignitable dust suspension in the air, or 
where volatile flammables such as thinner or gasoline 

are handled. Operating the unit in such conditions 

may result in a fire.

•  Take adequate measures to prevent the outdoor unit from 

being used as a shelter by small animals. Small animals 
making contact with electrical parts may result in malfunc-

tions, smoke, or fire. Instruct the customer to keep the 

area around the unit clean.

• 

This product is designed for installation at a max altitude 

of 10500 ft. (3200 m) above sea level or a min altitude of 
-184 ft. (-56 m) below sea level.

 NOTE

•  Install the power supply and transmission wires for the in-

door and outdoor units at least 3.5 ft. (1 m) away from tele

-

visions or radios to prevent image interference or noise. 

Depending on the radio waves, a distance of 3.5 ft. (1 m) 
may not be sufficient to eliminate the noise.

•  Dismantling the unit, treatment of the refrigerant, oil and 

additional parts must be done in accordance with the 
relevant local, state, and national regulations.

•  Do not use the following tools that are used with con-

ventional refrigerants: gauge manifold, charge hose, gas 

leak detector, reverse flow check valve, refrigerant charge 

base, vacuum gauge, or refrigerant recovery equipment.

•  If the conventional refrigerant and refrigerator oil are 

mixed in R410A, the refrigerant may deteriorate.

•  This air conditioner or heat pump is an appliance that 

should not be accessible to the general public.

•  As design pressure is 580 psi (4.0 MPa), the wall thick-

ness of field-installed pipes should be selected in accor

-

dance with the relevant local, state, and national regula-
tions.

Codes and Regulations

This product is designed and manufactured to comply with 
national codes. Installation in accordance with such codes 
and/or prevailing local codes/regulations is the responsibility 
of the installer. The manufacturer assumes no responsibility 
for equipment installed in violation of any codes or regula-
tions. Rated performance is achieved after 72 hours of opera-
tion. 

Make sure to use a DAIKIN specified checker while measur

-

ing sub cooling. Do not use the check valve or the other port 
to measure it.

01_EN_PL_VRV6_HP_IM.indd   2

01_EN_PL_VRV6_HP_IM.indd   2

2022/12/08   17:53:31

2022/12/08   17:53:31

Summary of Contents for VRV RXYQ72AATJ Series

Page 1: ...aikinac com content resources manuals for the most current version of installation instructions In the event of conflicting information the online installation instruction is to be used Veuillez visit...

Page 2: ...rdance with this in stallation manual Improper installation may result in water leakage electric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentrat...

Page 3: ...tdoors or indoors Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist or oil spray or vapor is pro duced for example in a kitchen Plastic parts may d...

Page 4: ...ping length limitations 12 8 Precautions on refrigerant piping 17 8 1 Caution for brazing 17 8 2 Connecting the refrigerant piping 17 8 3 Guidelines for handling stop valve 21 9 Field wiring 21 9 1 Po...

Page 5: ...YQ 120 240 single modules as indicated 72 96 120 144 168 192 216 240 RXYQ72AATJ AAYD 1 RXYQ96AATJ AAYD 1 RXYQ120AATJ AAYD 1 RXYQ144AATJ AAYD 1 RXYQ168AATJ AAYD 1 RXYQ192AATJ AAYD 1 RXYQ216AATJ AAYD 1...

Page 6: ...ype Outdoor unit Total capacity index of indoor units RXYQ72AATJ AAYD 36 93 RXYQ96AATJ AAYD 48 124 RXYQ120AATJ AAYD 60 156 RXYQ144AATJ AAYD 72 187 RXYQ168AATJ AAYD 84 218 RXYQ192AATJ AAYD 96 249 RXYQ2...

Page 7: ...strong enough to support the weight of the unit Installation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for main...

Page 8: ...n the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will disturb the operation of the unit If...

Page 9: ...olt holes 9 16 15 7 8 22 5 oblong holes 4 2 Pitch of foundation bolt holes 30 3 16 766 42 3 8 1076 62 7 16 1586 3 Pitch of foundation bolt holes 28 7 16 29 722 737 4 2 7 16 62 5 2 7 16 62 6 30 1 8 765...

Page 10: ...2 or more Service space h1 2 or more h1 b Service space 2 a 59 1 16 in 1500 mm b 19 11 16 in 500 mm In case of an installation site where sides A B C D have obsta cles the wall heights of sides A C ha...

Page 11: ...n to the position of the unit s center of gravity NOTE Use a belt sling of 13 16 in 20 mm wide that adequately bears the weight of the unit CAUTION Lift the unit with caution as the unit s center of g...

Page 12: ...Q192 240 type 62 7 16 in 1586 mm 8 Distance between foundation bolt holes RXYQ72 type 15 1 16 in 383 mm RXYQ96 168 type 21 3 16 in 538 mm RXYQ192 240 type 31 1 4 in 793 mm 9 1 Hole for foundation bolt...

Page 13: ...mplies with national and local laws For piping work follow the maximum tolerated length difference in height and length after a branch indicated in the 7 5 System piping length limitations on page 12...

Page 14: ...g between BP unit and Mini split indoor unit G Only in case Mini split indoor units are connected Indoor unit capacity index Gas pipe Liquid pipe 07 09 12 3 8 in 9 5 mm 1 4 in 6 4 mm 15 1 2 in 12 7 mm...

Page 15: ...downstream of REFNET headers Indoor unit total capacity at REFNET joints accord ing to the REFNET header are as follows REFNET joint Downstream of REFNET joint Indoor unit REFNET header Indoor unit R...

Page 16: ...xample 2 2 1 a b c d j i A 1 2 3 4 5 6 7 8 H2 e f g h H1 Example 1 2 2 a t s H3 b c d j i A 1 2 3 4 5 6 7 8 H2 e f g h H1 Example 2 2 2 Branch with REFNET header a c b d e f i g h 1 2 3 4 5 6 7 8 H1 H...

Page 17: ...1 4 in 31 8 mm 1 RXYQ168 216A type 5 8 in 15 9 mm 3 4 in 19 1 mm RXYQ240A type Increase is NOT allowed RXYQ264 336A type 1 3 8 in 34 9 mm 1 1 2 in 38 1 mm 1 3 4 in 19 1 mm 7 8 in 22 2 mm RXYQ360 480A...

Page 18: ...m 33 ft 10 m 540 ft 165 m See 2 35 Height difference setting on page 38 2 49 Height difference setting on page 39 Table C Refrigerant charge limits when 295 H1 361 Outdoor unit capacity type Additiona...

Page 19: ...ndoor unit 8 The nearest indoor unit 1 a b c d e f g p a h 130 ft 40 m 7 5 3 System containing VRV indoor units and Mini split indoor units System setup H5 H4 a c f e h H1 BP1 6 i j g b d A B 7 k l BP...

Page 20: ...eak Use Dry Nitrogen to perform a gas leak detection After cutting the slit holes it is recommended to remove burrs in the slit holes and paint the edges and areas around the edges using the repair pa...

Page 21: ...12 Field piping 13 Gas flow 14 Stop valve service port A Valve A B Valve B 3 Recover gas and oil from the pinched piping by using a recovery unit CAUTION Do not vent gases into the atmosphere 4 When...

Page 22: ...onnection from the stop valves to the field piping can be done by us ing accessory pipes supplied as accessory NOTE Make sure that the onsite piping does not come in contact with other piping the bott...

Page 23: ...r REFNET header for multiple connections of indoor units and others other than outdoor units REFNET joint Mount the REFNET joint so that it branches either horizontally within 30 or vertically 3 0 Hor...

Page 24: ...ield wiring and components must be installed by a licensed elec trician and must comply with relevant local and national regulations Be sure to use a dedicated power circuit Never use a power supply s...

Page 25: ...AWG18 16 AWG18 16 AWG18 16 AWG18 16 AWG18 16 RXYQ72AAYD RXYQ96AAYD RXYQ120AAYD RXYQ144AAYD RXYQ168AAYD RXYQ192AAYD RXYQ216AAYD RXYQ240AAYD RXYQ264AAYD RXYQ288AAYD RXYQ312AAYD RXYQ336AAYD RXYQ360AAYD...

Page 26: ...ire 7 To outdoor unit of other system 8 Use duplex wires No polarity 9 Indoor unit The outdoor unit that connect the transmission wiring to an indoor unit is Master unit of the multi system And the ot...

Page 27: ...ircuit board of the master unit The outdoor unit that connects transmission wiring to indoor unit is the master unit The others are sub unit 9 5 Power wiring connection procedure Be sure to connect th...

Page 28: ...er and trans mission wiring using the included clamp Wire so that the ground wiring does not come into contact with the compressor lead wiring If they touch this may have an adverse effect on other de...

Page 29: ...the front panel of the outdoor unit for details on the location of the service port see the figure below R410A Label See 14 3 Method for adding refrigerant on page 31 for details on handling the stop...

Page 30: ...riorated Measure the insulation and check the insulation is above regular value in accordance with relevant local and national regulations For those doing pipe work 1 Make sure piping size is correct...

Page 31: ...ndication as indicated When above situation cannot be confirmed after 12 minutes the error code can be checked on the indoor unit user interface and the outdoor unit segment display Solve the error co...

Page 32: ...return to the default situation when shipped from factory 13 2 2 Operating the DIP switches By operating the DIP switches it is possible to What to do with DIP switch DS1 1 Cool Heat selector refer t...

Page 33: ...0 kg unit RXYQ 120A type 0 0 lbs unit 0 0 kg unit RXYQ 144A type 3 4 lbs unit 1 5 kg unit RXYQ 168A type 3 9 lbs unit 1 8 kg unit RXYQ 192A type 18 5 lbs unit 8 4 kg unit RXYQ 216A type 18 7 lbs unit...

Page 34: ...15 4 Test opera tion on page 43 R Q You want to execute automatic refrigerant charge B A Step 4b 5 Manual refrigerant charging method in cooling operation NO YES Step 4b 5 Automatic refrigerant charg...

Page 35: ...on to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a siphon tube or not Charge the liquid refrigerant with the cylinder in upright positio...

Page 36: ...step is included in below procedure This step can be skipped charging will take longer in such a case Follow the steps as described below and take into account whether you want to use the automatic ch...

Page 37: ...ge or E 3 in case the out door temperature is out of range In this case when the additional refrigerant charging was not finished step 6A has to be repeated INFORMATION When a malfunction is detected...

Page 38: ...s applicable DANGER ELECTRICAL SHOCK See Safety considerations on page i 15 1 Checks before initial start up After the installation of the unit first check the following items Once all below checks ar...

Page 39: ...tion of the unit compared to nominal operating conditions Power consumption limitation can be set in mode 2 There are two methods to activate power consumption limitation of the outdoor unit system T...

Page 40: ...rcuit Standard 2 Eco mode active by demand terminal short circuit 2 C short circuit Low 3 C short circuit Standard Eco mode can be activated by short circuit the terminal on External control adaptor O...

Page 41: ...conditions when an external signal is sent to the unit this setting defines the level power consumption limitation that will be applied for step 1 The level is according to the table Default value 3...

Page 42: ...n and advice about the effect of these settings see 15 3 Energy saving and optimum operation on page 41 2 83 Master user interface allocation in case VRV indoor units and Mini split indoor units are u...

Page 43: ...ump lockout release differential Heat pump would be resumed when the outdoor ambient temp is recovered by differential below above the Heat Pump Lockout Temp Value 2 47 Fahrenheit F Celsius C 0 5 2 8...

Page 44: ...n nected indoor unit type E g when your system is operating in heating you do not need as much heating under high outdoor ambient temperatures e g 68 F 20 C as under low outdoor ambient temperatures e...

Page 45: ...of cooling operation the evaporating temperature is allowed to go down to 43 F 6 C on temporary base depending on the situation In case of heating operation the condense temperature is allowed to go u...

Page 46: ...r purge etc See installation manual of the indoor units for details CAUTION Do not insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will caus...

Page 47: ...5 seconds or more The unit will start test operation The test operation is automatically carried out the outdoor unit display will indicate 01 and the indication Test operation and Under centralized c...

Page 48: ...A8P X8A Check connection on printed circuit board or actuator 26 27 Electronic expansion valve malfunction Y4E A1P X25A Check connection on printed circuit board or actuator 29 34 Electronic expansion...

Page 49: ...A Check connection on printed circuit board or actuator 07 09 High pressure sensor malfunction short circuit S1NPH A1P X32A Check connection on printed circuit board or actuator JC 06 08 Low pressure...

Page 50: ...ch R407C Mini split etc Check if other indoor units have malfunction and con firm indoor unit mix is allowed 18 20 Wrong combination different series e g RXYQ and REYQ or different type e g A type and...

Page 51: ...ester 3 White connector 3 To prevent damaging the printed circuit board touch a noncoated metal part to eliminate static electricity before pulling out or plug ging in connectors 4 Pull out junction c...

Page 52: ...directly related to the humanly occupied space in to which it could leak The unit of measurement of the concentration is lbs ft 3 kg m3 the weight in lbs kg of the refrigerant gas in 1 ft 3 1 m3 volu...

Page 53: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P657316 2F EM22A039 2212 SP 00_CV_VRV6_HP_IM indd 2 00_CV_VRV6_HP_IM indd 2 2022 12 14 18 06 05 2022 12 14 18 06 05...

Reviews: