24
English
•
Pass the transmission wiring through the rubber sleeve and fix with
a clamp to prevent water and dust from entering the control box.
In the control box
clamp (accessory)
rubber sleeve
How to pass wire through the rubber sleeve:
1
Remove the rubber sleeve
(detachable portion).
2
Place the wire.
3
Attach the rubber sleeve
(detachable portion).
Attach by inserting the
control box edge into the
slit of the rubber sleeve.
control box edge
4
Fix with a clamp.
•
Outside the units, the transmission wiring must be finished simulta
-
neously with the local refrigerant piping, and wound with tape (field
supply) as shown in the figure below.
1
2
3
3
4
5
1
2
3
3
4
5
1
Gas pipe
2
Liquid pipe
3
Insulation material
4
Finishing tape
5
Transmission wiring
• For multi system:
1
Transmission wiring between outdoor units in the same piping
system must be connected to terminals X4 and X5.
Connecting the wires to the X2, X3 terminals results in system
malfunction.
2
Wiring to other systems should be connected to terminals X2 and
X3 on the printed circuit board of the master unit. The outdoor unit
that connects transmission wiring to indoor unit is the master unit.
The others are sub unit.
9.5. Power wiring connection procedure
• Be sure to connect the power supply wiring to the power supply ter-
minal block, pass each phase (L1- 3) wire through separate rubber
sleeves and fix with the included clamps.
• Fix the ground wiring with the included clamp by taking care not to
apply external pressure on the terminal area.
• Pass the power supply wiring and ground wiring through their
respective rubber sleeve and fix with the included clamps to prevent
water from entering the control box.
8
1
2
3
4
9
6
5
7
1
Power supply
(MODEL AATJ
*
: 3-208/230V 60 Hz)
(MODEL AAYD
*
: 3-460V 60 Hz)
2
Branch switch, Overcurrent breaker
3
Ground wire
4
Control box
5
Insulation sleeves
6
Power supply terminal block
7
Ground terminal
8
Clamp (accessory)
9
Rubber sleeve
How to pass wire through the rubber sleeve:
1
Remove the rubber sleeve (detachable portion).
2
Place the wire.
3
Attach the rubber sleeve (detachable portion).
Attach by inserting the control box edge into the slit of the rubber
sleeve.
control box edge
01_EN_Main_VRV6_HP_IM.indd 24
01_EN_Main_VRV6_HP_IM.indd 24
2022/11/17 16:07:30