![Daikin VRV RXYQ72AATJ Series Installation Manual Download Page 43](http://html1.mh-extra.com/html/daikin/vrv-rxyq72aatj-series/vrv-rxyq72aatj-series_installation-manual_4705166043.webp)
40
English
[2-52]= AUX heater max allowable temp release differential
AUX Heater is not allowed to energize when the outdoor
ambient temp is recovered by differential (below) above the
AUX Heater Max Allowable Temp.
Value
[2-52]
Fahrenheit (
°F)
Celsius (
°C)
0
5
2.8
1
10
(default)
5.6 (default)
2
15
8.3
15.2.4. Heat pump lockout
• Control logic to provide more application options for cold climates.
• Outside temperature can now be measured directly from the out-
door unit coil sensor.
• This heat pump system can also be programed to automatically
switch to emergency heat is there is a system fault.
Item
Description
Min
Max
Increments
Heat Pump
Lockout Temp
Below this tempera-
ture, heat pump is
locked out.
− 15°F
(-26.1°C)*
50°F
(10°C)
5°F
(2.8°C)
Heat Pump
Lockout
Release dif-
ferential
When the outdoor
temp is recovered by
this temp, heat pump
is resumed.
5°F (2.8°C)
10°F (5.6°C)*
15°F (8.3°C)
* Default
[2-16]= AUX heater setting (Type
I
)
Value
[2-16]
AUX heater
Description
0
OFF
Function not active
1
ON
Heat-pump heating is always locked out
Value
[2-16]
Actions
Shorted
between
Heating Thermo-on Heating Thermo-off
AUX
heater
Indoor
fan
AUX
heater
Indoor
fan
0
−
−
−
−
−
1
−
ON
ON
(H/L)
OFF
LL
[2-37]= AUX heater setting (Type
II
)
Value
[2-37]
Controlling mode
Description
1
Mode 1
Lockout is controlled by ABC
terminals
2
Mode 2 *
3
Mode 3
Lockout is controlled by the
outdoor ambient tempera-
ture and setpoint which is
configured by the field set
-
ting 2-47 and 2-65
4
Mode 4
5
Mode 5
6
Mode 6
* For a heater which doesn’t need airflow
Value
[2-37]
Actions
Shorted
between
Heating Thermo-on Heating Thermo-off
AUX
heater
Indoor
fan
AUX
heater
Indoor
fan
1
A-C
ON
ON
(H/L)
OFF
LL
B-C
OFF
2
A-C
LL
LL
B-C
LL
OFF
3
Same as 2-37 = Mode 1 & A-C shorted
4
Same as 2-37 = Mode 1 & B-C shorted
5
Same as 2-37 = Mode 2 & A-C shorted
6
Same as 2-37 = Mode 2 & B-C shorted
[2-47]= Heat pump lockout release differential
Heat pump would be resumed when the outdoor ambient
temp is recovered by differential (below) above the Heat
Pump Lockout Temp.
Value
[2-47]
Fahrenheit (
°F)
Celsius (
°C)
0
5
2.8
1
10 (default)
5.6 (default)
2
15
8.3
When HP lockout mode has been set the auto backup func-
tion will automatically be set. This will allow the auxiliary or
secondary heat source to be automatically energized in the
event of a system failure.
Error codes capable of auto backup are listed in the table below.
Please be aware that the error codes that are not listed do
not auto backup in order to protect the unit.
Error contents
Error code
(Auto
backup
possible)
Actuation of high pressure switch
E3
Actuation of low pressure sensor
E4
Inv. compressor motor lock
E5
Compressor damage alarm
E6
Outdoor unit fan motor abnormality
E7
Electronic expansion valve coil abnormality
E9
Position signal abnormality of outdoor unit
fan motor
H3
H7
Outdoor air thermistor (R1T) abnormality
H9
Discharge pipe temperature abnormality
F3
Wet alarm
F4
Discharge pipe thermistor (R13T, R15T) and
compressor surface temperature thermistor
(R14T, R16T) abnormality
J3
Suction pipe thermistor (R5T) abnormality
J5
Heat exchanging deicer thermistor (R3T,
R10T) and heat exchanger gas pipe therm-
istor (R11T, R12T) abnormality
J6
Liquid temperature sensor (after subcool HE)
malfunction (R7T, R8T)
J7
Heat exchanger liquid pipe thermistor (R2T,
R9T) abnormality
J8
Subcooling heat exchanger gas pipe therm-
istor (R6T) and E.BOX Air cooling pipe
thermistor (R4T) abnormality
J9
High pressure sensor abnormality
JA
Low pressure sensor abnormality
JC
Inverter PCB abnormality
L1
Reactor temperature rise abnormality
L3
Inverter radiation fin temperature rise
abnormality
L4
Inv. compressor instantaneous overcurrent
L5
Inv. compressor overcurrent
L8
Inv. compressor startup abnormality
L9
Transmission error between inverter and
control PCB
LC
01_EN_Main_VRV6_HP_IM.indd 40
01_EN_Main_VRV6_HP_IM.indd 40
2022/11/17 19:51:21
2022/11/17 19:51:21