background image

English

3

2-1 Combination

The indoor units can be installed in the following range.

Be sure to connect a dedicated indoor unit. See the catalog for 
indoor unit models which can be connected.

• Total capacity/quantity of indoor units

Outdoor unit

Total capacity of indoor units

 

Total quantity of indoor units

RXTQ60 type................ 8.35~21.7kW 

  9 units

28.5~74.1 MBh

2-2 Standard operation limit

Normal operation

The figures below assume following operating conditions for indoor and 
outdoor units:

Equivalent pipe length .................................................... 25ft. (7.6m)
Level difference.................................................................... 0ft. (0m)

Cooling

Heating

Range for operation
Range for pull down operation
Range for warming up operation

2-3 Standard supplied accessories

Make sure that the accessories shown below are all present. 
(The accessories can be found behind the front panel.)

(Refer to figure 1)

1.

Accessories

2.

Screw for front panel

3.

Front panel

2-4 Option accessory

Refrigerant branching kit

* See “

7. PRECAUTIONS ON REFRIGERANT PIPING

” for details 

on how to connect refrigerant branch kits and how many are 
needed.

3.

BEFORE INSTALLATION

<Transporting the Unit>

As shown in figure 2, bring the unit slowly. (Take care not to let hands or 
things come in contact with rear fins.)

(Refer to figure 2)

1.

Air outlet grille

2.

Intake hole

3.

Corner

4.

Outdoor unit

5.

Handle

6.

Front

7.

Rear

8.

Always hold the unit by the corners, as holding it by the side 
intake holes on the casing may cause them to deform.

Use only accessories and parts which are of the designated specifica-
tion when installing.

4.

SELECTING INSTALLATION SITE

(1) Select an installation site where the following conditions are 

satisfied and that meets with your customer’s approval.

• Places which are well-ventilated.
• Places where the unit does not bother next-door neighbors.
• A locations where small animals will not make nests in the unit.
• Safe places which can withstand the unit’s weight and vibration and 

where the unit can be installed level.

• A locations where there is enough space to install the unit.
• Places where the indoor and outdoor unit’s piping and wiring 

lengths come within the allowable ranges.

• A location where there is no risk of flammable gas leaking. 

(2) If the unit is installed in a location where it might be exposed to 

strong wind, install as per figure 3.

• 11 mph (5 m/s) or higher winds blown against the outdoor unit’s 

exhaust cause a deterioration in the system performance. High 
winds force re-circulation of the exhaust air into the inlet, which is 
known to cause the following effects:

• Reduction in performance.
• Increased frost formation in heating mode.
• System shut down due to increased pressures.

• If very strong wind blows continuously on the air outlet side of the 

outdoor unit, the fan may turn in reverse at high speed and break, 
so install as per figure 3.

(Refer to figure 3)

1.

Turn the air outlet side toward the building’s wall, fence or 
windbreak screen.

2.

Air inlet grille

3.

Ensure there is enough space for installing the unit.

4.

Set the outlet side at a right angle to the direction of the 
wind.

5.

Strong wind

6.

Blown air

Name

Operation 

manual

Clamp

Conduit mounting plate

Quantity

1

4 pcs.

2 pcs.

2 pcs.

Shape

Name

Gas side acces-

sory piping

Insulation tube

Installation 

manual

Quantity

1 pc.

1 pc.

1 pc.

1

Shape

67

(19)

57.2
(14)

77

(25)

50

(10)

23(–5)

82.4
(28)

Outdoor temperature °FDB (°CDB)

95(35)

122(50)

Indoor temperature 

°FWB (°CWB)

Rated 
cooling 
capacity

41(5)

–4(–20)

50

(10)

68

(20)

43(6)

80.6

(27)

59

(15)

Outdoor temperature °FWB (°CWB)

60(15.5)

Rated 
heating 
capacity

Indoor temperature 

°FDB (°CDB)

(Large)

(Small)

REFNET joint

KHRP26A22T9

REFNET header

KHRP26M22H9

KHRP26M33H9

01_EN_3P591321-1B.fm  3 ページ  2019年12月24日 火曜日 午後5時19分

Summary of Contents for VRV IV-S Series

Page 1: ...nglish Fran ais Installation manual VRV IV S System air conditioner Manuel d installation Conditionneur d air VRV IV S System Espa ol Manual de instalaci n Acondicionador de aire con sistema VRV IV S...

Page 2: ...more 20 500 or less inch mm 40 1000 or more 40 1000 or more 20 500 or less 12 300 or more 8 200 or more 4 100 or more 4 100 or more figure 5 figure 6 1 2 3 4 20 500 or more 20 500 or less 20 500 or m...

Page 3: ...or more 8 200 or more 4 100 or more inch mm 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more L H A 60 1500 or more 24 600 or more 120 3000 or more 1 13 16 20 inch m...

Page 4: ...UNIT F2 F1 F2 F1F2 F1F2 1 2 3 4 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 1 2 3 1 7 2 2 8 3 4 5 6 B A figure 18 figure 20 1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 3 2 figure 21 figure 22 figure 23 figure 24 1 2...

Page 5: ...r lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explosion result...

Page 6: ...ar away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install t...

Page 7: ...ces where the unit does not bother next door neighbors A locations where small animals will not make nests in the unit Safe places which can withstand the unit s weight and vibration and where the uni...

Page 8: ...wiring in conduits and ground the conduits Use non shielded wire for transmission wiring Refer to figure 4 1 Indoor unit 2 Fuse Breaker 3 Remote controller 4 Personal computer or radio 7 Space needed...

Page 9: ...le below inch mm 5 PRECAUTIONS ON INSTALLATION Before installation make sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 found...

Page 10: ...ION Use a power wire pipe for the power supply wiring Outside the unit make sure the weak electric wiring i e for the remote controller cord between units etc and the strong electric wiring do not pas...

Page 11: ...ndoor unit 4 Under no circumstances should 208 230V be connected Precautions regarding the length of wiring between units Exceeding the following limits may cause transmission malfunctions so observe...

Page 12: ...e operation procedure in 7 7 Air tight test and vac uum drying regarding handling of the stop valve Only use the flare nuts included with the unit Using different flare nuts may cause the refrigerant...

Page 13: ...ntrol box Refer to figure 26 1 Putty or insulating material 2 field supply 7 5 Heat insulation of piping Highly recommended to insulate the interunit piping liquid and gas side and the refrigerant bra...

Page 14: ...joint from the following table RXTQ60 type KHRP26A22T9 Outdoor unit capacity type Refrigerant branch kit name How to select the refnet header Choose from the following table below the REFNET header a...

Page 15: ...id line stop valve Close 10 Indicates local procurement 11 Outdoor unit NOTE The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of par...

Page 16: ...k of the front panel All indoor units connected to the outdoor unit operate automatically Complete work on the indoor units in order to ensure maximum safety 10 1 Power On Check Operation Make sure to...

Page 17: ...running 3 Check to see if cold or hot air is coming out of the indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during tem...

Page 18: ...a the system automatically starts increasing its refrig erant temperature automatically reducing the delivered capacity and increasing the system s efficiency To activate this operation method under c...

Page 19: ...e of cooling operation the evaporating temperature is allowed to go down to 43 F 6 C on temporary base depending on the situ ation In case of heating operation the condense temperature is allowed to g...

Page 20: ...A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virt...

Page 21: ...and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lb charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen...

Page 22: ...18 English MEMO 01_EN_3P591321 1B fm 18...

Page 23: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 2001 3P591321 1B EM19A004A HT 00_CV_3P591321 1B fm 5...

Reviews: