background image

12

English

8.

ADDITIONAL REFRIGERANT CHARGE

WARNING

• When leaving the unit with the power on, be sure to 

switch with another person doing the installation or close 
the front panel.

8-1 Before adding refrigerant

• Make sure the following work and inspection is complete, in accor-

dance with the installation manual.
• Piping
• Wiring
• Airtightness test, Vacuum drying

8-2 Checking the refrigerant tank

• Check whether the tank has a siphon pipe before charging and place 

the tank so that the refrigerant is charged in liquid form. (See the fig-
ure below.)

8-3 Adding refrigerant

9.

POST-WORK CHECKS

Perform the following checks after work is complete.
(1) Drain pipe connection, removal of transport clasp 

See “

5. PRECAUTIONS ON INSTALLATION

”. 

(2) Incorrect power supply wiring, loose screws 



See “

6-3 How to connect the power supply wiring

”.

(3) Incorrect transmission wiring, loose screws 



See “

6-4 Transmission wiring connection procedure

”.

(4) Incorrect refrigerant piping connections 



See “

7. PRECAUTIONS ON REFRIGERANT PIPING

”.

(5) Piping sizes, use of insulation 



See : “

7-1 Selecting piping material

”.

7-5 Heat insulation of piping

”.

(6) Stop valve check 



Make sure both the liquid-side and gas-side stop valves are open.

(7) Record of Amount of Refrigerant Added 



Record it on “Record of Amount of Refrigerant Added” on the “Ser-
vice Precautions” plate.

(8) Measuring the insulation of the main power circuit 



• Use a 500V mega-tester. 
• Do not use the mega-tester for weak currents other than 208/230V. 

(Transmission wiring)

CAUTION

To the pipe-layer

After completing installation, be sure to open the valve.
(Operating the unit with the valve shut will break the compressor.)

10. TEST RUN

This unit is equipped with a crank case heater to ensure smooth 
startup. Be sure to turn the power on at least 6 hours before oper-
ation in order to have power running to the crank case heater.

WARNING

When leaving the unit with the power on, be sure to switch 
with another person doing the installation or close the front 
panel.

Precautions before turning the power on

• Using insulating sheets, tape electric parts as described in the “Ser-

vice Precautions” plate on the back of the front panel.

• All indoor units connected to the outdoor unit operate automatically. 

Complete work on the indoor units in order to ensure maximum safety.

10-1 Power On–Check Operation

• Make sure to perform the check operation after installation. 

(If the air conditioner is operated using the indoor remote controller 
without performing the check operation, the malfunction code “U3” is 
displayed in the indoor remote controller, and normal operation is 
disabled.)

• When making settings on the outdoor unit PC board (A1P) after turn-

ing the power on, do not touch anything other than the push-button 
switches and dip switches. 
(See the “Service Precautions” plate for the locations of the push-
button switches (BS1-5) and dip switches (DS1-1, 2) on the PC 
board (A1P).)

Tank with siphon pipe

Other tanks

There is a siphon 
pipe inside, so the 
cylinder need not be 
upside-down to fill 
with liquid.
(Stand the cylinder 
upright when filling.)

Stand the tank 
upside down and 
charge.

1.  Calculate the amount of refrigerant to add as described in “Calculating the 

amount of refrigerant to add” in “

7. PRECAUTIONS ON 

REFRIGERANT PIPING

”.

2.  After the vacuum drying is finished, open valve A and charge the calculated 

amount of refrigerant through the service port for the liquid-side stop valve.

3.  Close valve A after charging is complete.
Note: If all the refrigerant to be added cannot be charged using the above 

procedure, right-hand the procedure below and re-charge the refrigerant.

If all the refrigerant could not be added

Add refrigerant using the following procedure. See the “Service Precautions” plate 
attached to the outdoor unit for details on the settings for adding refrigerant.

Filling after calculating the amount of refrigerant to add

•  See “Stop valve operation procedure” in “

7. PRECAUTIONS ON REFRIGERANT PIPING

” for

  details on how to use the stop valve.
  (

Refer to figure 28

)

   1.  R410A Tank (Siphon system) 

5.  Stop valve service port

   2.  Measuring instrument 

6.  Gas line stop valve

   3.  Valve A 

7.  Outdoor unit

   4.  Indoor unit 

8.  Liquid line stop valve

Status of the Stop valve and other valves when adding refrigerant

State of valve A and the stop valve

Valve A

Liquid line 
stop valve

Gas line 
stop valve

Close

Close

Close

Close

Close

Open

Before starting to charge the refrigerant

During charging of the refrigerant

01_EN_3P591321-1B.fm  12 ページ  2019年12月24日 火曜日 午後5時19分

Summary of Contents for VRV IV-S Series

Page 1: ...nglish Fran ais Installation manual VRV IV S System air conditioner Manuel d installation Conditionneur d air VRV IV S System Espa ol Manual de instalaci n Acondicionador de aire con sistema VRV IV S...

Page 2: ...more 20 500 or less inch mm 40 1000 or more 40 1000 or more 20 500 or less 12 300 or more 8 200 or more 4 100 or more 4 100 or more figure 5 figure 6 1 2 3 4 20 500 or more 20 500 or less 20 500 or m...

Page 3: ...or more 8 200 or more 4 100 or more inch mm 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more L H A 60 1500 or more 24 600 or more 120 3000 or more 1 13 16 20 inch m...

Page 4: ...UNIT F2 F1 F2 F1F2 F1F2 1 2 3 4 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 1 2 3 1 7 2 2 8 3 4 5 6 B A figure 18 figure 20 1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 3 2 figure 21 figure 22 figure 23 figure 24 1 2...

Page 5: ...r lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explosion result...

Page 6: ...ar away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install t...

Page 7: ...ces where the unit does not bother next door neighbors A locations where small animals will not make nests in the unit Safe places which can withstand the unit s weight and vibration and where the uni...

Page 8: ...wiring in conduits and ground the conduits Use non shielded wire for transmission wiring Refer to figure 4 1 Indoor unit 2 Fuse Breaker 3 Remote controller 4 Personal computer or radio 7 Space needed...

Page 9: ...le below inch mm 5 PRECAUTIONS ON INSTALLATION Before installation make sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 found...

Page 10: ...ION Use a power wire pipe for the power supply wiring Outside the unit make sure the weak electric wiring i e for the remote controller cord between units etc and the strong electric wiring do not pas...

Page 11: ...ndoor unit 4 Under no circumstances should 208 230V be connected Precautions regarding the length of wiring between units Exceeding the following limits may cause transmission malfunctions so observe...

Page 12: ...e operation procedure in 7 7 Air tight test and vac uum drying regarding handling of the stop valve Only use the flare nuts included with the unit Using different flare nuts may cause the refrigerant...

Page 13: ...ntrol box Refer to figure 26 1 Putty or insulating material 2 field supply 7 5 Heat insulation of piping Highly recommended to insulate the interunit piping liquid and gas side and the refrigerant bra...

Page 14: ...joint from the following table RXTQ60 type KHRP26A22T9 Outdoor unit capacity type Refrigerant branch kit name How to select the refnet header Choose from the following table below the REFNET header a...

Page 15: ...id line stop valve Close 10 Indicates local procurement 11 Outdoor unit NOTE The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of par...

Page 16: ...k of the front panel All indoor units connected to the outdoor unit operate automatically Complete work on the indoor units in order to ensure maximum safety 10 1 Power On Check Operation Make sure to...

Page 17: ...running 3 Check to see if cold or hot air is coming out of the indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during tem...

Page 18: ...a the system automatically starts increasing its refrig erant temperature automatically reducing the delivered capacity and increasing the system s efficiency To activate this operation method under c...

Page 19: ...e of cooling operation the evaporating temperature is allowed to go down to 43 F 6 C on temporary base depending on the situ ation In case of heating operation the condense temperature is allowed to g...

Page 20: ...A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virt...

Page 21: ...and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lb charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen...

Page 22: ...18 English MEMO 01_EN_3P591321 1B fm 18...

Page 23: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 2001 3P591321 1B EM19A004A HT 00_CV_3P591321 1B fm 5...

Reviews: