![Daikin VRV IV-S Series Installation Manual Download Page 12](http://html1.mh-extra.com/html/daikin/vrv-iv-s-series/vrv-iv-s-series_installation-manual_2459217012.webp)
8
English
7-1 Selecting piping material
CAUTION
Piping and other pressure containing parts shall comply with the
applicable legislation and shall be suitable for refrigerant. Use phos-
phoric acid deoxidized seamless copper for refrigerant.
CAUTION
• All field piping must be installed by a licensed refrigeration techni-
cian and must comply with relevant local and national regulations.
• After piping work is complete, do not under any circumstances
open the stop valve until
6. FIELD WIRING
on page 6 and
9. POST-WORK CHECKS
on page 12 are complete.
• Do not use flux when brazing the rerigerant piping. Use the phos-
phor copper brazing filler metal(B-Cu93P-710/795:ISO 3677)
which does not require flux.Flux has extremely negative effect on
refrigerant piping systems.For instance, if the chlorine based flux is
used,it will cause pipe corrosion or,in particular,if the flux contains
fluorine,it will damage the refrigerant oil.
• Use only pipes which are clean inside and outside and which do not
accumulate harmful sulfur, oxidants, dirt, cutting oils, moisture, or
other contamination. (Foreign materials inside pipes including oils
for fabrication must be 0.14 gr/10 ft. (30 mg/10 m) or less.)
• Use the following items for the refrigerant piping.
Material :
Jointless phosphor-deoxidized copper pipe.
Size :
See
7-6 Example of connection
.
Thickness :
Select a thickness for the refrigerant piping which com-
plies with national and local laws.
• Install the refrigerant branch kit while observing the following condi-
tion and referring to the installation manual offered as an accessory
of the kit.
(Refer to figure 20)
1.
Install the REFNET joint so it splits horizontally or vertically.
2.
Horizontal surface
3.
A-arrow view
4.
±30° or less
5.
Level
6.
Vertical is also OK
7.
Install the REFNET header so that it splits horizontally.
8.
B-arrow view
7-2 Protection against contamination when install-
ing pipes
• Wrap the piping to prevent moisture, dirt, dust, etc. from entering the
piping.
• Exercise caution when passing copper piping through the through-
holes and when passing them out to the outside.
7-3 Pipe connection
• See “Stop valve operation procedure” in “
7-7 Air tight test and vac-
uum drying
” regarding handling of the stop valve.
• Only use the flare nuts included with the unit. Using different flare
nuts may cause the refrigerant to leak.
•
Be sure to perform a nitrogen blow when brazing.
(Brazing without performing nitrogen replacement or releasing nitro-
gen into the piping will create large quantities of oxidized film on the
inside of the pipes, adversely affecting valves and compressors in the
refrigerating system and preventing normal operation.)
(Refer to figure 21)
1.
Refrigerant pipe
2.
Location to be brazed
3.
Regulator
4.
Nitrogen
5.
Manual valve
6.
Taping
7-4 Connecting the refrigerant piping
• The local interunit piping is connectable in four directions.
(Refer to figure 22)
1.
Front panel
2.
Pipe outlet panel
3.
Backward
4.
Sideways
5.
Downward
6.
Pipe outlet panel screw
7.
Forward
8.
Screw for front panel
•
When connecting the pipings downward, remove the knockout
by making four holes in the middle on the each side of the
knockout with a drill.
(Refer to figure 23)
1.
Drill
2.
Center area around knockout hole
3.
Knockout hole
4.
Slit
• After knocking out the knock-out, it is recommended to apply repair
paint to the edge and the surrounding end surfaces to prevent rust-
ing.
(Refer to figure 24)
1.
Bottom frame
2.
Interunit piping
3.
piping (accessory)
NOTE
Cutting out the two slits makes it possible to install as shown in figure 24.
(Use a metal saw to cut out the slits.)
<Precautions when connecting pipes>
• Please refer to the Table 1 for the dimensions for processing flares.
• When connecting the flare nut, coat the flare both inside and outside
with refrigerating machine oil and initially tighten by hand 3 or 4 turns
before tightening firmly.
• Please refer to the Table 1 for the tightening torque. (Too much tight-
ening will end up in splitting of the flare.)
Table 1
Place
Installation Protection
method
More than a month
Pinch the pipe
Less than a month
Pinch or tape the pipe
Regardless of the period
Pipe size
(in.)
Tightening
torque (ft·lbf)
A dimen-
sions for
processing
flares (in.)
Flare shape (in.)
3/8”
(9.5mm)
24.1~29.4
(32.7~39.9N·m)
0.504~0.520
(12.8~13.2mm)
5/8”
(15.9mm)
45.6~55.6
(61.8~75.4N·m)
0.760~0.776
(19.3~19.7mm)
3/4”
(19.1mm)
71.7~87.5
(97.2~118.6N·m)
0.929~0.945
(23.6~24.0mm)
A
45
°± 2
°
90
°± 2
°
R0.016~0.031
(0.4~0.8mm)
01_EN_3P591321-1B.fm 8 ページ 2019年12月24日 火曜日 午後5時19分