background image

8

English

7-1 Selecting piping material

CAUTION

Piping and other pressure containing parts shall comply with the 
applicable legislation and shall be suitable for refrigerant. Use phos-
phoric acid deoxidized seamless copper for refrigerant.

CAUTION

• All field piping must be installed by a licensed refrigeration techni-

cian and must comply with relevant local and national regulations.

• After piping work is complete, do not under any circumstances 

open the stop valve until 

6. FIELD WIRING

 on page 6 and 

9. POST-WORK CHECKS

 on page 12 are complete.

• Do not use flux when brazing the rerigerant piping. Use the phos-

phor copper brazing filler metal(B-Cu93P-710/795:ISO 3677) 
which does not require flux.Flux has extremely negative effect on 
refrigerant piping systems.For instance, if the chlorine based flux is 
used,it will cause pipe corrosion or,in particular,if the flux contains 
fluorine,it will damage the refrigerant oil.

• Use only pipes which are clean inside and outside and which do not 

accumulate harmful sulfur, oxidants, dirt, cutting oils, moisture, or 
other contamination. (Foreign materials inside pipes including oils 
for fabrication must be 0.14 gr/10 ft. (30 mg/10 m) or less.)

• Use the following items for the refrigerant piping.

Material :

Jointless phosphor-deoxidized copper pipe.

Size :

See 

7-6 Example of connection

.

Thickness :

Select a thickness for the refrigerant piping which com-

plies with national and local laws.

• Install the refrigerant branch kit while observing the following condi-

tion and referring to the installation manual offered as an accessory 
of the kit.

(Refer to figure 20)

1.

Install the REFNET joint so it splits horizontally or vertically.

2.

Horizontal surface

3.

A-arrow view

4.

±30° or less

5.

Level

6.

Vertical is also OK

7.

Install the REFNET header so that it splits horizontally.

8.

B-arrow view

7-2 Protection against contamination when install-

ing pipes

• Wrap the piping to prevent moisture, dirt, dust, etc. from entering the 

piping.

• Exercise caution when passing copper piping through the through-

holes and when passing them out to the outside.

7-3 Pipe connection

• See “Stop valve operation procedure” in “

7-7 Air tight test and vac-

uum drying

” regarding handling of the stop valve.

• Only use the flare nuts included with the unit. Using different flare 

nuts may cause the refrigerant to leak.

Be sure to perform a nitrogen blow when brazing.

(Brazing without performing nitrogen replacement or releasing nitro-
gen into the piping will create large quantities of oxidized film on the 

inside of the pipes, adversely affecting valves and compressors in the 
refrigerating system and preventing normal operation.)

(Refer to figure 21)

1.

Refrigerant pipe

2.

Location to be brazed

3.

Regulator

4.

Nitrogen

5.

Manual valve

6.

Taping

7-4 Connecting the refrigerant piping

• The local interunit piping is connectable in four directions.

(Refer to figure 22)

1.

Front panel

2.

Pipe outlet panel

3.

Backward

4.

Sideways

5.

Downward

6.

Pipe outlet panel screw

7.

Forward

8.

Screw for front panel

When connecting the pipings downward, remove the knockout 
by making four holes in the middle on the each side of the 
knockout with a drill.

(Refer to figure 23)

1.

Drill

2.

Center area around knockout hole

3.

Knockout hole

4.

Slit

• After knocking out the knock-out, it is recommended to apply repair 

paint to the edge and the surrounding end surfaces to prevent rust-
ing.

(Refer to figure 24)

1.

Bottom frame

2.

Interunit piping

3.

piping (accessory)

NOTE

Cutting out the two slits makes it possible to install as shown in figure 24. 
(Use a metal saw to cut out the slits.)

<Precautions when connecting pipes>

• Please refer to the Table 1 for the dimensions for processing flares.
• When connecting the flare nut, coat the flare both inside and outside 

with refrigerating machine oil and initially tighten by hand 3 or 4 turns 
before tightening firmly.

• Please refer to the Table 1 for the tightening torque. (Too much tight-

ening will end up in splitting of the flare.)

Table 1

Place

Installation Protection 

method

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Regardless of the period

Pipe size 

(in.)

Tightening 

torque (ft·lbf)

A dimen-

sions for 

processing 

flares (in.)

Flare shape (in.)



3/8”

(9.5mm)

24.1~29.4

(32.7~39.9N·m)

0.504~0.520

(12.8~13.2mm)



5/8”

(15.9mm)

45.6~55.6

(61.8~75.4N·m)

0.760~0.776

(19.3~19.7mm)

 3/4”

(19.1mm)

71.7~87.5

(97.2~118.6N·m)

0.929~0.945
(23.6~24.0mm)

A

45

°± 2

°

90

°± 2

°

R0.016~0.031

(0.4~0.8mm)

01_EN_3P591321-1B.fm  8 ページ  2019年12月24日 火曜日 午後5時19分

Summary of Contents for VRV IV-S Series

Page 1: ...nglish Fran ais Installation manual VRV IV S System air conditioner Manuel d installation Conditionneur d air VRV IV S System Espa ol Manual de instalaci n Acondicionador de aire con sistema VRV IV S...

Page 2: ...more 20 500 or less inch mm 40 1000 or more 40 1000 or more 20 500 or less 12 300 or more 8 200 or more 4 100 or more 4 100 or more figure 5 figure 6 1 2 3 4 20 500 or more 20 500 or less 20 500 or m...

Page 3: ...or more 8 200 or more 4 100 or more inch mm 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more L H A 60 1500 or more 24 600 or more 120 3000 or more 1 13 16 20 inch m...

Page 4: ...UNIT F2 F1 F2 F1F2 F1F2 1 2 3 4 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 1 2 3 1 7 2 2 8 3 4 5 6 B A figure 18 figure 20 1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 3 2 figure 21 figure 22 figure 23 figure 24 1 2...

Page 5: ...r lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explosion result...

Page 6: ...ar away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install t...

Page 7: ...ces where the unit does not bother next door neighbors A locations where small animals will not make nests in the unit Safe places which can withstand the unit s weight and vibration and where the uni...

Page 8: ...wiring in conduits and ground the conduits Use non shielded wire for transmission wiring Refer to figure 4 1 Indoor unit 2 Fuse Breaker 3 Remote controller 4 Personal computer or radio 7 Space needed...

Page 9: ...le below inch mm 5 PRECAUTIONS ON INSTALLATION Before installation make sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 found...

Page 10: ...ION Use a power wire pipe for the power supply wiring Outside the unit make sure the weak electric wiring i e for the remote controller cord between units etc and the strong electric wiring do not pas...

Page 11: ...ndoor unit 4 Under no circumstances should 208 230V be connected Precautions regarding the length of wiring between units Exceeding the following limits may cause transmission malfunctions so observe...

Page 12: ...e operation procedure in 7 7 Air tight test and vac uum drying regarding handling of the stop valve Only use the flare nuts included with the unit Using different flare nuts may cause the refrigerant...

Page 13: ...ntrol box Refer to figure 26 1 Putty or insulating material 2 field supply 7 5 Heat insulation of piping Highly recommended to insulate the interunit piping liquid and gas side and the refrigerant bra...

Page 14: ...joint from the following table RXTQ60 type KHRP26A22T9 Outdoor unit capacity type Refrigerant branch kit name How to select the refnet header Choose from the following table below the REFNET header a...

Page 15: ...id line stop valve Close 10 Indicates local procurement 11 Outdoor unit NOTE The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of par...

Page 16: ...k of the front panel All indoor units connected to the outdoor unit operate automatically Complete work on the indoor units in order to ensure maximum safety 10 1 Power On Check Operation Make sure to...

Page 17: ...running 3 Check to see if cold or hot air is coming out of the indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during tem...

Page 18: ...a the system automatically starts increasing its refrig erant temperature automatically reducing the delivered capacity and increasing the system s efficiency To activate this operation method under c...

Page 19: ...e of cooling operation the evaporating temperature is allowed to go down to 43 F 6 C on temporary base depending on the situ ation In case of heating operation the condense temperature is allowed to g...

Page 20: ...A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virt...

Page 21: ...and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lb charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen...

Page 22: ...18 English MEMO 01_EN_3P591321 1B fm 18...

Page 23: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 2001 3P591321 1B EM19A004A HT 00_CV_3P591321 1B fm 5...

Reviews: