background image

14

English

[Remote controller displays malfunction code]
(Check on a remote controller connected to the indoor unit.)

• When using a central controller, see the installation manual or ser-

vice manual which came with the central controller.

[If nothing is displayed on the remote controller]

• There might be a problem with the connections or communication 

between the indoor unit and the remote controller.
Make sure all the wiring is properly connected.

CAUTION

To the pipe-layer, To the electrician

After the test run, when handing the unit over to the customer, make 
sure the front panel on the unit and all screws are attached.

10-3 Final charge adjustment

It is not necessary to do this final adjustment normally, but perform the 
following operation only when the most adequate refrigerant charge for 
the best performance is required and the piping length between the out-
door and indoor units is less than 50ft.(15m).
The outdoor temperature must be between 60°F (16°C) and 97°F (36 °C).

Run the system for 30 minutes in cooling by the forced operation using 
the field setting mode 2, No.6 (value 0: OFF, 1:ON) (Refer to Service 
Manual.) to allow pressures to stabilize.

Check subcooling of outdoor unit at LSV. Systems should have the 
target subcooling in the table below.

a. If the subcooling is low, add charge to raise subcooling to the target 

value. (The maximum additional charge is 2.2 lbs.(1kg))

b. If the subcooling is high, remove charge to lower the subcooling to 

the target value.

11. ENERGY SAVING AND OPTIMUM 

OPERATION

RXTQ~ units are equipped with advanced energy saving functionality. 
Depending on the priority, emphasis can be put on energy saving or 
comfort level. Several parameters can be selected, resulting
in the optimal balance between energy consumption and comfort for the 
particular application.

Several patterns are available and explained below. Modify the param-
eters to the needs of your building and to realize the best balance 
between energy consumption and comfort.

Refer to Service Manual for changing the field settings.
Setting definition:[A-B]=C;A=mode,B=setting NO.,C=setting value.

11-1 Three main operation methods are available:

Basic

The refrigerant temperature is fixed independent from the situation.
It corresponds to the standard operation which is known and can be 
expected from/under previous VRV systems:

• To activate this operation method under cooling operation:

change field setting [2-8]=2.

• To activate this operation method under heating operation:

change field setting [2-9]=2.

Automatic(default)

The refrigerant temperature is set depending on the outdoor ambient 
conditions. As such adjusting the refrigerant temperature to match 
the required load (which is also related to the outdoor ambient
conditions).
E.g., when your system is operating in cooling, you do not need as 
much cooling under low outdoor ambient temperatures (e.g., 
77°F(25°C)) as under high outdoor ambient temperatures (e.g., 
95°F(35°C)).
Using this idea, the system automatically starts increasing its refrig-
erant temperature, automatically reducing the delivered capacity 
and increasing the system’s efficiency.

• To activate this operation method under cooling operation:

change field setting [2-8]=3(default).

E.g., when your system is operating in heating, you do not need as 
much heating under high outdoor ambient temperatures (e.g., 
59°F(15°C)) as under low outdoor ambient temperatures (e.g., 23°F
(–5°C)).
Using this idea, the system automatically starts decreasing its refrig-
erant temperature, automatically reducing the delivered capacity 
and increasing the system’s efficiency.

• To activate this operation method under heating operation:

change field setting [2-9]=1 (default).

Malfunc-

tion code

Installation error

Remedial action

E3

The stop valve of an outdoor 
unit is left closed.

Open the gas-side stop valve and the liq-
uid-side stop valve.

Refrigerant overcharge.

Recalculate the required amount of refrig-
erant from the piping length and correct 
the refrigerant charge level by recovering 
any excessive refrigerant with a refriger-
ant recovery machine.

F6

Refrigerant overcharge.

Recalculate the required amount of refrig-
erant from the piping length and correct 
the refrigerant charge level by recovering 
any excessive refrigerant with a refriger-
ant recovery machine.

E4

The stop valve of an outdoor 
unit is left closed.

Open the gas-side stop valve and the liq-
uid-side stop valve.

Insufficient refrigerant.

Check if the additional refrigerant charge 
has been finished correctly.

Recalculate the required amount of refrig-
erant from the piping length and add an 
adequate amount of refrigerant.

F3

Refrigerant overcharge.

Recalculate the required amount of refrig-
erant from the piping length and correct 
the refrigerant charge level by recovering 
any excessive refrigerant with a refriger-
ant recovery machine.

The stop valve of an outdoor 
unit is left closed.

Open the gas-side stop valve and the liq-
uid-side stop valve.

Insufficient refrigerant.

Check if the additional refrigerant charge 
has been finished correctly.

Recalculate the required amount of refrig-
erant from the piping length and add an 
adequate amount of refrigerant.

U2

Insufficient supply voltage

Check to see if the supply voltage is sup-
plied properly.

U3

If a check operation has not 
been performed.

Perform a check operation.

U4

No power is supplied to an out-
door unit.

Turn the power on for the outdoor 
unit.

UA

If no dedicated indoor unit is 
being used.

Check the indoor unit. If it is not a dedi-
cated unit, replace the indoor unit.

UF

The stop valve of an outdoor 
unit is left closed.

Open the gas-side stop valve and the liq-
uid-side stop valve.

If the right indoor unit piping and 
wiring are not properly con-
nected to the outdoor unit.

Make sure that the right indoor unit piping 
and wiring are properly connected to the 
outdoor unit.

UH

If the transmission wiring has 
not be connected or it has 
shorted.

Make sure the transmission wiring is cor-
rectly attached to terminals (X2M) F1/F2 
(TO IN/D UNIT) on the outdoor unit circuit 
board.

Model

Target subcooling

RXTQ60~

14±1°F(7.78±0.56°C) 

01_EN_3P591321-1B.fm  14 ページ  2019年12月24日 火曜日 午後5時19分

Summary of Contents for VRV IV-S Series

Page 1: ...nglish Fran ais Installation manual VRV IV S System air conditioner Manuel d installation Conditionneur d air VRV IV S System Espa ol Manual de instalaci n Acondicionador de aire con sistema VRV IV S...

Page 2: ...more 20 500 or less inch mm 40 1000 or more 40 1000 or more 20 500 or less 12 300 or more 8 200 or more 4 100 or more 4 100 or more figure 5 figure 6 1 2 3 4 20 500 or more 20 500 or less 20 500 or m...

Page 3: ...or more 8 200 or more 4 100 or more inch mm 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more L H A 60 1500 or more 24 600 or more 120 3000 or more 1 13 16 20 inch m...

Page 4: ...UNIT F2 F1 F2 F1F2 F1F2 1 2 3 4 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 1 2 3 1 7 2 2 8 3 4 5 6 B A figure 18 figure 20 1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 3 2 figure 21 figure 22 figure 23 figure 24 1 2...

Page 5: ...r lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explosion result...

Page 6: ...ar away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install t...

Page 7: ...ces where the unit does not bother next door neighbors A locations where small animals will not make nests in the unit Safe places which can withstand the unit s weight and vibration and where the uni...

Page 8: ...wiring in conduits and ground the conduits Use non shielded wire for transmission wiring Refer to figure 4 1 Indoor unit 2 Fuse Breaker 3 Remote controller 4 Personal computer or radio 7 Space needed...

Page 9: ...le below inch mm 5 PRECAUTIONS ON INSTALLATION Before installation make sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 found...

Page 10: ...ION Use a power wire pipe for the power supply wiring Outside the unit make sure the weak electric wiring i e for the remote controller cord between units etc and the strong electric wiring do not pas...

Page 11: ...ndoor unit 4 Under no circumstances should 208 230V be connected Precautions regarding the length of wiring between units Exceeding the following limits may cause transmission malfunctions so observe...

Page 12: ...e operation procedure in 7 7 Air tight test and vac uum drying regarding handling of the stop valve Only use the flare nuts included with the unit Using different flare nuts may cause the refrigerant...

Page 13: ...ntrol box Refer to figure 26 1 Putty or insulating material 2 field supply 7 5 Heat insulation of piping Highly recommended to insulate the interunit piping liquid and gas side and the refrigerant bra...

Page 14: ...joint from the following table RXTQ60 type KHRP26A22T9 Outdoor unit capacity type Refrigerant branch kit name How to select the refnet header Choose from the following table below the REFNET header a...

Page 15: ...id line stop valve Close 10 Indicates local procurement 11 Outdoor unit NOTE The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of par...

Page 16: ...k of the front panel All indoor units connected to the outdoor unit operate automatically Complete work on the indoor units in order to ensure maximum safety 10 1 Power On Check Operation Make sure to...

Page 17: ...running 3 Check to see if cold or hot air is coming out of the indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during tem...

Page 18: ...a the system automatically starts increasing its refrig erant temperature automatically reducing the delivered capacity and increasing the system s efficiency To activate this operation method under c...

Page 19: ...e of cooling operation the evaporating temperature is allowed to go down to 43 F 6 C on temporary base depending on the situ ation In case of heating operation the condense temperature is allowed to g...

Page 20: ...A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virt...

Page 21: ...and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lb charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen...

Page 22: ...18 English MEMO 01_EN_3P591321 1B fm 18...

Page 23: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 2001 3P591321 1B EM19A004A HT 00_CV_3P591321 1B fm 5...

Reviews: