background image

6

English

6.

FIELD WIRING

CAUTION

To the electrician

• Do not operate until refrigerant piping work is completed.

(Failure to adhere by this caution may lead to irrepairable 
compressor damage.)

6-1 Wiring connection example for whole system

• Electrical wiring work should be done by a certified professional.
• Follow the “Electrical wiring diagram face plate” when carrying out 

any electrical wiring.
Only proceed with wiring work after blocking off all power.

• Make sure the ground resistance is no greater than 4



• Ground the indoor and outdoor units.
• Do not connect the ground wire to gas pipes, sewage pipes, lightning 

rods, or telephone ground wires.

Gas pipes:

 can explode or catch fire if there is a gas leak.

Sewage pipes:

 no grounding effect is possible if hard plastic pip-

ing is used.

Telephone ground wires and lightning rods:

 dangerous when 

struck by lightning due to abnormal rise in electrical potential in the 
grounding.

• Use copper wire.
• When doing the electrical wiring, always shut off the power source 

before working, and do not turn on the switch until all work is com-
plete.

• This unit has an inverter, so it must be grounded in order to reduce 

noise and prevent it affecting other appliances, and also to release 
any electrical build-up in the unit case due to leaked current.

• Do not install a power-factor improving phase-advancing capacitor 

under any circumstances.
(Not only will this not improve the power factor, but it might cause a 
fire.)

• Connect the wire securely using designated wire and fix it with 

attached clamp without applying external pressure on the terminal 
parts (terminal for power wiring, terminal for transmission wiring and 
earth terminal). See “

6-3 How to connect the power supply wir-

ing

”.

• Left-over wiring should not be wrapped and stuffed into the unit.
• To prevent the power wiring from being damaged by the knock hole 

edges, put it in a wiring pipe or plastic tube to protect it.

• Secure the wiring with the included clamp so that it does not come in 

contact with the piping or stop valve. 
(See “

6-3 How to connect the power supply wiring

”.)

CAUTION

• Use a power wire pipe for the power supply wiring.
• Outside the unit, make sure the weak electric wiring (i.e. for the 

remote controller cord, between units, etc.) and the strong electric 
wiring do not pass near each other, 

keeping them at least 

2in.(50mm) apart

.

Proximity may cause electrical interference, malfunctions, and 
breakage.

• Be sure to connect the power wiring to the power wiring terminal 

block and secure it as described in “

6-3 How to connect the 

power supply wiring

”.

• Transmission wiring should be secured as described in “

6-4 Trans-

mission wiring connection procedure

”.

• Secure wiring with clamp (accessory) to avoid contact with piping.
• Make sure the wiring and the front panel do not stick up above the 

structure, and close the cover firmly.

(Refer to figure 15)

1.

Fuse/Breaker

2.

Power supply

3.

Outdoor unit

4.

16V

5.

208/230V

6.

Indoor unit

7.

Remote controller

8.

Ground wire

6-2 How to lay the power supply wiring and trans-

mission wiring

Let the power supply wiring and transmission wiring with a conduit pass 
through one of the knockout holes on the front or side cover, and let the 
transmission wiring with a conduit pass through another knockout hole.

• For protection from uninsulated live parts, thread the power supply 

wiring and the transmission wiring through the included insulation 
tube and secure it with the included clamp.

Precautions knock out holes

• Open the knock holes with a hammer or the like.
• After knocking out the holes, we recommend you remove burrs in the 

knock holes and paint the edges and areas around the edges using 
the repair paint to prevent rusting.

• When passing wiring through knock holes, make sure there are no 

burrs, and protect the wiring with protective tape.

(Refer to figure 16)

1.

Stop valve attachment plate

2.

Power supply wiring (including ground wire) or transmission 
wiring.

3.

Back of unit

4.

Knockout hole

5.

Side of unit

6.

Front of unit

7.

Terminal block

8.

Control Box

Insulation tube
(accessory)

Clamp
(accessory)

Power supply 
wiring

3in.(75mm)

2in.(50mm)
or more

5/8in.(15.9mm)

Insulation tube
(accessory)

Clamp
(accessory)

Transmission
wiring

3in.(75mm)

<Power supply wiring>

<Transmission wiring>

Ground wire

If small animals might enter the 
unit, block the knock holes with an 
appropriate material (field supply).

Burr

01_EN_3P591321-1B.fm  6 ページ  2019年12月24日 火曜日 午後5時19分

Summary of Contents for VRV IV-S Series

Page 1: ...nglish Fran ais Installation manual VRV IV S System air conditioner Manuel d installation Conditionneur d air VRV IV S System Espa ol Manual de instalaci n Acondicionador de aire con sistema VRV IV S...

Page 2: ...more 20 500 or less inch mm 40 1000 or more 40 1000 or more 20 500 or less 12 300 or more 8 200 or more 4 100 or more 4 100 or more figure 5 figure 6 1 2 3 4 20 500 or more 20 500 or less 20 500 or m...

Page 3: ...or more 8 200 or more 4 100 or more inch mm 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more L H A 60 1500 or more 24 600 or more 120 3000 or more 1 13 16 20 inch m...

Page 4: ...UNIT F2 F1 F2 F1F2 F1F2 1 2 3 4 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 1 2 3 1 7 2 2 8 3 4 5 6 B A figure 18 figure 20 1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 3 2 figure 21 figure 22 figure 23 figure 24 1 2...

Page 5: ...r lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explosion result...

Page 6: ...ar away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install t...

Page 7: ...ces where the unit does not bother next door neighbors A locations where small animals will not make nests in the unit Safe places which can withstand the unit s weight and vibration and where the uni...

Page 8: ...wiring in conduits and ground the conduits Use non shielded wire for transmission wiring Refer to figure 4 1 Indoor unit 2 Fuse Breaker 3 Remote controller 4 Personal computer or radio 7 Space needed...

Page 9: ...le below inch mm 5 PRECAUTIONS ON INSTALLATION Before installation make sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 found...

Page 10: ...ION Use a power wire pipe for the power supply wiring Outside the unit make sure the weak electric wiring i e for the remote controller cord between units etc and the strong electric wiring do not pas...

Page 11: ...ndoor unit 4 Under no circumstances should 208 230V be connected Precautions regarding the length of wiring between units Exceeding the following limits may cause transmission malfunctions so observe...

Page 12: ...e operation procedure in 7 7 Air tight test and vac uum drying regarding handling of the stop valve Only use the flare nuts included with the unit Using different flare nuts may cause the refrigerant...

Page 13: ...ntrol box Refer to figure 26 1 Putty or insulating material 2 field supply 7 5 Heat insulation of piping Highly recommended to insulate the interunit piping liquid and gas side and the refrigerant bra...

Page 14: ...joint from the following table RXTQ60 type KHRP26A22T9 Outdoor unit capacity type Refrigerant branch kit name How to select the refnet header Choose from the following table below the REFNET header a...

Page 15: ...id line stop valve Close 10 Indicates local procurement 11 Outdoor unit NOTE The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of par...

Page 16: ...k of the front panel All indoor units connected to the outdoor unit operate automatically Complete work on the indoor units in order to ensure maximum safety 10 1 Power On Check Operation Make sure to...

Page 17: ...running 3 Check to see if cold or hot air is coming out of the indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during tem...

Page 18: ...a the system automatically starts increasing its refrig erant temperature automatically reducing the delivered capacity and increasing the system s efficiency To activate this operation method under c...

Page 19: ...e of cooling operation the evaporating temperature is allowed to go down to 43 F 6 C on temporary base depending on the situ ation In case of heating operation the condense temperature is allowed to g...

Page 20: ...A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virt...

Page 21: ...and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lb charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen...

Page 22: ...18 English MEMO 01_EN_3P591321 1B fm 18...

Page 23: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 2001 3P591321 1B EM19A004A HT 00_CV_3P591321 1B fm 5...

Reviews: