background image

English

13

• During the operation, monitor the outdoor unit operation status and 

check for any incorrect wiring.

<Precautions During Check Operation>

If operation is performed within 12 minutes of the indoor and 
outdoor units being turned on, H2P will light up, and the com-
pressor will not run.

Only perform operation after checking that the LED display is as 
shown in “

10-1 Power On–Check Operation

” 2. table.

• In order to ensure uniform refrigerant distribution, it may take up to 

around 10 minutes for the compressor to start up after the unit 
begins running. This is not a malfunction.

• Each indoor unit cannot be checked individually for problems.

After this operation is complete, run the unit normally using the 
remote controller.

• The check run cannot be performed in recovery or other modes.
• If the outlet pipe thermistor (R2T), the intake pipe thermistor (R3T), 

and the pressure sensors (S1NPH and S1NPL) are removed before 
operation, the compressor might burn out, so avoid this under all cir-
cumstances.

10-2 Temperature control operation checklist

[Set the master unit (the indoor unit with rights of selection cooling 
or heating)]
<With a wired remote controller>

• After check operation is complete, displays of all the connected 

remote controllers will flash “Switching mode”.

• Ask the customer which indoor unit to set as the master unit. 

(Setting the most frequently used indoor unit as the master unit is 
recommended.)

• Press the mode-switch button on the remote controller for the mas-

ter unit.

• That remote controller will then become the remote controller for 

switching between cooling and heating.

• All other remote controllers will display “Switching mode”.

<With wireless remote controller>

• After check operation is complete, the timer lamps on all the indoor 

units which are connected will flash.

• Ask the customer which indoor unit to set as the master unit. 

(Setting the most frequently used indoor unit as the parent unit is 
recommended.)

• Press the mode-switch button on the remote controller for the mas-

ter unit. 
A beeping sound will be emitted and the timer lamps on all the 
indoor units will go off. 

• That indoor unit will be the indoor unit which has the right to switch 

between cooling and heating. 
For details, see the operation manual which comes with the unit.

• After check operation is complete, checking the temperature control 

using normal operation.
(Heating is not possible if the outdoor temperature is 75°F(24°C) or 
higher. See the included operation manual.)
(1)Make sure the indoor and outdoor units are operating normally.

(If liquid compression by the compressor or other abnormal 
noises can be heard, stop the unit immediately, heat the crank 
case for a sufficient amount of time, and try again.)

(2)Run each indoor unit one at a time and make sure the corre-

sponding outdoor unit is also running.

(3)Check to see if cold (or hot) air is coming out of the indoor unit.
(4)Press the fan direction and fan strength buttons on the indoor 

unit to see if they operate properly.

<Precautions during temperature control checks>

• For around 5 minutes after the compressor stops, the compressor 

will not run even if the “operate/stop” button on the remote controller 
is pressed.

• When the system operation is stopped by the remote controller, the 

outdoor units may continue operating for further 1 minutes at maxi-
mum.

• Malfunction code “U3” is displayed if check operation is not per-

formed using the test run button the first time after installation. Per-
form the check operation in accordance with “

10-1 Power On–

Check Operation

”.

1. Close the outdoor unit’s front panel.
 

Turn the power

 on for the outdoor 

  unit and the indoor unit.

2.  • Open the outdoor unit’s front panel.
  • Make sure the LED display on the outdoor unit’s PC board (A1P) is as 
      shown in the following chart. 

LED display 
(Default status 
before delivery)

HAP

A1P

H1P

H2P

H3P

H4P

H5P

H6P

H7P

6. Close the front panel of the outdoor unit after check operation is complete.

Do not leave any stop valve closed 
otherwise the compressor will fail.

Caution

Be sure to turn the power on at least 
6 hours before operation in order to have 
power running to the crank case heater.

To avoid the risk of electric shock, do not touch anything other than the 
push-button switches on the PC board (A1P) when making settings.

Caution

LED display:     OFF      ON      Blinking

Use caution to avoid electric shock while 
working, since the outdoor unit is on.

•  Only set the push-button switches (BS1-5) 

after making sure the microcomputer OK 
monitor is lit up.

•  See the “Service Precautions” plate on the 

front panel of the outdoor unit for details on 
how to make the settings. 

  (Do not forget to write the settings down on 

the “Service Precautions” plate.)

•  The dip switch (DS1-1) does not need to be 

set, so do not touch it. 

  Doing so may cause malfunction.

•  If you have to leave the outdoor unit during check 

operation, either switch with another worker or close the 
front panel. 

•  The system operates for about 30 minutes (60 minutes at 

maximum) and automatically stops the check operation.

•  The system can start normal operation about 

3 minutes 

after the check operation if

 the 

remote controller does not display any error code.
The remote controller will show the test run 
display during check operation. 

3.  • When the customer requests
    quiet operation or demand
    operation, make these settings
    using the push-button switches
    (BS1-5) on the outdoor unit’s
    PC board (A1P).
  • Operate the push-button
    switches through the opening
    after protecting it with an
  insulation 

cover. 

    (See the “Service Precautions”
    plate for details.)

4.  • Check that the liquid and gas-side
    stop valves are open, and if
    they are closed, open them.

5. Press the test run button (BS4) for
  at least five seconds and perform
 check 

operation. 

  For details, see “How to perform
  check operation” on the “Service
 Precautions” 

plate.

01_EN_3P591321-1B.fm  13 ページ  2019年12月24日 火曜日 午後5時19分

Summary of Contents for VRV IV-S Series

Page 1: ...nglish Fran ais Installation manual VRV IV S System air conditioner Manuel d installation Conditionneur d air VRV IV S System Espa ol Manual de instalaci n Acondicionador de aire con sistema VRV IV S...

Page 2: ...more 20 500 or less inch mm 40 1000 or more 40 1000 or more 20 500 or less 12 300 or more 8 200 or more 4 100 or more 4 100 or more figure 5 figure 6 1 2 3 4 20 500 or more 20 500 or less 20 500 or m...

Page 3: ...or more 8 200 or more 4 100 or more inch mm 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more L H A 60 1500 or more 24 600 or more 120 3000 or more 1 13 16 20 inch m...

Page 4: ...UNIT F2 F1 F2 F1F2 F1F2 1 2 3 4 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 1 2 3 1 7 2 2 8 3 4 5 6 B A figure 18 figure 20 1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 3 2 figure 21 figure 22 figure 23 figure 24 1 2...

Page 5: ...r lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes will result a gas leak and potential explosion result...

Page 6: ...ar away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install t...

Page 7: ...ces where the unit does not bother next door neighbors A locations where small animals will not make nests in the unit Safe places which can withstand the unit s weight and vibration and where the uni...

Page 8: ...wiring in conduits and ground the conduits Use non shielded wire for transmission wiring Refer to figure 4 1 Indoor unit 2 Fuse Breaker 3 Remote controller 4 Personal computer or radio 7 Space needed...

Page 9: ...le below inch mm 5 PRECAUTIONS ON INSTALLATION Before installation make sure the unit is level and the foundation is sturdy enough to prevent vibration and noise Fasten the unit in place using 4 found...

Page 10: ...ION Use a power wire pipe for the power supply wiring Outside the unit make sure the weak electric wiring i e for the remote controller cord between units etc and the strong electric wiring do not pas...

Page 11: ...ndoor unit 4 Under no circumstances should 208 230V be connected Precautions regarding the length of wiring between units Exceeding the following limits may cause transmission malfunctions so observe...

Page 12: ...e operation procedure in 7 7 Air tight test and vac uum drying regarding handling of the stop valve Only use the flare nuts included with the unit Using different flare nuts may cause the refrigerant...

Page 13: ...ntrol box Refer to figure 26 1 Putty or insulating material 2 field supply 7 5 Heat insulation of piping Highly recommended to insulate the interunit piping liquid and gas side and the refrigerant bra...

Page 14: ...joint from the following table RXTQ60 type KHRP26A22T9 Outdoor unit capacity type Refrigerant branch kit name How to select the refnet header Choose from the following table below the REFNET header a...

Page 15: ...id line stop valve Close 10 Indicates local procurement 11 Outdoor unit NOTE The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of par...

Page 16: ...k of the front panel All indoor units connected to the outdoor unit operate automatically Complete work on the indoor units in order to ensure maximum safety 10 1 Power On Check Operation Make sure to...

Page 17: ...running 3 Check to see if cold or hot air is coming out of the indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during tem...

Page 18: ...a the system automatically starts increasing its refrig erant temperature automatically reducing the delivered capacity and increasing the system s efficiency To activate this operation method under c...

Page 19: ...e of cooling operation the evaporating temperature is allowed to go down to 43 F 6 C on temporary base depending on the situ ation In case of heating operation the condense temperature is allowed to g...

Page 20: ...A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virt...

Page 21: ...and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lb charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen...

Page 22: ...18 English MEMO 01_EN_3P591321 1B fm 18...

Page 23: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 2001 3P591321 1B EM19A004A HT 00_CV_3P591321 1B fm 5...

Reviews: