background image

3P405106-10 English

5

NOTE 

• 

The Branch Selector unit has a top and a bottom, so install it so that the diagonal lines in the 

Fig. 4 are 

where the top is. (Failing to do so may prevent the unit from operating properly and increase the volume 
of the operating noise.)

Control box cover

Coil cover

Top Panel

Control box

5)-2
(Move the 
control box)

1)

1)

2)

4), 6)

3), 7)

3), 7)

3), 7)

3), 7)

(Rotate 180 degrees)

6)

7)

(Rotate 180 degrees)

2)

9)

9)

8)

8)

4)

2)

[Before change 5)-1]

[After change 5)-3]

Control box

Control box

Remove the wire 

from the wire clip.

Pass the wire 

through the wire clip.

Fig. 4

5.  REFRIGERANT PIPING WORK

• 

For instruction for installing piping between the outdoor unit and Branch Selector unit, selecting a refrig-

erant branch kit, and installing piping between the refrigerant branch kit and the indoor unit, refer to the 

installation manual and equipment design materials included with the outdoor unit.

• 

Before beginning the work, be sure to verify that the type of refrigerant used is R410A. (The unit will not 

operate correctly with a different type of refrigerant.)

• 

Insulate all of the piping, including the liquid pipes, high/low pressure gas pipes, suction gas pipes, gas 

pipes, and the pipe connections for these. 

Not insulating these pipes could result in water leaks or burns. 

In particular, low-temperature gas flows in the high/low pressure gas piping during full cooling operation, 

so the same amount of insulation as used for the suction gas pipes is required. 

In addition, high-temperature gas flows in the high/low pressure gas piping and gas piping, so use insu

-

lation that can withstand more than 250°F (120°C).

• 

Select insulation material as necessary for the installation environment. 

For details, refer to the Engineering Data Book.

 

If you fail to do so, condensation could form on the surface of the insulation.

NOTE 

• 

This product only uses the new refrigerant (R410A). Be sure to use the special pipe cutters for R410A, 

during installation.

• 

Make sure that nothing besides the specified refrigerant, such as air, gets into the refrigerant piping.

• 

If refrigerant gas leaks during the work, ventilate the area. (The outdoor units are filled with refrigerant.)

5-1  Piping material selection

• 

Use only pipes which are clean inside and outside and which do not accumulate harmful sulfur, oxidants, 

dirt, cutting oils, moisture, or other contamination. (Foreign materials inside pipes including oils for 

fabrica tion must be 9 mg/10 ft. (9 mg/3 m) or less.)

01_EN_3P405106-10.indb   5

4/21/2015   4:29:04 PM

Summary of Contents for VRV IV BSQ36TVJ

Page 1: ...A HANDY PLACE FOR FUTURE REFERENCE English Fran ais Espa ol 3P405106 10 LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUI...

Page 2: ...onnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When install...

Page 3: ...amps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat...

Page 4: ...uc tions CONTENTS Safety considerations i Codes and Regulations ii 1 BEFORE INSTALLATION 2 2 SELECTING INSTALLATION SITE 3 3 PREPARATIONS BEFORE INSTALLATION 4 4 BRANCH SELECTOR UNIT INSTALLATION 4 5...

Page 5: ...l BSQ96TVJ Name 1 Accessory pipes 2 Clamp 3 Insulation tube Explanation Document Quantity 1 pc 2 pcs 16 pcs 2 pcs 2 pcs 1 pc 1 copy Shape 1 1 f3 4 f19 1 1 2 f3 4 f19 1 3 1 Medium 3 2 Small 3 3 Large I...

Page 6: ...here the wall is not significantly tilted Where sufficient clearance for maintenance and service can be ensured Refer to Fig 1 Locations where an inspection hole refer to Fig 2 can be installed to the...

Page 7: ...or less Unit Suspension bolt pitch Example installation Note All the above parts are part to be procured in the field Fig 3 Unit in mm 4 BRANCH SELECTOR UNIT INSTALLATION Use only accessories and par...

Page 8: ...uction gas pipes gas pipes and the pipe connections for these Not insulating these pipes could result in water leaks or burns In particular low temperature gas flows in the high low pressure gas pipin...

Page 9: ...or perform brazing while nitrogen is flowing in the refrigerant piping 2 refer to Fig 5 1 For details on nitrogen replacement see the VRV Installation Manual available at any Daikin dealer 2 The pres...

Page 10: ...pressure gas pipe Liquid pipe Branch Selector unit Refrigerant branch kit Upstream Downstream Table 3 Indoor unit total capacity and pipe size Total capacity index of indoor units x Pipe size Outside...

Page 11: ...or unit total capacity is more than 36 but less than 54 and when one indoor unit with a capacity of 42 to 54 is connected downstream When the downstream indoor unit total capacity is 54 or more but 60...

Page 12: ...Selector unit Clamp 2 Accessory Clamp 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 1 Accessory Insulation tube 3 2 Accessory...

Page 13: ...and be sure the terminal board wiring to the outdoor unit and indoor unit are properly matched If wiring and piping between the outdoor unit Branch Selector unit and an indoor unit are mismatched the...

Page 14: ...ranch Selector unit B Final Branch Selector unit C H SELECTOR COOL HEAT SELECTOR COOL HEAT SELECTOR COOL HEAT SELECTOR C H SELECTOR C H SELECTOR TO IN D UNIT TOOUT DUNIT TO IN D UNIT TOOUT DUNIT TO IN...

Page 15: ...through the wire through hole right and into the control box and use the included clamps 2 to securely hold the wires in 2 places Be sure to wire the ground wire so that comes out of the slit in the...

Page 16: ...in a malfunction or breakdown After the wiring working is complete use sealer field supply to seal closed the wire through hole Entry by small animals etc could cause a malfunction 7 INITIAL SETTING W...

Page 17: ...ctory shipment 2 1 8 1 3 3 6 2 4 5 4 3 5 7 2 4 6 9 0 5 7 10 8 6 8 12 6 7 8 ADDING AN ADDITIONAL CHARGE OF REFRIGERANT Follow the instructions in the installation manual that came with the outdoor unit...

Page 18: ...3P405106 10 EM14A004A 1506 HT 5151 San Felipe Suite 500 Houston TX 77056 00_CV_3P405106 10 indd 2 4 20 2015 3 09 18 PM...

Reviews: