background image

3P405106-10 English

11

Table 6 

Units

Power supply

Model

Type

Hz

Voltage

Voltage range

Min.

Max.

MCA

MOP

BSQ36TVJ
BSQ60TVJ
BSQ96TVJ

VJ

60

208/230

187

253

0.1

15

MCA: Minimum Circuit Ampacity (A);  

MOP: Maximum Overcurrent Protective Device (A)

NOTE 

• 

Table 6 of electrical characteristics refers to one Branch Selector unit.

• 

See the Engineering Data Book for other details.

6-4  Wiring example

 WARNING

Install circuit protection safety devices in accordance with local and national codes.

Failure to install circuit protection safety devices in accordance with local and national codes may result in 

electric shock or fire.

• 

Here is shown a wiring example for one system transmission wiring.

• 

Connect  “TO IN/D UNIT (F1, F2)” terminals on the printed circuit board of the outdoor unit and “TO 

OUT/D UNIT (F1, F2)” terminals on the printed circuit board of the first Branch Selector unit A.

F1 F2

F1

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F2 F1 F2

F1 F2 F1 F2

F1 F2 F1 F2

A

A B C

A B C

A B C

B
C

A
B
C

A
B
C

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(2)

(2)

(2)

L1

B

208/230V

L2

Power supply

Absolutely do not 
connect the power 
supply wiring.

Transmission wiring

Use 2-core wires.
(There is no polarity.)

COOL/HEAT SELECTOR wiring

Use 3-core wires. (There is polarity. 
Match the terminal numbers.)

Cooling/Heating selectable indoor unit

Cooling-dedicated 

indoor unit

Outdoor unit

Branch Selector

unit A

Branch Selector

unit B

Final Branch

Selector unit

C/H SELECTOR

COOL/HEAT

SELECTOR

COOL/HEAT

SELECTOR

COOL/HEAT

SELECTOR

C/H SELECTOR

C/H SELECTOR

TO IN/D UNIT TO OUT/D UNIT

TO IN/D UNIT TO OUT/D UNIT

TO IN/D UNIT TO OUT/D UNIT

TO IN/D UNIT

B : Circuit protection safety devices in accordance with local and national codes 

NOTE 

1. 

Connect cooling-dedicated air conditioners to “TO OUT/D UNIT (F1, F2)” terminals of the final Branch 

Selector unit.

2.  Use 2-core wire for the transmission wiring. Using a multi-core wire with 3 or more cores when 2 or 

more indoor units are used at once could cause abnormal stoppage. (Only use 3-core wire in the 

COOL/HEAT SELECTOR.)

3.  Absolutely do not connect the power supply wiring to the transmission wiring terminal block. Doing so 

could damage the entire system.

4. 

For the transmission wiring, use wire that is within the following ranges. Exceeding these limits could 

cause a transmission error.

(1) 

Between the Branch Selector unit and indoor units: Max. 3,280 ft. (1,000 m)

 

Between the Branch Selector unit and outdoor unit: Max. 3,280 ft. (1,000 m)

 

Between Branch Selector units: Max. 3,280 ft. (1,000 

m)

Total wiring length: 6,560 ft. (2,000 m) or less

Branch point max: 16 branch points

(2) 

Between a Branch Selector unit and COOL/HEAT SELECTOR

Maximum wiring length: 1,640 ft. (500 m) or less

5.  When the shield wire is used, be sure to ground the one side of the 

shield wire. 

The total wiring length is 4,920 ft. (1,500 m) when shielded wire is used.

F1 F2

F1F2

F1F2

F1F2

F1F2

branch

Sub-branching

01_EN_3P405106-10.indb   11

4/21/2015   4:29:07 PM

Summary of Contents for VRV IV BSQ36TVJ

Page 1: ...A HANDY PLACE FOR FUTURE REFERENCE English Fran ais Espa ol 3P405106 10 LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUI...

Page 2: ...onnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When install...

Page 3: ...amps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat...

Page 4: ...uc tions CONTENTS Safety considerations i Codes and Regulations ii 1 BEFORE INSTALLATION 2 2 SELECTING INSTALLATION SITE 3 3 PREPARATIONS BEFORE INSTALLATION 4 4 BRANCH SELECTOR UNIT INSTALLATION 4 5...

Page 5: ...l BSQ96TVJ Name 1 Accessory pipes 2 Clamp 3 Insulation tube Explanation Document Quantity 1 pc 2 pcs 16 pcs 2 pcs 2 pcs 1 pc 1 copy Shape 1 1 f3 4 f19 1 1 2 f3 4 f19 1 3 1 Medium 3 2 Small 3 3 Large I...

Page 6: ...here the wall is not significantly tilted Where sufficient clearance for maintenance and service can be ensured Refer to Fig 1 Locations where an inspection hole refer to Fig 2 can be installed to the...

Page 7: ...or less Unit Suspension bolt pitch Example installation Note All the above parts are part to be procured in the field Fig 3 Unit in mm 4 BRANCH SELECTOR UNIT INSTALLATION Use only accessories and par...

Page 8: ...uction gas pipes gas pipes and the pipe connections for these Not insulating these pipes could result in water leaks or burns In particular low temperature gas flows in the high low pressure gas pipin...

Page 9: ...or perform brazing while nitrogen is flowing in the refrigerant piping 2 refer to Fig 5 1 For details on nitrogen replacement see the VRV Installation Manual available at any Daikin dealer 2 The pres...

Page 10: ...pressure gas pipe Liquid pipe Branch Selector unit Refrigerant branch kit Upstream Downstream Table 3 Indoor unit total capacity and pipe size Total capacity index of indoor units x Pipe size Outside...

Page 11: ...or unit total capacity is more than 36 but less than 54 and when one indoor unit with a capacity of 42 to 54 is connected downstream When the downstream indoor unit total capacity is 54 or more but 60...

Page 12: ...Selector unit Clamp 2 Accessory Clamp 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 1 Accessory Insulation tube 3 2 Accessory...

Page 13: ...and be sure the terminal board wiring to the outdoor unit and indoor unit are properly matched If wiring and piping between the outdoor unit Branch Selector unit and an indoor unit are mismatched the...

Page 14: ...ranch Selector unit B Final Branch Selector unit C H SELECTOR COOL HEAT SELECTOR COOL HEAT SELECTOR COOL HEAT SELECTOR C H SELECTOR C H SELECTOR TO IN D UNIT TOOUT DUNIT TO IN D UNIT TOOUT DUNIT TO IN...

Page 15: ...through the wire through hole right and into the control box and use the included clamps 2 to securely hold the wires in 2 places Be sure to wire the ground wire so that comes out of the slit in the...

Page 16: ...in a malfunction or breakdown After the wiring working is complete use sealer field supply to seal closed the wire through hole Entry by small animals etc could cause a malfunction 7 INITIAL SETTING W...

Page 17: ...ctory shipment 2 1 8 1 3 3 6 2 4 5 4 3 5 7 2 4 6 9 0 5 7 10 8 6 8 12 6 7 8 ADDING AN ADDITIONAL CHARGE OF REFRIGERANT Follow the instructions in the installation manual that came with the outdoor unit...

Page 18: ...3P405106 10 EM14A004A 1506 HT 5151 San Felipe Suite 500 Houston TX 77056 00_CV_3P405106 10 indd 2 4 20 2015 3 09 18 PM...

Reviews: