background image

3P405106-10 English

9

When one indoor unit with a capacity of 72 is connected downstream

Suction gas pipe (Site piping)
High/low pressure gas pipe (Site piping)

Liquid pipe (Site piping)

Gas pipe (Site piping)

Liquid pipe (Site piping)

Branch

Selector

unit

(Top)

Accessory pipe 1)-2

5-6  Piping insulation

• 

After the gas leak inspection is completed, refer to the following figures and use the included insulation 

tube 3) and clamps 2) to apply the insulation.

 CAUTION

• 

Insulate all of the piping including the liquid pipes, high/low pressure gas pipes, suction gas pipes, gas 
pipes, and the pipe connections for these. 
Not insulating these pipes could result in water leaks or burns. 

In particular, low-temperature gas flows in the high/low pressure gas pipes during full cooling operation, 

so the same amount of insulation as used for the suction gas pipes is required. 

In addition, high-temperature gas flows in the high/low pressure gas piping and gas piping, so use 

insulation that can withstand more than 250°F (120°C).

• 

When reinforcing the insulation material in accordance with the installation environment, also reinforce 
the insulation on the piping protruding from the unit. 

Insulation material required for reinforcement work should be supplied in the field.

 

For more information, refer to the Engineering Data Book.

BSQ36 · 60TVJ type

BSQ96TVJ type

Branch Selector

unit

Branch Selector

unit

Clamp 2)
(Accessory)

Clamp 2) 
(Accessory)

Insulation tube 3)-2
(Accessory)

Insulation 
tube 3)-2
(Accessory)

Insulation tube 3)-2
(Accessory)

Insulation 
tube 3)-1
(Accessory)

Insulation 
tube 3)-2
(Accessory)

Insulation 
tube 3)-1
(Accessory)

Insulation tube 3)-2
(Accessory)

Insulation tube 3)-1
(Accessory)

Insulation tube 3)-1
(Accessory)

Insulation tube 3)-3
(Accessory)

Suction gas pipe 
(Note 1)

Gas pipe 
(Note 1)

Liquid pipe

Gas pipe 
(Note 2)

Liquid pipe

High/low pressure 
gas pipe (Note 1)
Liquid pipe

Suction gas pipe 
(Note 2)
High/low pressure 
gas pipe (Note 1)
Liquid pipe

Clamp 2) 
(Accessory)

Clamp 2) 
(Accessory)

Insulation Attachment Instructions

Piping insulation
(Product piping side)

Pipe connection

Insulation material 
(Field supply)

Seal the connection.

Piping insulation
(Site piping side)

(1) Attach the included 

insulation.

(2) Seal

(3) Use the clamps (accessory) 

to hold both ends.

Note 1: For suction gas pipes, high/low 

pressure gas pipes, and gas pipes, 
after attaching the included 
insulation tube, wrap more 
insulation (field supply) around the 
connections.

Note 2: For Model Q96, wrap sealing 

material (field supply) around the 
insulation tube 3)-2 Branch 
Selector unit side and site piping 
side connections to seal them.

Main unit

Main 
unit

Insulation tube 3)-2
(Accessory)

 Insulation Installation Precautions

1.  Seal so that air cannot be in and out of the end.

2.  Do not over tighten the clamp so as to maintain the insulation thickness.

3. 

Be sure to attach the insulation (field supply) with the seams facing up. 

 

(See figure at right.)

Attach facing up

Seam

01_EN_3P405106-10.indb   9

4/21/2015   4:29:07 PM

Summary of Contents for VRV IV BSQ36TVJ

Page 1: ...A HANDY PLACE FOR FUTURE REFERENCE English Fran ais Espa ol 3P405106 10 LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUI...

Page 2: ...onnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When install...

Page 3: ...amps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat...

Page 4: ...uc tions CONTENTS Safety considerations i Codes and Regulations ii 1 BEFORE INSTALLATION 2 2 SELECTING INSTALLATION SITE 3 3 PREPARATIONS BEFORE INSTALLATION 4 4 BRANCH SELECTOR UNIT INSTALLATION 4 5...

Page 5: ...l BSQ96TVJ Name 1 Accessory pipes 2 Clamp 3 Insulation tube Explanation Document Quantity 1 pc 2 pcs 16 pcs 2 pcs 2 pcs 1 pc 1 copy Shape 1 1 f3 4 f19 1 1 2 f3 4 f19 1 3 1 Medium 3 2 Small 3 3 Large I...

Page 6: ...here the wall is not significantly tilted Where sufficient clearance for maintenance and service can be ensured Refer to Fig 1 Locations where an inspection hole refer to Fig 2 can be installed to the...

Page 7: ...or less Unit Suspension bolt pitch Example installation Note All the above parts are part to be procured in the field Fig 3 Unit in mm 4 BRANCH SELECTOR UNIT INSTALLATION Use only accessories and par...

Page 8: ...uction gas pipes gas pipes and the pipe connections for these Not insulating these pipes could result in water leaks or burns In particular low temperature gas flows in the high low pressure gas pipin...

Page 9: ...or perform brazing while nitrogen is flowing in the refrigerant piping 2 refer to Fig 5 1 For details on nitrogen replacement see the VRV Installation Manual available at any Daikin dealer 2 The pres...

Page 10: ...pressure gas pipe Liquid pipe Branch Selector unit Refrigerant branch kit Upstream Downstream Table 3 Indoor unit total capacity and pipe size Total capacity index of indoor units x Pipe size Outside...

Page 11: ...or unit total capacity is more than 36 but less than 54 and when one indoor unit with a capacity of 42 to 54 is connected downstream When the downstream indoor unit total capacity is 54 or more but 60...

Page 12: ...Selector unit Clamp 2 Accessory Clamp 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 1 Accessory Insulation tube 3 2 Accessory...

Page 13: ...and be sure the terminal board wiring to the outdoor unit and indoor unit are properly matched If wiring and piping between the outdoor unit Branch Selector unit and an indoor unit are mismatched the...

Page 14: ...ranch Selector unit B Final Branch Selector unit C H SELECTOR COOL HEAT SELECTOR COOL HEAT SELECTOR COOL HEAT SELECTOR C H SELECTOR C H SELECTOR TO IN D UNIT TOOUT DUNIT TO IN D UNIT TOOUT DUNIT TO IN...

Page 15: ...through the wire through hole right and into the control box and use the included clamps 2 to securely hold the wires in 2 places Be sure to wire the ground wire so that comes out of the slit in the...

Page 16: ...in a malfunction or breakdown After the wiring working is complete use sealer field supply to seal closed the wire through hole Entry by small animals etc could cause a malfunction 7 INITIAL SETTING W...

Page 17: ...ctory shipment 2 1 8 1 3 3 6 2 4 5 4 3 5 7 2 4 6 9 0 5 7 10 8 6 8 12 6 7 8 ADDING AN ADDITIONAL CHARGE OF REFRIGERANT Follow the instructions in the installation manual that came with the outdoor unit...

Page 18: ...3P405106 10 EM14A004A 1506 HT 5151 San Felipe Suite 500 Houston TX 77056 00_CV_3P405106 10 indd 2 4 20 2015 3 09 18 PM...

Reviews: