3P405106-10 English

10

6.  ELECTRIC WIRING WORK

6-1  General instructions

• 

All wiring must be performed by an authorized electrician.

• 

All field supplied parts and materials, electric works must conform to local codes.

• 

Always ground wires. (In accordance with national regulations of the pertinent country.)

• 

Always turn off the power before performing the electric wire installation work.

• 

Follow the “WIRING DIAGRAM” attached to the unit body to wire the outdoor unit and indoor units.

• 

Properly connect wire of the specified wire type and copper thickness. Also use the included clamp to 

avoid applying excessive force to the terminal (field wire, ground wire).

• 

Do no let the ground wire should come in contact with gas pipes, water pipes, lighting rods, or telephone ground 

wires.

• 

Gas pipes: gas leaks can cause explosions and fire.

• 

Water pipes: cannot be grounded if hard vinyl pipes are used.

• 

Telephone ground and lightning rods: the ground potential when struck by lightning gets extremely 

high.

• 

A circuit breaker capable of shutting down the power supply to the entire system must be installed.

• 

This system consists of multiple Branch Selector unit. Mark each Branch Selector unit as unit A, unit B . . . , 

and be sure the terminal board wiring to the outdoor unit and indoor unit are properly matched. If wiring and 

piping between the out door unit, Branch Selector unit and an indoor unit are mismatched, the system may 

cause a malfunction.

• 

Do not turn on the power supply (branch switches, overload interrupters) until all other work is done.

6-2  Example for the whole system

Power supply wiring

Transmission wiring

Circuit protection 

safety devices in 

accordance with local 

and national codes 

Outdoor unit

Power supply

Power supply

Main switch

Main switch

Branch 

Selector 

unit

Indoor unit

Remote controller

Cooling/Heating selectable indoor unit

Cooling-dedicated 
indoor unit

6-3  Power circuit, safety device and cable requirements

• 

A power circuit (

refer to Table 6) must be provided for connection of the unit. The circuit must be pro-

tected with safety devices in accordance with local and national codes. i.e a fuse, a circuit breaker or a 

GFCI.

• 

When using residual current operated circuit breakers, be sure to use a high-speed type (0.1 second or 

less) 30 mA rated residual operating current.

• 

Use copper conductors only.

• 

Use insulated wire for the power cord.

• 

Select the power supply cable type and size in accordance with relevant local and national regulations.

• 

Use vinyl cord with sheath or cable (2-wire) of AWG 18-16 for transmission wiring.

01_EN_3P405106-10.indb   10

4/21/2015   4:29:07 PM

Summary of Contents for VRV IV BSQ36TVJ

Page 1: ...A HANDY PLACE FOR FUTURE REFERENCE English Fran ais Espa ol 3P405106 10 LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUI...

Page 2: ...onnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When install...

Page 3: ...amps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat...

Page 4: ...uc tions CONTENTS Safety considerations i Codes and Regulations ii 1 BEFORE INSTALLATION 2 2 SELECTING INSTALLATION SITE 3 3 PREPARATIONS BEFORE INSTALLATION 4 4 BRANCH SELECTOR UNIT INSTALLATION 4 5...

Page 5: ...l BSQ96TVJ Name 1 Accessory pipes 2 Clamp 3 Insulation tube Explanation Document Quantity 1 pc 2 pcs 16 pcs 2 pcs 2 pcs 1 pc 1 copy Shape 1 1 f3 4 f19 1 1 2 f3 4 f19 1 3 1 Medium 3 2 Small 3 3 Large I...

Page 6: ...here the wall is not significantly tilted Where sufficient clearance for maintenance and service can be ensured Refer to Fig 1 Locations where an inspection hole refer to Fig 2 can be installed to the...

Page 7: ...or less Unit Suspension bolt pitch Example installation Note All the above parts are part to be procured in the field Fig 3 Unit in mm 4 BRANCH SELECTOR UNIT INSTALLATION Use only accessories and par...

Page 8: ...uction gas pipes gas pipes and the pipe connections for these Not insulating these pipes could result in water leaks or burns In particular low temperature gas flows in the high low pressure gas pipin...

Page 9: ...or perform brazing while nitrogen is flowing in the refrigerant piping 2 refer to Fig 5 1 For details on nitrogen replacement see the VRV Installation Manual available at any Daikin dealer 2 The pres...

Page 10: ...pressure gas pipe Liquid pipe Branch Selector unit Refrigerant branch kit Upstream Downstream Table 3 Indoor unit total capacity and pipe size Total capacity index of indoor units x Pipe size Outside...

Page 11: ...or unit total capacity is more than 36 but less than 54 and when one indoor unit with a capacity of 42 to 54 is connected downstream When the downstream indoor unit total capacity is 54 or more but 60...

Page 12: ...Selector unit Clamp 2 Accessory Clamp 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 1 Accessory Insulation tube 3 2 Accessory...

Page 13: ...and be sure the terminal board wiring to the outdoor unit and indoor unit are properly matched If wiring and piping between the outdoor unit Branch Selector unit and an indoor unit are mismatched the...

Page 14: ...ranch Selector unit B Final Branch Selector unit C H SELECTOR COOL HEAT SELECTOR COOL HEAT SELECTOR COOL HEAT SELECTOR C H SELECTOR C H SELECTOR TO IN D UNIT TOOUT DUNIT TO IN D UNIT TOOUT DUNIT TO IN...

Page 15: ...through the wire through hole right and into the control box and use the included clamps 2 to securely hold the wires in 2 places Be sure to wire the ground wire so that comes out of the slit in the...

Page 16: ...in a malfunction or breakdown After the wiring working is complete use sealer field supply to seal closed the wire through hole Entry by small animals etc could cause a malfunction 7 INITIAL SETTING W...

Page 17: ...ctory shipment 2 1 8 1 3 3 6 2 4 5 4 3 5 7 2 4 6 9 0 5 7 10 8 6 8 12 6 7 8 ADDING AN ADDITIONAL CHARGE OF REFRIGERANT Follow the instructions in the installation manual that came with the outdoor unit...

Page 18: ...3P405106 10 EM14A004A 1506 HT 5151 San Felipe Suite 500 Houston TX 77056 00_CV_3P405106 10 indd 2 4 20 2015 3 09 18 PM...

Reviews: