Penyelesaian Masalah Menggunakan Remote Kontrol
Si341213
Diagnosis Servis
126
Replace the unit outdoor main
PCB.
Correct the relay wires of the
outdoor multi and then reset the
Catu Daya.
Replace the unit outdoor main
PCB.
Correct the relay wires of the
outdoor multi and then reset the
Catu Daya.
Replace the unit outdoor main
PCB.
Correct the relay wires of the
outdoor multi and then reset the
Catu Daya.
Diagnosis Flow 8
Confirmation of error 3 Confirmation of error 4
Check
the connection status
of the relay wires of outdoor multi.
NO
Check if the wiring has any connection error or
broken, or is about to be
disconnected.
YES
Diagnosis Flow 7
Confirmation of error 3 Confirmation of error 4
In the
connection
status of the outdoor
multi, check if more than 4
unit outdoors are
connected.
NO
YES
Diagnosis Flow 6
Confirmation of error 3 Confirmation of error 4
Check the
connection status of
one of the relay wires of outdoor
multi. Check if the wiring is broken
or disconnected.
NO
YES