![background image](http://html1.mh-extra.com/html/daikin/vrv-iii-rqq8-48py1/vrv-iii-rqq8-48py1_service-manual_2459193130.webp)
Penyelesaian Masalah Menggunakan Remote Kontrol
Si341213
Diagnosis Servis
120
Do all the units
indicate “
U9
”?
NO
YES
Did more than 2
minutes pass since
“
U9
”
was indicated?
NO
YES
Penyelesaian
Masalah
Perhatian
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Continued from the previous
halaman In Confirmation of error
4,
LED lamp indicates as follows:
Start operation of all the Unit
Indoor.
Continue the operation.
Make a diagnosis again based on
the indication in 2 minutes and
over.
The Unit Indoor PCB indicating
“
U9
” are normal.
Check the Unit Indoor in the other
circuits to diagnose failure
according to the corresponding
Kode kesalahans.