Si341213
Penyelesaian Masalah Menggunakan Remote Kontrol
137
Diagnosis Servis
CHECK 11
Termistor Resistance / Temperature Characteristics
Unit outdoor
Unit outdoor
Unit outdoor
For radiation sirip
R1T
For outdoor air
R1T
For discharge pipe
R3T,
For penerima ketinggian air
R2T
R31T~R33T
For refrigeran regulator liquid R4T
pipe
For
subcooling
heat
R5T
exchanger outlet
For pipa cairan
R6T
For penerima outlet ventilasi
gas
R7T
For pipa hisap
R8T
For penukar panas deicer
R9T
T°C
k
-30
361.7719
-25
265.4704
-20
196.9198
-15
147.5687
-10
111.6578
-5
85.2610
0
65.6705
5
50.9947
10
39.9149
15
31.4796
20
25.0060
25
20.0000
30
16.1008
35
13.0426
40
10.6281
45
8.7097
50
7.1764
55
5.9407
60
4.9439
65
4.1352
70
3.4757
75
2.9349
80
2.4894
85
2.1205
90
1.8138
95
1.5575
100
1.3425
105
1.1614
3SA48001 (AD87A001J)
3PA61998L (AD92A057)
3SA48006 (AD87A001J)
T°C
k
-30
354.1
-25
259.7
-20
192.6
-15
144.2
-10
109.1
-5
83.25
0
64.10
5
49.70
10
38.85
15
30.61
20
24.29
25
19.41
30
15.61
35
12.64
40
10.30
45
8.439
50
6.954
55
5.761
60
4.797
65
4.014
70
3.375
75
2.851
80
2.418
85
2.060
90
1.762
95
1.513
100
1.304
105
1.128
110
0.9790
115
0.8527
120
0.7450
125
0.6530
130
0.5741
T°C
k
-30
3257.371
-25
2429.222
-20
1827.883
-15
1387.099
-10
1061.098
-5
817.9329
0
635.0831
5
496.5712
10
391.0070
15
309.9511
20
247.2696
25
198.4674
30
160.2244
35
130.0697
40
106.1517
45
87.0725
50
71.7703
55
59.4735
60
49.5180
65
41.4168
70
34.7923
75
29.3499
80
24.8586
85
21.1360
90
18.0377
95
15.4487
100
13.2768
105
11.4395
110
9.8902
115
8.5788
120
7.4650
125
6.5156
130
5.7038
135
5.0073
140
4.4080
145
3.8907
150
3.4429