Penyelesaian Masalah Menggunakan Remote Kontrol
Si341213
Diagnosis Servis
116
CHECK 4
Refer to P.136
Replace the noise filter PCB
(A3P).
(Defective of noise filter)
Replace the PCB Inverter (A4P).
If the PCB Inverter is
badly damaged, recheck
the compressor.
Check the harness.
Continue the operation.
The error may temporarily
result from external factors.
Causes: Instantaneous
power failure (open fasa),
noises, or else.
Turn ON the power supply,
and start operation.
A
Stop
(standby) before the fan
rotates.
NO
YES
Stop
(standby) when the
compressor
startup.
NO
YES
The "
U2
" error
recurs.
YES
NO