NOTES

The above Table 3 of Electrical Characteristics refers to one BS unit.

See the Engineering data book for other details.

7-4 WIRING EXAMPLE

Here is shown a wiring example for one system transmission wiring.

Connect terminals F1 and F2 (TO IN/D UNIT) on the control PCB (A1P) in the outdoor unit EL. COMPO. 
BOX and terminals F1 and F2 (TO OUT/D UNIT) of the control PCB (A1P) of the first BS unit A.

NOTES

1.

Connect cooling-dedicated air conditioners to terminals F1 and F2 (TO OUT/D UNIT) of the final BS unit.

2.

Use 2-core wire for the transmission wiring. Using a multi-core wire with 3 or more cores when two or more 
indoor units are used at once could cause abnormal stoppage. (Only use 3-core wire in the COOL/HEAT 
SELECTOR.)

3.

Absolutely do not connect the power supply wiring to the transmission wiring terminal block. Doing so 
could damage the entire system.

4.

For the transmission wiring, use wire that is within the following ranges. Exceeding these limits could 
cause a transmission error.

(1)

Between an outdoor unit and BS unit,
Between a BS unit and indoor unit, and
Between a BS unit and BS unit

Maximum wiring length: 1000m or less
Total wiring length: 2000 or less
Branch point max: 16 branch points

(2)

Between a BS unit and COOL/HEAT SELECTOR

Maximum wiring length: 500m or less

7-5 WIRING CONNECTIONS

Remove the EL. COMPO. BOX lid on the side and follow the directions to connect the wires.

Transmission wiring

Remove the EL. COMPO. BOX lid and connect the wires to F1 and F2 (TO IN/D UNIT) and F1 and F2 (TO 
OUT/D UNIT) transmission wiring terminals (control PCB (A1P)).
At this time, pass the wiring into the unit through the wiring through hole (left) and use the included clamps 2) 
to securely hold the wires (in 2 places).

Power supply wiring and ground wire

Remove the EL. COMPO. BOX lid and connect the power supply wiring to 
the power terminal block (X1M).
Also connect the ground wire to the ground wire terminal. Pass both the 
power supply wire and the ground wire together through the wire through 
hole (right) and into the EL. COMPO. BOX and use the included clamps 2) to 
securely hold the wires (in 2 places).
Be sure to wire the ground wire so that comes out of the slit in the cup washer.
(Not doing so could cause insufficient ground wire contact and causing the wire not to function as a ground.)

F1 F2

F1

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

F2 F1 F2

F1 F2

F1 F2 F1 F2

F1 F2 F1 F2

A

A

B C

A

B C

A

B C

B

C

A

B

C

A

B

C

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(2)

(2)

(2)

Absolutely do not 
connect the power 
supply wiring.

Transmission wiring

Use 2-core wires.
(There is no polarity.)

COOL/HEAT SELECTOR wiring

Use 3-core wires. (There is polarity. 
Match the terminal numbers.)

Cooling/Heating selectable indoor unit

Cooling-dedicated 

indoor unit

Outdoor unit

BS unit A

BS unit B

Final BS unit

C/H SELECTOR

COOL/HEAT

SELECTOR

COOL/HEAT

SELECTOR

COOL/HEAT

SELECTOR

C/H SELECTOR

C/H SELECTOR

TO IN/D UNIT TO OUT/D UNIT

TO IN/D UNIT TO OUT/D UNIT

TO IN/D UNIT TO OUT/D UNIT

TO IN/D UNIT TO OUT/D UNIT

F1 F2

F1 F2

F1 F2

F1 F2

F1 F2

branch

Sub-branching

Cut out section

Cup washer

Ring-type crimp 
style terminal

01_EN_3P194121-1E.fm  Page 13  Thursday, September 4, 2008  5:33 PM

Summary of Contents for VRV III BSVQ100PV1

Page 1: ...MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVUL...

Page 2: ...Q32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1...

Page 3: ...tions properly may result in property damage or per sonal injury which may be serious depending on the circumstances WARNING Ask your dealer or qualified personnel to carry out installation work Do no...

Page 4: ...rant that has leaked from refrigerant pipes or other areas as there is a danger of frostbite CAUTION Install the BS units power cord and connecting wires at least 1 meter away from televisions or radi...

Page 5: ...logue for indoor outdoor unit models that can be connected Normal operation is not possible when connecting units that are originally designed for other refrigerants 2 2 PRECAUTIONS Hold the unit by t...

Page 6: ...o Fig 1 Locations where an inspection hole Refer to Fig 2 can be installed to EL COMPO BOX side See Note Where the total piping length involving indoor unit and outdoor unit is below the allowable pip...

Page 7: ...so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets that are kept within 1 meter of t...

Page 8: ...For M8 Outside diameter dimension 24 to 28mm For M10 Outside diameter 30 to 34mm 2 pcs 4 locations field supply from both the top and bottom sides of the hanging bracket and make sure they are tighte...

Page 9: ...ing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outdoor units are filled with refrigerant 6 1 PIPING...

Page 10: ...ing a chlorine flux may cause the pipes to corrode and if it contains fluoride it may cause the refrigerant lubricant to deteriorate adversely affecting the refrigerant piping system Use phosphor copp...

Page 11: ...ameter minimum thickness Gas pipe Liquid pipe 20 25 32 40 50 12 7 0 80 6 4 0 80 63 80 100 125 15 9 0 99 9 5 0 80 200 19 1 0 80 250 22 2 0 80 mm BS unit Piping size outer diameter Gas pipe Liquid pipe...

Page 12: ...ite piping Liquid pipe Site piping BS unit Top Accessory pipes 1 2 Accessory pipes 1 1 Gas pipe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site piping HP LP gas pipe Site piping...

Page 13: ...ms facing up See figure at right BSVQ100 160P type BSVQ250P type BS unit BS unit Clamp 2 2 Accessory Clamp 2 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2...

Page 14: ...nd an indoor unit are mismatched the system may cause a malfunction Do not turn on the power supply branch switches overload interrupters until all other work is done 7 2 EXAMPLE FOR THE WHOLE SYSTEM...

Page 15: ...t the wires to F1 and F2 TO IN D UNIT and F1 and F2 TO OUT D UNIT transmission wiring terminals control PCB A1P At this time pass the wiring into the unit through the wiring through hole left and use...

Page 16: ...t the wires Do not pass the transmission wiring and power supply wiring through the same locations and outside of the unit keep them separated by at least 50mm Not doing so could cause the transmissio...

Page 17: ...Setting method The setting is made using the Local Setting Mode by the remote controller of indoor unit connected to the BS unit For information regarding the setting method refer to Engineering data...