Note: The EL. COMPO. BOX mounting surface can be changed.

For information on how to change the mounting surface, refer to “

5. BS UNIT INSTALLATION”

.

NOTES

Study if the installation location is strong enough to hold the weight of the unit, and if necessary reinforce 
the area with a beam or other member and then install suspension bolts. Use the suspension bolts to install 
the unit. (Refer to “

4. PREPARATIONS BEFORE INSTALLATION”

)

Install the BS unit and its power supply wiring and transmission wiring at least 1 meter away from televi-
sions and radios to prevent image distortion and noise in those devices. Noise may still be introduced at this 
distance depending on the electromagnetic wave conditions.

4. PREPARATIONS BEFORE INSTALLATION

Refer the figure 3 and install the suspension bolts and hanging brackets.

Suspension bolts: For supporting the product

Use M8-M10 suspension bolts.

When holes are to be made anew, used embedded inserts and embedded foundation bolts. When holes 
are already provided, use hole-in-anchors or the like.
Install the BS unit so that its weight can be withstood.

Hanging bracket: For supporting the connection pipe

Be sure to support the connection piping around the unit using hanging brackets that are kept within 
1 meter of the body side surface. Hanging excessive weight on the BS unit hanging bracket could cause the 
unit to fall and injure someone.

(mm)

BS Unit Name

BSVQ100P
BSVQ160P
BSVQ250P

250 or more

250 or more (*2)
300 or more (*3)

250 or more (*1)
250 or more (*2)
300 or more (*3)

A

B

(*1) When using accessory pipes 1)-1, 2 (Refer to 6-5 PIPING 

CONNECTION), provide a service space of at least 300mm.

(*2) When using accessory pipes 1)-1, 2 (Refer to 6-5 PIPING 

CONNECTION), provide a service space of at least 350mm.

(*3) When using accessory pipes 1)-1, 2 (Refer to 6-5 PIPING 

CONNECTION), provide a service space of at least 400mm.

A

B

Indoor unit 

side (2 pipes)

(mm)

Outdoor unit 

side (3 pipes)

65 or 

more

50 or 

more

BS unit 

proper top

EL. COMPO. BOX

Inspection hole    450

(mm)

Be sure to open this to the 
EL. COMPO. BOX side.

Fig. 1

Fig. 2

428

219

Hanging 
bracket

Suspension 
bolt

Long nut or
turnbuckle

Anchor

1m or less

1m or less

Unit 

proper

<Suspension bolt pitch>

<Example installation>

Note: All the above parts are part to be procured in the field.

Fig. 3

01_EN_3P194121-1E.fm  Page 5  Thursday, September 4, 2008  5:33 PM

Summary of Contents for VRV III BSVQ100PV1

Page 1: ...MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVUL...

Page 2: ...Q32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1...

Page 3: ...tions properly may result in property damage or per sonal injury which may be serious depending on the circumstances WARNING Ask your dealer or qualified personnel to carry out installation work Do no...

Page 4: ...rant that has leaked from refrigerant pipes or other areas as there is a danger of frostbite CAUTION Install the BS units power cord and connecting wires at least 1 meter away from televisions or radi...

Page 5: ...logue for indoor outdoor unit models that can be connected Normal operation is not possible when connecting units that are originally designed for other refrigerants 2 2 PRECAUTIONS Hold the unit by t...

Page 6: ...o Fig 1 Locations where an inspection hole Refer to Fig 2 can be installed to EL COMPO BOX side See Note Where the total piping length involving indoor unit and outdoor unit is below the allowable pip...

Page 7: ...so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets that are kept within 1 meter of t...

Page 8: ...For M8 Outside diameter dimension 24 to 28mm For M10 Outside diameter 30 to 34mm 2 pcs 4 locations field supply from both the top and bottom sides of the hanging bracket and make sure they are tighte...

Page 9: ...ing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outdoor units are filled with refrigerant 6 1 PIPING...

Page 10: ...ing a chlorine flux may cause the pipes to corrode and if it contains fluoride it may cause the refrigerant lubricant to deteriorate adversely affecting the refrigerant piping system Use phosphor copp...

Page 11: ...ameter minimum thickness Gas pipe Liquid pipe 20 25 32 40 50 12 7 0 80 6 4 0 80 63 80 100 125 15 9 0 99 9 5 0 80 200 19 1 0 80 250 22 2 0 80 mm BS unit Piping size outer diameter Gas pipe Liquid pipe...

Page 12: ...ite piping Liquid pipe Site piping BS unit Top Accessory pipes 1 2 Accessory pipes 1 1 Gas pipe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site piping HP LP gas pipe Site piping...

Page 13: ...ms facing up See figure at right BSVQ100 160P type BSVQ250P type BS unit BS unit Clamp 2 2 Accessory Clamp 2 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2...

Page 14: ...nd an indoor unit are mismatched the system may cause a malfunction Do not turn on the power supply branch switches overload interrupters until all other work is done 7 2 EXAMPLE FOR THE WHOLE SYSTEM...

Page 15: ...t the wires to F1 and F2 TO IN D UNIT and F1 and F2 TO OUT D UNIT transmission wiring terminals control PCB A1P At this time pass the wiring into the unit through the wiring through hole left and use...

Page 16: ...t the wires Do not pass the transmission wiring and power supply wiring through the same locations and outside of the unit keep them separated by at least 50mm Not doing so could cause the transmissio...

Page 17: ...Setting method The setting is made using the Local Setting Mode by the remote controller of indoor unit connected to the BS unit For information regarding the setting method refer to Engineering data...

Page 18: ...0809 HT 3P194121 1F EM06A053B 00_CV_3P194121 1F fm Page 2 Friday September 19 2008 9 57 AM...

Reviews: