6-2 PROTECTION AGAINST CONTAMINATION WHEN INSTALLING PIPES

Protect the piping to prevent moisture, dirt, dust, etc. from entering the piping.

NOTE

Exercise special caution to prevent dirt or dust when passing piping through holes in walls and when passing 
pipe edges to the exterior.

6-3 PIPING CONNECTION WORK PRECAUTIONS

When brazing refrigerant piping, begin working after replacing the nitrogen (*1) or perform brazing while 
nitrogen is flowing in the refrigerant piping (*2) (

Refer to Fig. 5

), and at the end made the indoor unit and 

BS unit flare or flange connections.
(*1) For details on nitrogen replacement, see the “VRV Installation Manual” (available at any Daikin dealer).
(*2) The pressure regulator for the nitrogen released when doing the brazing should be set to about 

0.02 MPa (0.2kg/cm

2

:Enough to feel a slight breeze on your cheek).

NOTES

Do not use an anti-oxidizing agent when brazing the piping. Residual debris could clog the piping or cause 
parts to malfunction.

Do not use a flux when brazing the refrigerant pipe joints.
Using a chlorine flux may cause the pipes to corrode, and if it contains fluoride it may cause the refrigerant 
lubricant to deteriorate, adversely affecting the refrigerant piping system.
Use phosphor copper brazing (BCuP-2: JIS Z 3264/B-Cu93P-710/795: ISO 3677) which does not require 
flux.

6-4 PIPING SIZE SELECTION

From 

Example of connection 1

 and 

2

 below and 

Table 1

2

, select the piping size between the outdoor unit 

(refrigerant branch kit) and BS unit, and between the BS unit and the indoor unit (refrigerant branch kit).

Example of connection 1: When 1 indoor unit is connected downstream from the BS unit

Place

Installation period

Protection method

Outdoor

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor

Regardless of the period

Refrigerant piping

Valve

Pressure-reducing valve

Part to be brazed

Taping

Nitrogen

Nitrogen

Fig. 5

To refrigerant branch 
kit or outdoor unit

*

Suction gas pipe

<Upstream>

<Downstream>

Gas pipe

Indoor unit

Liquid pipe

HP/LP gas pipe

Liquid pipe

Determine using 

Table 1

 based 

on the total capacity of the indoor 
units connected downstream.

Select from 

Table 2

 depending 

on the capacity type of the 
indoor unit.

BS

unit

01_EN_3P194121-1E.fm  Page 8  Thursday, September 4, 2008  5:33 PM

Summary of Contents for VRV III BSVQ100PV1

Page 1: ...MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVUL...

Page 2: ...Q32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1...

Page 3: ...tions properly may result in property damage or per sonal injury which may be serious depending on the circumstances WARNING Ask your dealer or qualified personnel to carry out installation work Do no...

Page 4: ...rant that has leaked from refrigerant pipes or other areas as there is a danger of frostbite CAUTION Install the BS units power cord and connecting wires at least 1 meter away from televisions or radi...

Page 5: ...logue for indoor outdoor unit models that can be connected Normal operation is not possible when connecting units that are originally designed for other refrigerants 2 2 PRECAUTIONS Hold the unit by t...

Page 6: ...o Fig 1 Locations where an inspection hole Refer to Fig 2 can be installed to EL COMPO BOX side See Note Where the total piping length involving indoor unit and outdoor unit is below the allowable pip...

Page 7: ...so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets that are kept within 1 meter of t...

Page 8: ...For M8 Outside diameter dimension 24 to 28mm For M10 Outside diameter 30 to 34mm 2 pcs 4 locations field supply from both the top and bottom sides of the hanging bracket and make sure they are tighte...

Page 9: ...ing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outdoor units are filled with refrigerant 6 1 PIPING...

Page 10: ...ing a chlorine flux may cause the pipes to corrode and if it contains fluoride it may cause the refrigerant lubricant to deteriorate adversely affecting the refrigerant piping system Use phosphor copp...

Page 11: ...ameter minimum thickness Gas pipe Liquid pipe 20 25 32 40 50 12 7 0 80 6 4 0 80 63 80 100 125 15 9 0 99 9 5 0 80 200 19 1 0 80 250 22 2 0 80 mm BS unit Piping size outer diameter Gas pipe Liquid pipe...

Page 12: ...ite piping Liquid pipe Site piping BS unit Top Accessory pipes 1 2 Accessory pipes 1 1 Gas pipe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site piping HP LP gas pipe Site piping...

Page 13: ...ms facing up See figure at right BSVQ100 160P type BSVQ250P type BS unit BS unit Clamp 2 2 Accessory Clamp 2 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2...

Page 14: ...nd an indoor unit are mismatched the system may cause a malfunction Do not turn on the power supply branch switches overload interrupters until all other work is done 7 2 EXAMPLE FOR THE WHOLE SYSTEM...

Page 15: ...t the wires to F1 and F2 TO IN D UNIT and F1 and F2 TO OUT D UNIT transmission wiring terminals control PCB A1P At this time pass the wiring into the unit through the wiring through hole left and use...

Page 16: ...t the wires Do not pass the transmission wiring and power supply wiring through the same locations and outside of the unit keep them separated by at least 50mm Not doing so could cause the transmissio...

Page 17: ...Setting method The setting is made using the Local Setting Mode by the remote controller of indoor unit connected to the BS unit For information regarding the setting method refer to Engineering data...

Page 18: ...0809 HT 3P194121 1F EM06A053B 00_CV_3P194121 1F fm Page 2 Friday September 19 2008 9 57 AM...

Reviews: