6

English

5. BS UNIT INSTALLATION

Use only accessories and parts which are of the designated specification when installing.

(1)

When necessary, use the following procedure to change the EL. COMPO. BOX mounting surface. 
(

Refer to Fig. 4

)

1) Remove the EL. COMPO. BOX lid. (2 screws)
2) Remove the EL. COMPO. BOX. (2 screws)
3) Remove the top panel. (4 screws)
4) Remove the coil cover. (1 screw)
5) Change the pull out direction of the wire (motorized valve coil) between the body and the EL. COMPO. 

BOX.

6) Rotate the coil cover 180 degrees and attach it.
7) Turn the top panel around 180 degrees and attach it.
8) Attach the EL. COMPO. BOX.
9) Attach the EL. COMPO. BOX lid.

(2)

Attach the hooks to the suspension bolts.
Be sure to use the nuts (M8 or M10: 3 pcs, 4 locations) and washers 
(For M8: Outside diameter dimension 24 to 28mm, For M10: Outside 
diameter 30 to 34mm: 2 pcs, 4 locations) (field supply) from both the 
top and bottom sides of the hanging bracket and make sure they are 
tightened correctly.

NOTES

The BS unit has a top and a bottom, so install it so that the diagonal 
lines in the figure 4 are where the top is.
(Failing to do so may prevent the unit from operating properly and increase the volume of the operating 
noise.)

Washer 
(Field supply)

Nut 
(Field supply)

BS unit 
proper

Hanging 
bracket

10 – 15mm

Nut
(Double nut)
(Field supply)

Suspension bolt
(Field supply)

EL. COMPO. BOX lid

Coil cover

Top Panel

EL. COMPO. BOX

5)-2
(Move the 
EL. COMPO. BOX)

1)

1)

2)

4), 6)

3), 7)

3), 7)

3), 7)

3), 7)

(Rotate 180 degrees)

6)

7)

(Rotate 180 degrees)

2)

9)

9)

8)

8)

4)

2)

[Before change 5)-1]

[After change 5)-3]

EL. COMPO. BOX

EL. COMPO. BOX

Remove the wire from the 
wire clip.

Pass the wire through the 
wire clip.

Fig. 4

01_EN_3P194121-1E.fm  Page 6  Thursday, September 4, 2008  5:33 PM

Summary of Contents for VRV III BSVQ100PV1

Page 1: ...MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVUL...

Page 2: ...Q32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1...

Page 3: ...tions properly may result in property damage or per sonal injury which may be serious depending on the circumstances WARNING Ask your dealer or qualified personnel to carry out installation work Do no...

Page 4: ...rant that has leaked from refrigerant pipes or other areas as there is a danger of frostbite CAUTION Install the BS units power cord and connecting wires at least 1 meter away from televisions or radi...

Page 5: ...logue for indoor outdoor unit models that can be connected Normal operation is not possible when connecting units that are originally designed for other refrigerants 2 2 PRECAUTIONS Hold the unit by t...

Page 6: ...o Fig 1 Locations where an inspection hole Refer to Fig 2 can be installed to EL COMPO BOX side See Note Where the total piping length involving indoor unit and outdoor unit is below the allowable pip...

Page 7: ...so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets that are kept within 1 meter of t...

Page 8: ...For M8 Outside diameter dimension 24 to 28mm For M10 Outside diameter 30 to 34mm 2 pcs 4 locations field supply from both the top and bottom sides of the hanging bracket and make sure they are tighte...

Page 9: ...ing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outdoor units are filled with refrigerant 6 1 PIPING...

Page 10: ...ing a chlorine flux may cause the pipes to corrode and if it contains fluoride it may cause the refrigerant lubricant to deteriorate adversely affecting the refrigerant piping system Use phosphor copp...

Page 11: ...ameter minimum thickness Gas pipe Liquid pipe 20 25 32 40 50 12 7 0 80 6 4 0 80 63 80 100 125 15 9 0 99 9 5 0 80 200 19 1 0 80 250 22 2 0 80 mm BS unit Piping size outer diameter Gas pipe Liquid pipe...

Page 12: ...ite piping Liquid pipe Site piping BS unit Top Accessory pipes 1 2 Accessory pipes 1 1 Gas pipe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site piping HP LP gas pipe Site piping...

Page 13: ...ms facing up See figure at right BSVQ100 160P type BSVQ250P type BS unit BS unit Clamp 2 2 Accessory Clamp 2 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2...

Page 14: ...nd an indoor unit are mismatched the system may cause a malfunction Do not turn on the power supply branch switches overload interrupters until all other work is done 7 2 EXAMPLE FOR THE WHOLE SYSTEM...

Page 15: ...t the wires to F1 and F2 TO IN D UNIT and F1 and F2 TO OUT D UNIT transmission wiring terminals control PCB A1P At this time pass the wiring into the unit through the wiring through hole left and use...

Page 16: ...t the wires Do not pass the transmission wiring and power supply wiring through the same locations and outside of the unit keep them separated by at least 50mm Not doing so could cause the transmissio...

Page 17: ...Setting method The setting is made using the Local Setting Mode by the remote controller of indoor unit connected to the BS unit For information regarding the setting method refer to Engineering data...

Page 18: ...0809 HT 3P194121 1F EM06A053B 00_CV_3P194121 1F fm Page 2 Friday September 19 2008 9 57 AM...

Reviews: