2-4 COMBINATION

This BS unit is only for systems for Models REYQ-P.
It cannot be connected to systems for Models REYQ-M.

For series of applicable indoor units, refer to the catalog or other literature.

Select the BS unit to fit the total capacity (sum of unit’s capacity) and max. number of the indoor units to be 
connected downstream. About indoor unit’s capacity, refer to the Table 2.

Table 1 

Table 2 

* About indoor unit’s capacity for HRV type (VKM), refer to the Engineering data book.

<

Example

>

In case of the BS unit witch connect two FXCQ

32

M and two FXSQ

40

M.

Total capacity = 

31.25

×2+

40

×2 = 142.5 

 

Select BSVQ160PV1

2-5 CHECK ITEM

For the following items, take special care during construction and check after installation is finished.

Completion check items

Hand-over check items

3. SELECTING INSTALLATION SITE

Select an installation site where the following conditions are satisfied and that meets with your customer’s 
approval.

Where is resistible against weight of BS unit.

Locations where the wall is not significantly tilted.

Where sufficient clearance for maintenance and service can be ensured. (

Refer to Fig. 1

)

Locations where an inspection hole (

Refer to Fig. 2

) can be installed to EL. COMPO. BOX side (See Note).

Where the total piping length involving indoor unit and outdoor unit is below the allowable piping length.
(See installation manual attached to outdoor unit.)

Model

Total capacity of all downstreem indoor units

Max. number of all downstreem indoor units

BSVQ100PV1

 100

5

BSVQ160PV1

100 < A 

 160

8

BSVQ250PV1

160 

<

 A 

 250

8

Capacity expressed as indoor unit’s model No.

20

25

32

40

50

63

80

100

125

200

250

Indoor unit’s capacity (for use in computation)

20

25

31.25

40

50

62.5

80

100

125

200

250

Check items

Problems

Check

Are the BS units installed securely?

Falling, vibration, and operating noise

Have you performed a gas leak test?

Does not cool or heat

Is the insulation complete? (Refrigerant piping and pipe connection part)

Water leaking

Is the voltage the same as that listed on the unit’s nameplate?

Does not operate/burnt out

Are all the wiring and piping correct?

Does not operate/burnt out

Is the unit grounded?

Dangers during electrical leak

Is the thickness of the power cord as specified?

Does not operate/burnt out

Check items

Check

Did you close the EL. COMPO. BOX lid?

Did you hand the operating manual and warranty card to the customer?

01_EN_3P194121-1E.fm  Page 4  Thursday, September 4, 2008  5:33 PM

Summary of Contents for VRV III BSVQ100PV1

Page 1: ...MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVUL...

Page 2: ...Q32PY1 E RXYQ34PY1 E RXYQ36PY1 E RXYQ38PY1 E RXYQ40PY1 E RXYQ42PY1 E RXYQ44PY1 E RXYQ46PY1 E RXYQ48PY1 E RXYQ50PY1 E RXYQ52PY1 E RXYQ54PY1 E REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1...

Page 3: ...tions properly may result in property damage or per sonal injury which may be serious depending on the circumstances WARNING Ask your dealer or qualified personnel to carry out installation work Do no...

Page 4: ...rant that has leaked from refrigerant pipes or other areas as there is a danger of frostbite CAUTION Install the BS units power cord and connecting wires at least 1 meter away from televisions or radi...

Page 5: ...logue for indoor outdoor unit models that can be connected Normal operation is not possible when connecting units that are originally designed for other refrigerants 2 2 PRECAUTIONS Hold the unit by t...

Page 6: ...o Fig 1 Locations where an inspection hole Refer to Fig 2 can be installed to EL COMPO BOX side See Note Where the total piping length involving indoor unit and outdoor unit is below the allowable pip...

Page 7: ...so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets that are kept within 1 meter of t...

Page 8: ...For M8 Outside diameter dimension 24 to 28mm For M10 Outside diameter 30 to 34mm 2 pcs 4 locations field supply from both the top and bottom sides of the hanging bracket and make sure they are tighte...

Page 9: ...ing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outdoor units are filled with refrigerant 6 1 PIPING...

Page 10: ...ing a chlorine flux may cause the pipes to corrode and if it contains fluoride it may cause the refrigerant lubricant to deteriorate adversely affecting the refrigerant piping system Use phosphor copp...

Page 11: ...ameter minimum thickness Gas pipe Liquid pipe 20 25 32 40 50 12 7 0 80 6 4 0 80 63 80 100 125 15 9 0 99 9 5 0 80 200 19 1 0 80 250 22 2 0 80 mm BS unit Piping size outer diameter Gas pipe Liquid pipe...

Page 12: ...ite piping Liquid pipe Site piping BS unit Top Accessory pipes 1 2 Accessory pipes 1 1 Gas pipe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site piping HP LP gas pipe Site piping...

Page 13: ...ms facing up See figure at right BSVQ100 160P type BSVQ250P type BS unit BS unit Clamp 2 2 Accessory Clamp 2 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2...

Page 14: ...nd an indoor unit are mismatched the system may cause a malfunction Do not turn on the power supply branch switches overload interrupters until all other work is done 7 2 EXAMPLE FOR THE WHOLE SYSTEM...

Page 15: ...t the wires to F1 and F2 TO IN D UNIT and F1 and F2 TO OUT D UNIT transmission wiring terminals control PCB A1P At this time pass the wiring into the unit through the wiring through hole left and use...

Page 16: ...t the wires Do not pass the transmission wiring and power supply wiring through the same locations and outside of the unit keep them separated by at least 50mm Not doing so could cause the transmissio...

Page 17: ...Setting method The setting is made using the Local Setting Mode by the remote controller of indoor unit connected to the BS unit For information regarding the setting method refer to Engineering data...

Page 18: ...0809 HT 3P194121 1F EM06A053B 00_CV_3P194121 1F fm Page 2 Friday September 19 2008 9 57 AM...

Reviews: