Troubleshooting by Indication on the Remote Controller
Si39-306
188
Troubleshooting
2.36
“
L8
”
Outdoor Unit:
Inverter Current Abnormal
Remote
Controller
Display
L8
Applicable
Models
REYQ8~48M
Method of
Malfunction
Detection
Malfunction is detected by current flowing in the power transistor.
Malfunction
Decision
Conditions
When overload in the compressor is detected.
Supposed
Causes
Compressor overload
Compressor coil disconnected
Defect of inverter PC board
Troubleshooting
Output current check
Refer check 13 to P.234.
(V2813)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Inverter
output
voltage check
Inverter output voltage
is not balanced.
(Normal if within
±
10V)
Must be measured
when frequency
is stable.
Compressor overload
Inspection of the compressor and
refrigerant system is required.
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
compressor.
NO
Replace the inverter PC board.
YES
NO
Reset and restart.
NO
The secondary
current of the inverter is
higher than 15A
for each phase.
Replace the compressor.
NO
YES
Compressor
inspection The
compressor's coil is
disconnected.
YES
YES
Check No. 13
Disconnect the the connection
between the compressor and
inverter. Make the power
transistor check mode setting
ON by service mode.
After turning
on again, "L8" blinks
again.
Summary of Contents for VRV II REYQ10MY1B
Page 19: ...Model Selection Si39 306 8 General Information ...
Page 150: ...Si39 306 Troubleshooting by Remote Controller Troubleshooting 139 ...
Page 250: ...Si39 306 Piping Diagrams Appendix 239 REYQ14MY1B REYQ16MY1B 4D042070A ...
Page 252: ...Si39 306 Piping Diagrams Appendix 241 1 3 BS Unit BSVQ100MV1 BSVQ160MV1 BSVQ250MV1 4D042115 ...
Page 254: ...Si39 306 Wiring Diagrams for Reference Appendix 243 REYQ14MY1B REYQ16MY1B 3D038572 ...
Page 256: ...Si39 306 Wiring Diagrams for Reference Appendix 245 REYQ18 20 22 24 26 28 30 32MY1B 3D043436 ...
Page 257: ...Wiring Diagrams for Reference Si39 306 246 Appendix REYQ34 36 38 40 42 44 46 48MY1B 3D043437 ...
Page 259: ...Wiring Diagrams for Reference Si39 306 248 Appendix FXCQ40M 50M 80M 125MVE 3D039557A ...
Page 260: ...Si39 306 Wiring Diagrams for Reference Appendix 249 FXZQ20M 25M 32M 40M 50MVE 3D038359 ...
Page 262: ...Si39 306 Wiring Diagrams for Reference Appendix 251 FXKQ25M 32M 40M 63MVE 3D039564A ...
Page 264: ...Si39 306 Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A ...
Page 265: ...Wiring Diagrams for Reference Si39 306 254 Appendix FXMQ200M 250MVE 3D039621A ...
Page 266: ...Si39 306 Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C ...
Page 267: ...Wiring Diagrams for Reference Si39 306 256 Appendix FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206A ...
Page 283: ...REFNET Pipe System Si39 306 272 Appendix ...
Page 284: ...Si39 306 Appendix 273 DPSOH RI RQQHFWLRQ 5 7 SH 5 4 0 HDW 5HFRYHU ...
Page 285: ...Si39 306 274 Appendix ...
Page 291: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 306 280 Appendix ...
Page 305: ...Si39 306 iv Index ...