Troubleshooting (OP: Centralized Remote Controller)
Si39-306
214
Troubleshooting
3.
Troubleshooting (OP: Centralized Remote Controller)
3.1
“
UE
”
Malfunction of Transmission between Centralized
Remote Controller and Indoor Unit
Remote
Controller
Display
UE
Applicable
Models
All models of indoor units
REYQ8~48M
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and centralized remote controller is
normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Malfunction of transmission between optional controllers for centralized control and indoor unit
Connector for setting master controller is disconnected.
Failure of PC board for centralized remote controller
Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
power supply turned
on for indoor units displaying
malfunction?
Is
transmission wiring
disconnected or wired
incorrectly?
Is the
transmission wiring
with the master controller
disconnected or wired
incorrectly?
Is the
master controller's
connector for setting
master controller
disconnected?
Set the group No. correctly.
Replace indoor unit PC
board.
Fix the wiring correctly.
Fix the wiring correctly.
Connect the connector
correctly.
Replace the central PC board.
Reset power supply
simultaneously for all optional
controllers for centralized
control.
YES
YES
NO
YES
YES
YES
YES
Turn indoor unit's power
supply.
YES
NO
NO
NO
NO
NO
NO
Has
an indoor unit once
connected been remove
or its address
changed?
Is the group
No. of malfunctioning
indoor units set?
Is transmission
with all indoor units
malfunctioning?
(V2832)
Summary of Contents for VRV II REYQ10MY1B
Page 19: ...Model Selection Si39 306 8 General Information ...
Page 150: ...Si39 306 Troubleshooting by Remote Controller Troubleshooting 139 ...
Page 250: ...Si39 306 Piping Diagrams Appendix 239 REYQ14MY1B REYQ16MY1B 4D042070A ...
Page 252: ...Si39 306 Piping Diagrams Appendix 241 1 3 BS Unit BSVQ100MV1 BSVQ160MV1 BSVQ250MV1 4D042115 ...
Page 254: ...Si39 306 Wiring Diagrams for Reference Appendix 243 REYQ14MY1B REYQ16MY1B 3D038572 ...
Page 256: ...Si39 306 Wiring Diagrams for Reference Appendix 245 REYQ18 20 22 24 26 28 30 32MY1B 3D043436 ...
Page 257: ...Wiring Diagrams for Reference Si39 306 246 Appendix REYQ34 36 38 40 42 44 46 48MY1B 3D043437 ...
Page 259: ...Wiring Diagrams for Reference Si39 306 248 Appendix FXCQ40M 50M 80M 125MVE 3D039557A ...
Page 260: ...Si39 306 Wiring Diagrams for Reference Appendix 249 FXZQ20M 25M 32M 40M 50MVE 3D038359 ...
Page 262: ...Si39 306 Wiring Diagrams for Reference Appendix 251 FXKQ25M 32M 40M 63MVE 3D039564A ...
Page 264: ...Si39 306 Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A ...
Page 265: ...Wiring Diagrams for Reference Si39 306 254 Appendix FXMQ200M 250MVE 3D039621A ...
Page 266: ...Si39 306 Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C ...
Page 267: ...Wiring Diagrams for Reference Si39 306 256 Appendix FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206A ...
Page 283: ...REFNET Pipe System Si39 306 272 Appendix ...
Page 284: ...Si39 306 Appendix 273 DPSOH RI RQQHFWLRQ 5 7 SH 5 4 0 HDW 5HFRYHU ...
Page 285: ...Si39 306 274 Appendix ...
Page 291: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 306 280 Appendix ...
Page 305: ...Si39 306 iv Index ...