Special Control
Si39-306
78
Function
3.7.2 Stopping Operation of Slave Units During Master Unit is in Operation
with Multi-Outdoor-Unit System
This operation is used to make adjustments of required refrigerant amount with non-operating
slave units while the master unit is in operation.
In cooling operation : The system operates in mode A or mode B listed in the table below.
In heating operation or simultaneously in cooling / heating operation :
The system operates in mode A or mode B listed in the table below.
The changeover operation for mode A and B is performed for the reason that the required refrigerant amount varies
depending on the indoor unit operation capacity.
*
Actuators are based on REYQ16M.
Actuator
Mode-A operation
Mode-B operation
Compressor
OFF
OFF
Outdoor unit fan
STEP4
OFF
Four way valve 1
OFF
OFF
Four way valve 2
OFF
OFF
Main motorized valve (EV1)
150 pls to 300 pls
0 pls
Sub motorized valve (EV2)
0 pls
0 pls
Sub-cooling motorized valve (EV3)
Built-in compressor discharge pipe
temperature control
Built-in compressor discharge pipe
temperature control
Hot gas bypass valve (SVP)
ON
ON
Oil equalization valve (SVO)
OFF
OFF
Receiver gas charging valve (SVL)
OFF
OFF
Receiver gas discharge valve (SVG)
OFF
OFF
Discharge pipe stop valve (SVR)
OFF
OFF
Non-operating unit liquid pipe stop
valve (SVSL)
OFF
ON
High pressure gas pipe pressure
reduction valve (SVC)
ON
ON
Mode transition conditions
To Mode B when Tc-Tl
>0.27×(Tc - Ta) +6
To Mode A when gas shortage signal is
sent from indoor unit
Ending conditions
Slave units are required to operate.
Actuator
Mode-A operation
Mode-B operation
Compressor
OFF
OFF
Outdoor unit fan
Incorporated INVFIN temperature
control
Incorporated INVFIN temperature
control
Four way valve 1
ON
ON
Four way valve 2
ON
ON
Main motorized valve (EV1)
0 pls
0 pls
Sub motorized valve (EV2)
0 pls
0 pls
Sub-cooling motorized valve (EV3)
Built-in compressor discharge pipe
temperature control
Built-in compressor discharge pipe
temperature control
Hot gas bypass valve (SVP)
High/Low pressure protection control
High/Low pressure protection control
Oil equalization valve (SVO)
OFF
OFF
Receiver gas charging valve (SVL)
ON
OFF
Receiver gas discharge valve (SVG)
OFF
OFF
Discharge pipe stop valve (SVR)
ON
ON
Non-operating unit liquid pipe stop
valve (SVSL)
In case of EV3
≠
0, this valve turns ON.
In case of EV3
≠
0, this valve turns ON.
High pressure gas pipe pressure
reduction valve (SVC)
OFF
OFF
Mode transition conditions
To mode B when Tc - mean temperature
of indoor unit liquid pipes > 10
Motorized valve of outdoor unit in heat
exchange mode fully opens.
Ending conditions
Slave units are required to operate.
Mode A : Operating unit collects refrigerant.
Mode B : Stopping unit storage refrigerant.
Operating
unit
Stopping
unit
∗
Mode A or B operation
Summary of Contents for VRV II REYQ10MY1B
Page 19: ...Model Selection Si39 306 8 General Information ...
Page 150: ...Si39 306 Troubleshooting by Remote Controller Troubleshooting 139 ...
Page 250: ...Si39 306 Piping Diagrams Appendix 239 REYQ14MY1B REYQ16MY1B 4D042070A ...
Page 252: ...Si39 306 Piping Diagrams Appendix 241 1 3 BS Unit BSVQ100MV1 BSVQ160MV1 BSVQ250MV1 4D042115 ...
Page 254: ...Si39 306 Wiring Diagrams for Reference Appendix 243 REYQ14MY1B REYQ16MY1B 3D038572 ...
Page 256: ...Si39 306 Wiring Diagrams for Reference Appendix 245 REYQ18 20 22 24 26 28 30 32MY1B 3D043436 ...
Page 257: ...Wiring Diagrams for Reference Si39 306 246 Appendix REYQ34 36 38 40 42 44 46 48MY1B 3D043437 ...
Page 259: ...Wiring Diagrams for Reference Si39 306 248 Appendix FXCQ40M 50M 80M 125MVE 3D039557A ...
Page 260: ...Si39 306 Wiring Diagrams for Reference Appendix 249 FXZQ20M 25M 32M 40M 50MVE 3D038359 ...
Page 262: ...Si39 306 Wiring Diagrams for Reference Appendix 251 FXKQ25M 32M 40M 63MVE 3D039564A ...
Page 264: ...Si39 306 Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A ...
Page 265: ...Wiring Diagrams for Reference Si39 306 254 Appendix FXMQ200M 250MVE 3D039621A ...
Page 266: ...Si39 306 Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C ...
Page 267: ...Wiring Diagrams for Reference Si39 306 256 Appendix FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206A ...
Page 283: ...REFNET Pipe System Si39 306 272 Appendix ...
Page 284: ...Si39 306 Appendix 273 DPSOH RI RQQHFWLRQ 5 7 SH 5 4 0 HDW 5HFRYHU ...
Page 285: ...Si39 306 274 Appendix ...
Page 291: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 306 280 Appendix ...
Page 305: ...Si39 306 iv Index ...