background image

7

Use the insulation for fitting (3) and (4) provided to the

liquid piping and gas piping, respectively, and conduct heat

insulation work.

(Tighten both edges of the insulation for fitting (3) and (4) for

each joint with the clamp (7).)

Make sure that the joint of the insulation for fitting (4) and (5)

for the joint on the liquid piping and gas piping side faces

upward.

Wrap the middle sealing material (6) around the insulation

for fitting (3) and (4) for the joint (flare nut part).

Be sure to perform the heat insulation of the local piping

up to the piping joint.

If the piping is exposed, dew condensation may result. Fur-
theremore, a burn may be caused if a human body comes
in contact with the piping.

Perform nitrogen substituent or apply nitrogen into the

refrigerant piping (see NOTE 1) in the case of refrigerant

piping brazing (see NOTE 2). Then perform the flare con-

nection of the indoor unit. 

(Refer to Fig. 7)

Do not use any antioxidant at the time of piping brazing.

The piping may be clogged with a residual antioxidant and

parts may malfunction.

NOTE

1.

At the time of brazing, set the pressure of nitrogen to

approximately 0.02 MPa (close to the pressure of a

breeze coming in contact with the cheek) with a decom-

pression valve.

2.

Do not use flux at the time of brazing and connecting the

refrigerant piping. Use a copper phosphorus brazing alloy

(BCuP-2: JIS Z 3264/BCu 93P-710/795: ISO3677), which

does not require flux, for brazing.

(Flux has a bad influence on the refrigerant piping.

Chlorine-based flux will cause piping corrosion. Furthermore,

if

 

it contains fluorine, the flux will deteriorate refrigerant oil.)

(1) Conduct drain piping work.

Check that the piping

ensures proper draining.

• Make sure that the diam-

eter of the piping exclud-

ing the rising part is the

same as or larger than

the diameter of the con-

necting pipe (vinyl chloride pipe with an outer diameter

of 32 mm and a nominal inner diameter of 25 mm).

Make sure that the piping is short enough 

with a down-

ward slope of at least 1/100

 and that there is no air

bank formed. No drain trap is required.

• The drain piping will be clogged with water and water leak-

age may result if the water is accumulated in the drain piping.

• Conduct drain up piping work if the gradient is insufficient.

• Attach a support bracket at 1 to 1.5 m intervals for the

prevention of piping deflection.

Nitrogen

Refrigerant 

piping

Part to be 

brazed 

Taping

Pressurereducing valve

hands 

valve

Nitrogen

Fig. 7

Refrigerant 
piping

Drain socket 

Socket for 
maintenance 
(with rubber cap)

1 - 1.5 m

Support bracket

Downward slope of at least 1/100

Be sure to use the drain hose (2) and metal clamp (1).

Insert the drain hose (2) deep into the base of the drain

socket, and securely fasten the metal clamp (1) within

the taped part on the insertion front end of the hose.

Be sure to fasten the screw of the metal clamp (1) until the

margin of the screw thread decreases to 4 mm or less.

NOTE

Be sure to follow the instructions as below.

Do not connect the drain piping directly to a sewer that

smells of ammonia.

The ammonia in the sewer may reach through the drain

piping and corrode the heat exchanger of the indoor unit.

Do not bend or twist the provided drain hose (2) in order

not to impose excessive force on the hose. (Doing so

may result in water leakage.)

Take the procedure shown in the following illustration to

perform concentrated drain piping.

Select the diameter of the concentrated drain piping to

suit the capacity of equipment connecting to the concen-

trated drain piping (see the equipment design sheet).

(accessory)

(accessory)

Metal clamp (1)

Tape

Drain hose (2)

Concentrated drain piping

Maintain 

a downward slope of at least 

1/100

 so that no air bank will be formed. 

The drain piping will be clogged with water 

and water leakage may result if the water is 

accumulated in the drain piping.

0 - 467 mm

!

CAUTION

!

CAUTION

As for the branching of the refrigerant piping or refrigerant,

refer to the installation manual provided with the outdoor unit

.

4. REFRIGERANT PIPING WORK

!

CAUTION

Summary of Contents for VRV FXMQ40ARV16

Page 1: ...shocks or fire Install the air conditioner on a foundation strong enough to withstand the weight of the unit A foundation of insufficient strength may result in the equipment falling down and causing...

Page 2: ...t exerting any pressure on other parts especially the refrigerant piping drain piping flanges and other resin parts Be sure to check the type of R410A refrigerant to be used before installing the unit...

Page 3: ...liver instruction manual if any for the field supplies to the customer Hold the hanging brackets in the case of moving the indoor and outdoor units at the time of and after opening the packages Do not...

Page 4: ...cing purposes of the el compo box and drain pump prepare one of the following service spaces 1 2 Inspection hatch 1 2 450 450 for the el compo box and a minimum space of 300 mm for the lower part of t...

Page 5: ...he washer for the hanging bracket can be prevented if the washing fixing plate 8 is used During the installation work perform the curing of the air outlet and protect the resin drain pan of the indoor...

Page 6: ...lare are free of oil The drain pan and the resin part may be deteriorated if oil is attached If no torque wrenches are available refer to Table 3 as a standard When the flare nut is tightened with the...

Page 7: ...of 25 mm Make sure that the piping is short enough with a down ward slope of at least 1 100 and that there is no air bank formed No drain trap is required The drain piping will be clogged with water...

Page 8: ...ling operation according to 11 FIELD SETTING and 12 TEST OPERATION Make sure that the water is not spilled onto the electric parts of the drain pump and others Ceiling slab 1 1 5 m 300 mm max 700 mm m...

Page 9: ...g and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction A circuit breaker capable of shutting down power supply to the entire system must be installe...

Page 10: ...connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit from outside If any do get in they coul...

Page 11: ...t a screwdriver into the clearance between the grooves of the lower casing and the upper casing to remove the upper casing 2 grooves The remote controller PCB is attached to the upper casing Note Ther...

Page 12: ...possible by remote controllers Input OFF ON turns ON unit Input OFF enables control by remote con troller Input ON OFF turns OFF unit F2 T1 T2 FORCED OFF Input A SETTING MODE NO SECOND CODE NO FIELD S...

Page 13: ...door unit indoor control PCB transmission error C6 Lit Improper combination of fan driver PCB of indoor unit or setting failure in control PCB type Test operation of outdoor unit has not U3 Lit been f...

Page 14: ...formation regarding safety Be sure to observe all precautions without fail WARNING Failure to follow these instructions properly may result in personal injury or loss of life CAUTION Failure to observ...

Page 15: ...order to prevent electric shock or fire 10 Air filter inside filter chamber Sold separately 11 Suction filter chamber Sold separately 12 Suction duct Field supply 13 Machine nameplate The nameplate i...

Page 16: ...controller please clean the filter When the operating time exceeds the desig nated time this mark will be displayed If using the air conditioner under very dusty environment increase the frequency of...

Reviews: