13

Table 6

If interior finish work is continuing on completion of the test 

operation of the air conditioner, explain the customer not to 

operate the air conditioner until the interior finish work is com-

pleted for the protection of the air conditioner. 

Otherwise, substances that will be generated from interior finish 

work materials, such as paint and adhesive agents, may con-

taminate the air conditioner.

 Contents

 Remote Controller 

 Display

  "  A  B  "  Lit  

 Error in power supply votage to indoor unit.

  "  C  1  "  Lit  

 Fan driver PCB of indoor unit

 indoor control PCB transmission error.

  "  C  6  "  Lit  

 Improper combination of fan driver PCB of

 indoor unit or setting failure in control PCB type.

 Test operation of outdoor unit has not

  "  U  3  "  Lit  

 been finished.

 Contents

 Remote Controller 

 Display

"     " is Lit up

"U4" is lit up

"UH" is lit up

No display

The Power on the outdoor unit is off.

The outdoor unit has not been wired for power supply.

 

Incorrect wiring for the transmission wiring and/or

 

FORCED OFF wiring.

There is a short circuit at the FORCED OFF

 

terminals

(T1,T2)

The Power on the indoor unit is off.

The indoor unit has not been wired for power supply.

 

Incorrect wiring for the remote controller wiring,the

 

transmission wiring and/or the FORCED OFF wiring.

!

CAUTION

Table 

5

.

Summary of Contents for VRV FXMQ40ARV16

Page 1: ...shocks or fire Install the air conditioner on a foundation strong enough to withstand the weight of the unit A foundation of insufficient strength may result in the equipment falling down and causing...

Page 2: ...t exerting any pressure on other parts especially the refrigerant piping drain piping flanges and other resin parts Be sure to check the type of R410A refrigerant to be used before installing the unit...

Page 3: ...liver instruction manual if any for the field supplies to the customer Hold the hanging brackets in the case of moving the indoor and outdoor units at the time of and after opening the packages Do not...

Page 4: ...cing purposes of the el compo box and drain pump prepare one of the following service spaces 1 2 Inspection hatch 1 2 450 450 for the el compo box and a minimum space of 300 mm for the lower part of t...

Page 5: ...he washer for the hanging bracket can be prevented if the washing fixing plate 8 is used During the installation work perform the curing of the air outlet and protect the resin drain pan of the indoor...

Page 6: ...lare are free of oil The drain pan and the resin part may be deteriorated if oil is attached If no torque wrenches are available refer to Table 3 as a standard When the flare nut is tightened with the...

Page 7: ...of 25 mm Make sure that the piping is short enough with a down ward slope of at least 1 100 and that there is no air bank formed No drain trap is required The drain piping will be clogged with water...

Page 8: ...ling operation according to 11 FIELD SETTING and 12 TEST OPERATION Make sure that the water is not spilled onto the electric parts of the drain pump and others Ceiling slab 1 1 5 m 300 mm max 700 mm m...

Page 9: ...g and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction A circuit breaker capable of shutting down power supply to the entire system must be installe...

Page 10: ...connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit from outside If any do get in they coul...

Page 11: ...t a screwdriver into the clearance between the grooves of the lower casing and the upper casing to remove the upper casing 2 grooves The remote controller PCB is attached to the upper casing Note Ther...

Page 12: ...possible by remote controllers Input OFF ON turns ON unit Input OFF enables control by remote con troller Input ON OFF turns OFF unit F2 T1 T2 FORCED OFF Input A SETTING MODE NO SECOND CODE NO FIELD S...

Page 13: ...door unit indoor control PCB transmission error C6 Lit Improper combination of fan driver PCB of indoor unit or setting failure in control PCB type Test operation of outdoor unit has not U3 Lit been f...

Page 14: ...formation regarding safety Be sure to observe all precautions without fail WARNING Failure to follow these instructions properly may result in personal injury or loss of life CAUTION Failure to observ...

Page 15: ...order to prevent electric shock or fire 10 Air filter inside filter chamber Sold separately 11 Suction filter chamber Sold separately 12 Suction duct Field supply 13 Machine nameplate The nameplate i...

Page 16: ...controller please clean the filter When the operating time exceeds the desig nated time this mark will be displayed If using the air conditioner under very dusty environment increase the frequency of...

Reviews: