background image

6

Reinforce the insulation material for the refrigerant piping if 

the ambient temperature is high, or otherwise dew conden-

sation may result on the surface of the insulation material. 

Make sure that the refrigerant is R410A before refrigerant 

piping  work.  If  the  refrigerant  is  different,  the  air  condi-

tioner  will not operate normally.

This product uses new refrigerant (R410A) only. Be sure 

to keep the items on the right hand side and conduct the 

installation work.

Use an appropriate pipe cutter and flare tool for R410A.

When connecting the flare, apply ether oil or ester oil

only to inner side of the flare.

Be sure to use the flare nut provided with the unit. (Do

not use a different flare nut (such as a type-1 flare nut),

or otherwise refrigerant leakage may result.)

Perform the curing of the piping with pinching or taping

of the piping in order to prevent the intrusion of dirt,

dust, and moisture into the piping.

Be sure to use the specified type of refrigerant for the

refrigeration cycle and do not contaminate the refriger-

ant with air.

Ventilate the room in case of refrigerant leakage during

installation work.

The outdoor unit is filled with refrigerant.

• When connecting or disconnecting piping to or from the

unit, 

be sure to use two spanners and two torque

wrenches. (Refer to Fig. 4)

Refer to Table 2 for the processing dimensions of the

 

flare.

Use the flare nut provided with the unit.

Apply ether oil or ester oil only to inner side of the flare

and screw in the flare nut three to four turns first by hand at

the time of connecting the flare nut.

(Refer to Fig. 5)

Refer to Table 2 for the corresponding tightening torque.

Table 2

Do not excessively tighten the flare nut.

Doing so will break the flare nut and refrigerant leakage may

occur.

Make sure that all parts around the flare are free of oil.

The drain pan and the resin part may be deteriorated if oil is

attached.

If no torque wrenches are available, refer to Table 3 as

 

a

standard.

When the flare nut is tightened with the spanner, the

tightening torque should increase suddenly. Tighten the

 

flare

nut further for the corresponding angle shown in

 

Table 3.

Table 3

Torque wrench

Spanner

Piping union

Flare nut

Fig. 4

Pipe 

size

Tightening torque

Flare 

dimensions

A (mm)

Flare shape

 φ

6.4

14.2 – 17.2N·m

8.7 – 9.1

 φ

9.5

32.7 – 39.9N·m

12.8 – 13.2

 φ

12.7

49.5 – 60.3N·m

16.2 – 16.6

 φ

15.9

61.8 – 75.4N·m

19.3 – 19.7

Pipe size Further tightening angle

Recommended arm length of 

tool

φ 

6.4

60 to 90 degrees

Approx. 150mm

φ 

9.5

60 to 90 degrees

Approx. 200mm

φ 

12.7

30 to 60 degrees

Approx. 250mm

φ 

15.9

30 to 60 degrees

Approx. 300mm

Fig. 5

Apply ester oil or ether 

oil only to inner side of 

flare.

A

45

0

±2

0

R0.4-0.8

90

0

±2

0

 

Fig. 6

Heat insulation procedure for gas piping

Insulation material 

for piping 

(on unit side)

Insulation material 

for piping (field supply)

Make sure that 

the seam faces 

upward.

Clamp (7 
(accessory)

Gas pipe

Liquid pipe

Flare nut joint

Attached to 

the surface.

Insulation for fitting (4) (accessory)

Middle sealing pad (6) 
(accessory)

Wrap the insulation material 

around the portion from the 

surface of the main unit to the 

upper part of the flare nut joint.

Insulation material 

for piping (field supply)

Wrap the insulation material 

around the portion from the 

surface of the main unit to the 

upper part of the flare nut joint.

Heat insulation procedure for liquid piping

Insulation material 

for piping 

(on unit side)

Make sure that 

the seam faces 

upward.

Clamp (

7

(accessory)

Main unit

Flare nut joint

Attached to 

the surface.

Insulation for fitting (3)(accessory)

Middle sealing pad (6) 
(accessory)

!

CAUTION

(2) On completion of installation work, 

check that there is no gas

leakage.

(3) Refer to the illustration on the right hand side and be sure to

perform heat insulation work on the piping joints after gas leakage

checks. (Refer to Fig. 6)

!

CAUTION

Summary of Contents for VRV FXMQ40ARV16

Page 1: ...shocks or fire Install the air conditioner on a foundation strong enough to withstand the weight of the unit A foundation of insufficient strength may result in the equipment falling down and causing...

Page 2: ...t exerting any pressure on other parts especially the refrigerant piping drain piping flanges and other resin parts Be sure to check the type of R410A refrigerant to be used before installing the unit...

Page 3: ...liver instruction manual if any for the field supplies to the customer Hold the hanging brackets in the case of moving the indoor and outdoor units at the time of and after opening the packages Do not...

Page 4: ...cing purposes of the el compo box and drain pump prepare one of the following service spaces 1 2 Inspection hatch 1 2 450 450 for the el compo box and a minimum space of 300 mm for the lower part of t...

Page 5: ...he washer for the hanging bracket can be prevented if the washing fixing plate 8 is used During the installation work perform the curing of the air outlet and protect the resin drain pan of the indoor...

Page 6: ...lare are free of oil The drain pan and the resin part may be deteriorated if oil is attached If no torque wrenches are available refer to Table 3 as a standard When the flare nut is tightened with the...

Page 7: ...of 25 mm Make sure that the piping is short enough with a down ward slope of at least 1 100 and that there is no air bank formed No drain trap is required The drain piping will be clogged with water...

Page 8: ...ling operation according to 11 FIELD SETTING and 12 TEST OPERATION Make sure that the water is not spilled onto the electric parts of the drain pump and others Ceiling slab 1 1 5 m 300 mm max 700 mm m...

Page 9: ...g and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction A circuit breaker capable of shutting down power supply to the entire system must be installe...

Page 10: ...connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit from outside If any do get in they coul...

Page 11: ...t a screwdriver into the clearance between the grooves of the lower casing and the upper casing to remove the upper casing 2 grooves The remote controller PCB is attached to the upper casing Note Ther...

Page 12: ...possible by remote controllers Input OFF ON turns ON unit Input OFF enables control by remote con troller Input ON OFF turns OFF unit F2 T1 T2 FORCED OFF Input A SETTING MODE NO SECOND CODE NO FIELD S...

Page 13: ...door unit indoor control PCB transmission error C6 Lit Improper combination of fan driver PCB of indoor unit or setting failure in control PCB type Test operation of outdoor unit has not U3 Lit been f...

Page 14: ...formation regarding safety Be sure to observe all precautions without fail WARNING Failure to follow these instructions properly may result in personal injury or loss of life CAUTION Failure to observ...

Page 15: ...order to prevent electric shock or fire 10 Air filter inside filter chamber Sold separately 11 Suction filter chamber Sold separately 12 Suction duct Field supply 13 Machine nameplate The nameplate i...

Page 16: ...controller please clean the filter When the operating time exceeds the desig nated time this mark will be displayed If using the air conditioner under very dusty environment increase the frequency of...

Reviews: