Install the indoor and outdoor units, power supply wiring and
connecting wires at least 1 meter away from televisions or
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may
not be sufficient enough to eliminate the noise.)
•
In the case of the installation of a wireless remote controller,
the transmission distance of the wireless remote controller may
be shortened if the room has a fluorescent light of electronic
lighting type (i.e., an inverter or rapid-start fluorescent light).
Keep the distance between the receiver and the fluorescent
light as far as possible.
(2) Use hanging bolts to install the indoor unit. Check that the
place of installation withstands the weight of the indoor unit.
Secure the hanging bolts with proper beams if necessary.
(length: mm)
Ceiling
Floor surface
•
•
The H1 dimension indicates the
height of the product.
Determine the H2 dimension by
maintaining a downward slope of
at least 1/100 as specified in
“7. DRAIN PIPING WORK”.
Min. 20
Min. 300
Min. 450
For drain
pan
For el.
compo. box
Min. 2500
(If no ceiling board is provided.)
*H1=300
*H2=Min. 620
Min. 700 (service space)
[Required installation place]
The dimensions indicate
the minimum required
space of installation.
Fig. 2-1
Please secure
maintenance
spa
c
e.
(1) Check the positional relationship between the ceiling
opening hole and the hanging bolt of the unit.
•
For the maintenance, inspection, and other servicing
purposes of the el. compo. box and drain pump, prepare
one of the following service spaces.
1.
2.
Inspection hatch 1, 2 (450 × 450) for the el. compo.
box and a minimum space of 300 mm for the lower
part of the product.
(Refer to Fig. 2-2)
Inspection hatch 1 (450 × 450) for the el. compo. box
and inspection hatch 2 for the lower part of the prod-
uct (see axial direction view A-1).
(Refer to Fig. 2-3)
3.
Inspection hatch 3 for the lower part of the product
and the lower part of the el. compo. box (see axial
direction view A-2).
(Refer to Fig. 2-3)
700
631
(Hanging bolt pitch)
Inspection hatch 1
(450×450)
Inspection hatch 2 (450×450)
(For disassembly such as motors and drain pan)
*
When work is possible in space of the unit
lower
part, inspection hatch 2 is unnecessary.
Inspection hatch
El. compo. box
El. compo. box
Ceiling
B
C
(Hanging bolt pitch)
Bottom of unit
Air inlet
Air outlet
Hanging bolt (× 4)
Min. 200
*H3=Min. 300
Fig. 2-2
Case 1
• 40
~50
type
700
631
(Hanging bolt pitch)
Inspection hatch 1
(450×450)
Inspection hatch 2 (450×450)
(For disassembly such as motors and drain pan)
* When work is possible in space of the unit
lower part, inspection hatch 2 is unnecessary.
El. compo. box
B
C
(Hanging bolt pitch)
Bottom of unit
Air inlet
Air
outlet
Hanging bolt (× 4)
Min. 200
500
•
63
~ 1
0
0 type
700
700
Inspection hatch
Inspection hatch 1
(450×450)
Inspection
hatch 2
Inspection hatch 3
El. compo. box
El. compo. box
(Same as the indoor
unit size +300 or more)
El. compo. box
Inspection hatch
(Ceiling opening)
Ceiling
Axial direction view A-1
Axial direction view A-2
Min. D=B+300
Min. 200
B
*H3=Min. 20
A
Fig. 2-3
Case 2, 3
(Same as the
indoor unit
size or more)
!
CAUTION
4. PREPARING BEFORE INSTALLATION