4

Install the indoor and outdoor units, power supply wiring and

connecting wires at least 1 meter away from televisions or

radios in order to prevent image interference or noise.

(Depending on the radio waves, a distance of 1 meter may

not be sufficient enough to eliminate the noise.)

In the case of the installation of a wireless remote controller,

the transmission distance of the wireless remote controller may

be shortened if the room has a fluorescent light of electronic

lighting type (i.e., an inverter or rapid-start fluorescent light).

Keep the distance between the receiver and the fluorescent

light as far as possible.

(2) Use hanging bolts to install the indoor unit. Check that the

place of installation withstands the weight of the indoor unit.

Secure the hanging bolts with proper beams if necessary.

(length: mm)

Ceiling

Floor surface

The H1 dimension indicates the

height of the product.

Determine the H2 dimension by

maintaining a downward slope of

at least 1/100 as specified in

“7. DRAIN PIPING WORK”.

Min. 20

Min. 300

Min. 450

For drain 

pan

For el. 

compo. box

Min. 2500

(If no ceiling board is provided.)

*H1=300

*H2=Min. 620

Min. 700 (service space)

[Required installation place]

The dimensions indicate 

the minimum required 

space of installation.

Fig. 2-1

Please secure 

maintenance 

spa

c

e.

(1) Check the positional relationship between the ceiling

opening hole and the hanging bolt of the unit.

For the maintenance, inspection, and other servicing

purposes of the el. compo. box and drain pump, prepare

one of the following service spaces.

1.

2.

Inspection hatch 1, 2 (450 × 450) for the el. compo.

box and a minimum space of 300 mm for the lower

part of the product. 

(Refer to Fig. 2-2)

Inspection hatch 1 (450 × 450) for the el. compo. box

and inspection hatch 2 for the lower part of the prod-

uct (see axial direction view A-1). 

(Refer to Fig. 2-3)

3.

Inspection hatch 3 for the lower part of the product

and the lower part of the el. compo. box (see axial

direction view A-2). 

(Refer to Fig. 2-3)

700
631

(Hanging bolt pitch)

Inspection hatch 1 
(450×450)

Inspection hatch 2 (450×450)
(For disassembly such as motors and drain pan)

*

When work is possible in space of the unit

 

lower

part, inspection hatch 2 is unnecessary.

Inspection hatch

El. compo. box

El. compo. box

Ceiling

B

C

(Hanging bolt pitch)

Bottom of unit

Air inlet

Air outlet

Hanging bolt (× 4)

Min. 200

*H3=Min. 300

Fig. 2-2

Case 1

• 40

~50

 type

700
631

(Hanging bolt pitch)

Inspection hatch 1 
(450×450)

Inspection hatch 2 (450×450)
(For disassembly such as motors and drain pan)
* When work is possible in space of the unit

lower part, inspection hatch 2 is unnecessary.

El. compo. box

B

C

(Hanging bolt pitch)

Bottom of unit

Air inlet

Air 
outlet

Hanging bolt (× 4)

Min. 200

500

63

 ~ 1

0

0 type

700

700

Inspection hatch

Inspection hatch 1 
(450×450)

Inspection 
hatch 2

Inspection hatch 3

El. compo. box

El. compo. box

(Same as the indoor 
unit size +300 or more)

El. compo. box

Inspection hatch

(Ceiling opening)

Ceiling

Axial direction view A-1

Axial direction view A-2

Min. D=B+300

Min. 200

B

*H3=Min. 20

A

Fig. 2-3

Case 2, 3

(Same as the 
indoor unit 
size or more)

!

CAUTION

4. PREPARING BEFORE INSTALLATION

Summary of Contents for VRV FXMQ40ARV16

Page 1: ...shocks or fire Install the air conditioner on a foundation strong enough to withstand the weight of the unit A foundation of insufficient strength may result in the equipment falling down and causing...

Page 2: ...t exerting any pressure on other parts especially the refrigerant piping drain piping flanges and other resin parts Be sure to check the type of R410A refrigerant to be used before installing the unit...

Page 3: ...liver instruction manual if any for the field supplies to the customer Hold the hanging brackets in the case of moving the indoor and outdoor units at the time of and after opening the packages Do not...

Page 4: ...cing purposes of the el compo box and drain pump prepare one of the following service spaces 1 2 Inspection hatch 1 2 450 450 for the el compo box and a minimum space of 300 mm for the lower part of t...

Page 5: ...he washer for the hanging bracket can be prevented if the washing fixing plate 8 is used During the installation work perform the curing of the air outlet and protect the resin drain pan of the indoor...

Page 6: ...lare are free of oil The drain pan and the resin part may be deteriorated if oil is attached If no torque wrenches are available refer to Table 3 as a standard When the flare nut is tightened with the...

Page 7: ...of 25 mm Make sure that the piping is short enough with a down ward slope of at least 1 100 and that there is no air bank formed No drain trap is required The drain piping will be clogged with water...

Page 8: ...ling operation according to 11 FIELD SETTING and 12 TEST OPERATION Make sure that the water is not spilled onto the electric parts of the drain pump and others Ceiling slab 1 1 5 m 300 mm max 700 mm m...

Page 9: ...g and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction A circuit breaker capable of shutting down power supply to the entire system must be installe...

Page 10: ...connections are done fill in any gaps in the through holes with putty or insulation procured locally to prevent small animals and insects from entering the unit from outside If any do get in they coul...

Page 11: ...t a screwdriver into the clearance between the grooves of the lower casing and the upper casing to remove the upper casing 2 grooves The remote controller PCB is attached to the upper casing Note Ther...

Page 12: ...possible by remote controllers Input OFF ON turns ON unit Input OFF enables control by remote con troller Input ON OFF turns OFF unit F2 T1 T2 FORCED OFF Input A SETTING MODE NO SECOND CODE NO FIELD S...

Page 13: ...door unit indoor control PCB transmission error C6 Lit Improper combination of fan driver PCB of indoor unit or setting failure in control PCB type Test operation of outdoor unit has not U3 Lit been f...

Page 14: ...formation regarding safety Be sure to observe all precautions without fail WARNING Failure to follow these instructions properly may result in personal injury or loss of life CAUTION Failure to observ...

Page 15: ...order to prevent electric shock or fire 10 Air filter inside filter chamber Sold separately 11 Suction filter chamber Sold separately 12 Suction duct Field supply 13 Machine nameplate The nameplate i...

Page 16: ...controller please clean the filter When the operating time exceeds the desig nated time this mark will be displayed If using the air conditioner under very dusty environment increase the frequency of...

Reviews: