12 Unit installation

Installation and operation manual

15

FXMA-A
VRV system air conditioner
3P688304-1 – 2022.03

e

 1526

e

 1028

a

b

b

d

c

a

Nut (field supply)

b

Washer (accessories)

c

Hanger bracket

d

Double nut (field supply)

e

Suspension bolt pitch

Install the unit temporarily.

1

Attach the hanger bracket to the suspension bolt.

2

Fix it securely.

Level

. Make sure the unit is level at all four corners using a level

or a water-filled vinyl tube.

b

a

a

Water level

b

Vinyl tube

3

Tighten the upper nut.

NOTICE

Do  NOT  install  the  unit  tilted. 

Possible  consequence: 

If

the unit is tilted against the direction of the condensate flow
(the  drain  piping  side  is  raised),  the  float  switch  might
malfunction and cause water to drip.

INFORMATION

Optional  equipment.

  When  installing  optional  equipment,

also read the installation manual of the optional equipment.
Depending  on  the  field  conditions,  it  might  be  easier  to
install the optional equipment first.

INFORMATION

For  installation  of  the  optional  output  PCB  or  the  optional
8 mm pre-filter see the reference guide located on 

https://

www.daikin.eu

.  Use  the  search  function 

  to  find  your

model.

12.2.2

Guidelines when installing the ducting

WARNING

Do  NOT  install  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater) in the duct work.

CAUTION

In  case  of  installation  WITHOUT  the  duct  on  inlet  side,
make sure to install the air filter. For more information refer
to the option list of the indoor unit.

CAUTION

▪ Make sure the installation of the duct does NOT exceed

the setting range of the external static pressure for the
unit. Refer to the technical datasheet of your model for
the setting range.

▪ Make  sure  to  install  the  canvas  duct  so  vibrations  are

NOT  transmitted  to  the  duct  or  ceiling.  Use  a  sound-
absorbing material (insulation material) for the lining of
the  duct  and  apply  vibration  insulation  rubber  to  the
hanging bolts.

▪ When  welding,  make  sure  NOT  to  spatter  onto  the

drain pan or the air filter.

▪ If the metal duct passes through a metal lath, wire lath

or  metal  plate  of  the  wooden  structure,  separate  the
duct and wall electrically.

▪ Install the outlet grille in a position where the airflow will

not come into direct contact with people.

▪ Do NOT use booster fans in the duct. Use the function

to  adjust  the  fan  rate  setting  automatically  (see

"16 Configuration"

 [

4

 20]).

The ducting is to be field supplied.

a

c

e

f

d

d

b

c

4

a

Air inlet

b

Air outlet

c

Screws for duct flanges

d

Air outlet flange

e

Air inlet flange

f

Transportation case cover

1

Remove the air outlet flange from the transportation case cover.

2

Move and attach the air outlet flange to the air outlet side.

3

Fix  the  air  outlet  flange  with  the  34  screws  for  duct  flanges
(accessory).

4

Fix  the  air  inlet  flange  using  the  remaining  15  screws  for  duct
flanges (accessory).

5

Connect  the  canvas  duct  to  the  inside  of  the  flange  on  both
sides.

6

Connect the duct to the canvas duct on both sides.

7

Wind aluminium tape around the flanges and duct connections.
Make sure there are no air leaks at any other connection.

8

Insulate  the  ducts  to  prevent  condensation  from  forming.  Use
glass wool or polyethylene foam 25 mm thick.

a

b

c

b

a

f

f

e

e

d

d

a

Screws for duct flanges (accessory)

b

Flange (located on the unit)

c

Main unit

d

Insulation (field supply)

Summary of Contents for VRV FXMA200AXVMB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXMA200AXVMB FXMA250AXVMB...

Page 2: ...laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpoklad...

Page 3: ...n accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 6...

Page 4: ...st before commissioning 19 15 2 To perform a test run 20 16 Configuration 20 16 1 Field setting 20 17 Technical data 22 17 1 Wiring diagram 22 17 1 1 Unified wiring diagram legend 22 1 About the docum...

Page 5: ...sure the installation of the duct does NOT exceed the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to insta...

Page 6: ...tructions for equipment using R32 refrigerant WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cl...

Page 7: ...nderstand the hazards involved Children SHALL NOT play with the appliance Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire D...

Page 8: ...ct your dealer WARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been carried out correctly by an installer CAUTION It is unhealthy to...

Page 9: ...MATERIAL The refrigerant inside this unit is mildly flammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process other th...

Page 10: ...ernal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appliance problems may happen For checking and adjusting the internal parts contact your dealer...

Page 11: ...ith benzine thinner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the...

Page 12: ...aware that the refrigerant inside the system is odourless WARNING The refrigerant inside the unit is mildly flammable but normally does NOT leak If the refrigerant leaks in the room and comes in conta...

Page 13: ...properly except for the above mentioned cases and none of the above mentioned malfunctions is evident investigate the system in accordance with the following procedures INFORMATION Refer to the refer...

Page 14: ...ing then additional insulation is required minimum 10 mm thickness polyethylene foam Protective guards Make sure to install protective guards field supply on the suction and discharge side to prevent...

Page 15: ...d the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install the canvas duct so vibrations are NOT transmi...

Page 16: ...nection of the drain hose might cause leaks and damage the installation space and surroundings a b a Drain pipe connection b Refrigerant pipes Drain piping connection 1 Pull out the drain plug 2 Insta...

Page 17: ...might be required 13 1 2 Refrigerant piping insulation Use polyethylene foam as insulation material with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resist...

Page 18: ...240 V 220 V Phase 1 Frequency 50 60 Hz Wire sizes 1 5 mm2 3 core wire H07RN F 60245 IEC 66 Transmission wiring For specification refer to the installation manual of the outdoor unit User interface ca...

Page 19: ...fer to the installation and operation manual of the user interface CAUTION In case shielded wire is used connect the shielding to the outdoor unit side only 15 Commissioning NOTICE General commissioni...

Page 20: ...essure To set a higher or lower external static pressure reset the initial setting with the user interface Settings for external static pressure can be achieved in 2 ways Using the airflow automatic a...

Page 21: ...unit thermistor 10 20 2 01 Not used indoor unit thermistor only 02 Used exclusively 03 Setting Thermostat differential changeover if remote sensor is used If the system contains a remote sensor set t...

Page 22: ...entication required 17 1 Wiring diagram 17 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring diagram on the unit Part numbering is by Arabic numbers in ascending or...

Page 23: ...Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor lo...

Page 24: ...3P688304 1 2022 03 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: