background image

16 Configuration

Installation and operation manual

20

FXMA-A

VRV system air conditioner

3P688304-1 – 2022.03

Fuses, circuit breakers, or protection devices

Check  that  the  fuses,  circuit  breakers,  or  the  locally
installed  protection  devices  are  of  the  size  and  type
specified  in  the  chapter 

"14  Electrical  installation"

  [

4

  18].

Be  sure  that  neither  a  fuse  nor  a  protection  device  has
been bypassed.

Internal wiring

Visually  check  the  electrical  component  box  and  the
inside  of  the  unit  for  loose  connections  or  damaged
electrical components.

Pipe size and pipe insulation

Be  sure  that  correct  pipe  sizes  are  installed  and  that  the
insulation work is properly executed.

Damaged equipment

Check  the  inside  of  the  unit  for  damaged  components  or
squeezed pipes.

Field settings

Make  sure  all  field  settings  you  want  are  set.  See

"16.1 Field setting"

 [

4

 20].

15.2

To perform a test run

INFORMATION

▪ Perform the test run according to the instructions in the

outdoor unit manual.

▪ The test run is only completed if there is no malfunction

code displayed on the user interface or the outdoor unit
7‑segment display.

▪ See  the  service  manual  for  the  complete  list  of  error

codes and a detailed troubleshooting guideline for each
error.

NOTICE

Do NOT interrupt the test run.

16

Configuration

16.1

Field setting

Make  the  following  field  settings  so  that  they  correspond  with  the
actual installation setup and with the needs of the user:

▪ External static pressure setting using:

▪ Airflow automatic adjustment setting

▪ User interface

▪ Air volume when thermostat control is OFF

▪ Time to clean air filter

▪ Thermostat sensor selection

▪ Thermostat differential changeover (if remote sensor is used)

▪ Differential for automatic changeover

▪ Auto-restart after power failure

▪ T1/T2 input setting

Setting: External static pressure

INFORMATION

▪ The fan speed of the indoor unit is preset to ensure the

standard external static pressure.

▪ To set a higher or lower external static pressure, reset

the initial setting with the user interface.

Settings for external static pressure can be achieved in 2 ways:

▪ Using the airflow automatic adjustment function

▪ Using the user interface

To set external static pressure by airflow automatic adjustment
function

NOTICE

▪ Do  NOT  adjust  the  dampers  during  the  fan  only

operation for airflow automatic adjustment.

▪ For the external static pressure higher than 100 Pa, do

NOT use airflow automatic adjustment function.

▪ If the ventilation paths have been changed, perform the

airflow automatic adjustment again.

▪ Test  run  MUST  be  done  with  a  dry  coil,  run  the  unit  for  2  hours

with fan only to dry the coil.

▪ Check  if  the  power  supply  wiring,  duct,  air  filter  are  properly

attached. If the closing damper is installed in the unit, make sure it
is open.

▪ If there is more than one air inlet and outlet, adjust the dampers so

that the airflow rate of each air inlet and outlet is conform with the
designed airflow rate.

1

Operate  the  unit  in 

fan  only  mode

  prior  to  using  the  airflow

automatic adjustment function.

2

Stop 

the air conditioning unit.

3

Set the value

 number “—“ to 03 for 

M

 11(21) and 

SW

 7.

4

Start 

the air conditioning unit.

Result: 

The  operation  lamp  lights  up  and  the  unit  starts  the  fan

operation for airflow automatic adjustment.

5

After  airflow  automatic  adjustment  is  finished  (air  conditioning
unit will stop) check if the value number “—“ is set to 02. If there
is no change, perform the setting again.

Setting content:

Then

(1)

M

SW

Airflow adjustment is OFF

11(21)

7

01

Completion of automatic airflow adjustment

02

Start of automatic airflow adjustment

03

To set external static pressure by the user interface

Check the indoor unit setting: the value number “—“ must be set to
01 for 

M

 11(21) and 

SW

 7.

1

Change  the  value  number  “—“  according  to  the  external  static
pressure of the duct to be connected as in table below.

(1)

Field settings are defined as follows:

M

: Mode number – 

First number

: for group of units – 

Number between brackets

: for individual unit

SW

: Setting number

• —: Value number

: Default

Summary of Contents for VRV FXMA200AXVMB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXMA200AXVMB FXMA250AXVMB...

Page 2: ...laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpoklad...

Page 3: ...n accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 6...

Page 4: ...st before commissioning 19 15 2 To perform a test run 20 16 Configuration 20 16 1 Field setting 20 17 Technical data 22 17 1 Wiring diagram 22 17 1 1 Unified wiring diagram legend 22 1 About the docum...

Page 5: ...sure the installation of the duct does NOT exceed the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to insta...

Page 6: ...tructions for equipment using R32 refrigerant WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cl...

Page 7: ...nderstand the hazards involved Children SHALL NOT play with the appliance Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire D...

Page 8: ...ct your dealer WARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been carried out correctly by an installer CAUTION It is unhealthy to...

Page 9: ...MATERIAL The refrigerant inside this unit is mildly flammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process other th...

Page 10: ...ernal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appliance problems may happen For checking and adjusting the internal parts contact your dealer...

Page 11: ...ith benzine thinner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the...

Page 12: ...aware that the refrigerant inside the system is odourless WARNING The refrigerant inside the unit is mildly flammable but normally does NOT leak If the refrigerant leaks in the room and comes in conta...

Page 13: ...properly except for the above mentioned cases and none of the above mentioned malfunctions is evident investigate the system in accordance with the following procedures INFORMATION Refer to the refer...

Page 14: ...ing then additional insulation is required minimum 10 mm thickness polyethylene foam Protective guards Make sure to install protective guards field supply on the suction and discharge side to prevent...

Page 15: ...d the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install the canvas duct so vibrations are NOT transmi...

Page 16: ...nection of the drain hose might cause leaks and damage the installation space and surroundings a b a Drain pipe connection b Refrigerant pipes Drain piping connection 1 Pull out the drain plug 2 Insta...

Page 17: ...might be required 13 1 2 Refrigerant piping insulation Use polyethylene foam as insulation material with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resist...

Page 18: ...240 V 220 V Phase 1 Frequency 50 60 Hz Wire sizes 1 5 mm2 3 core wire H07RN F 60245 IEC 66 Transmission wiring For specification refer to the installation manual of the outdoor unit User interface ca...

Page 19: ...fer to the installation and operation manual of the user interface CAUTION In case shielded wire is used connect the shielding to the outdoor unit side only 15 Commissioning NOTICE General commissioni...

Page 20: ...essure To set a higher or lower external static pressure reset the initial setting with the user interface Settings for external static pressure can be achieved in 2 ways Using the airflow automatic a...

Page 21: ...unit thermistor 10 20 2 01 Not used indoor unit thermistor only 02 Used exclusively 03 Setting Thermostat differential changeover if remote sensor is used If the system contains a remote sensor set t...

Page 22: ...entication required 17 1 Wiring diagram 17 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring diagram on the unit Part numbering is by Arabic numbers in ascending or...

Page 23: ...Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor lo...

Page 24: ...3P688304 1 2022 03 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: