2 Specific installer safety instructions

Installation and operation manual

5

FXMA-A
VRV system air conditioner
3P688304-1 – 2022.03

General

WARNING

Make  sure  installation,  servicing,  maintenance,  repair  and
applied materials follow the instructions from Daikin and, in
addition,  comply  with  applicable  legislation  and  are
performed  by  qualified  persons  only.  In  Europe  and  areas
where  IEC  standards  apply,  EN/IEC  60335-2-40  is  the
applicable standard.

Unit installation (see 

"12 Unit installation"

 [

4

 13])

For 

additional 

installation 

site 

requirements, 

read 

also

"2.1 Instructions for equipment using R32 refrigerant"

 [

4

 6].

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

CAUTION

Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

WARNING

Keep  any  required  ventilation  openings  clear  of
obstructions.

CAUTION

This  equipment  is  NOT  intended  for  use  in  residential
locations  and  will  NOT  guarantee  to  provide  adequate
protection to radio reception in such locations.

Duct installation (see 

"12.2.2 Guidelines when installing the

ducting"

 [

4

 15])

WARNING

Do  NOT  install  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater) in the duct work.

CAUTION

In  case  of  installation  WITHOUT  the  duct  on  inlet  side,
make sure to install the air filter. For more information refer
to the option list of the indoor unit.

CAUTION

▪ Make sure the installation of the duct does NOT exceed

the setting range of the external static pressure for the
unit. Refer to the technical datasheet of your model for
the setting range.

▪ Make  sure  to  install  the  canvas  duct  so  vibrations  are

NOT  transmitted  to  the  duct  or  ceiling.  Use  a  sound-
absorbing material (insulation material) for the lining of
the  duct  and  apply  vibration  insulation  rubber  to  the
hanging bolts.

▪ When  welding,  make  sure  NOT  to  spatter  onto  the

drain pan or the air filter.

▪ If the metal duct passes through a metal lath, wire lath

or  metal  plate  of  the  wooden  structure,  separate  the
duct and wall electrically.

▪ Install the outlet grille in a position where the airflow will

not come into direct contact with people.

▪ Do NOT use booster fans in the duct. Use the function

to  adjust  the  fan  rate  setting  automatically  (see

"16 Configuration"

 [

4

 20]).

Refrigerant piping installation (see 

"13 Piping

installation"

 [

4

 17])

CAUTION

Piping MUST be installed according to instructions given in

"13  Piping  installation"

  [

4

  17].  Only  mechanical  joints  (e.g.

braze+flare connections) that are compliant with the latest
version of ISO14903 can be used.

CAUTION

Install  the  refrigerant  piping  or  components  in  a  position
where  they  are  unlikely  to  be  exposed  to  any  substance
which  may  corrode  components  containing  refrigerant,
unless  the  components  are  constructed  of  materials  that
are  inherently  resistant  to  corrosion  or  are  suitably
protected against corrosion.

Electrical installation (see 

"14 Electrical installation"

 [

4

 18])

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

Summary of Contents for VRV FXMA200AXVMB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXMA200AXVMB FXMA250AXVMB...

Page 2: ...laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpoklad...

Page 3: ...n accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 6...

Page 4: ...st before commissioning 19 15 2 To perform a test run 20 16 Configuration 20 16 1 Field setting 20 17 Technical data 22 17 1 Wiring diagram 22 17 1 1 Unified wiring diagram legend 22 1 About the docum...

Page 5: ...sure the installation of the duct does NOT exceed the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to insta...

Page 6: ...tructions for equipment using R32 refrigerant WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cl...

Page 7: ...nderstand the hazards involved Children SHALL NOT play with the appliance Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire D...

Page 8: ...ct your dealer WARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been carried out correctly by an installer CAUTION It is unhealthy to...

Page 9: ...MATERIAL The refrigerant inside this unit is mildly flammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process other th...

Page 10: ...ernal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appliance problems may happen For checking and adjusting the internal parts contact your dealer...

Page 11: ...ith benzine thinner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the...

Page 12: ...aware that the refrigerant inside the system is odourless WARNING The refrigerant inside the unit is mildly flammable but normally does NOT leak If the refrigerant leaks in the room and comes in conta...

Page 13: ...properly except for the above mentioned cases and none of the above mentioned malfunctions is evident investigate the system in accordance with the following procedures INFORMATION Refer to the refer...

Page 14: ...ing then additional insulation is required minimum 10 mm thickness polyethylene foam Protective guards Make sure to install protective guards field supply on the suction and discharge side to prevent...

Page 15: ...d the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install the canvas duct so vibrations are NOT transmi...

Page 16: ...nection of the drain hose might cause leaks and damage the installation space and surroundings a b a Drain pipe connection b Refrigerant pipes Drain piping connection 1 Pull out the drain plug 2 Insta...

Page 17: ...might be required 13 1 2 Refrigerant piping insulation Use polyethylene foam as insulation material with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resist...

Page 18: ...240 V 220 V Phase 1 Frequency 50 60 Hz Wire sizes 1 5 mm2 3 core wire H07RN F 60245 IEC 66 Transmission wiring For specification refer to the installation manual of the outdoor unit User interface ca...

Page 19: ...fer to the installation and operation manual of the user interface CAUTION In case shielded wire is used connect the shielding to the outdoor unit side only 15 Commissioning NOTICE General commissioni...

Page 20: ...essure To set a higher or lower external static pressure reset the initial setting with the user interface Settings for external static pressure can be achieved in 2 ways Using the airflow automatic a...

Page 21: ...unit thermistor 10 20 2 01 Not used indoor unit thermistor only 02 Used exclusively 03 Setting Thermostat differential changeover if remote sensor is used If the system contains a remote sensor set t...

Page 22: ...entication required 17 1 Wiring diagram 17 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring diagram on the unit Part numbering is by Arabic numbers in ascending or...

Page 23: ...Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor lo...

Page 24: ...3P688304 1 2022 03 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: