7 Maintenance and service

Installation and operation manual

12

FXMA-A

VRV system air conditioner

3P688304-1 – 2022.03

1

Remove  the  air  filter

  (composed  of  3  equal  parts).  For  the

removal  procedure  8  mm  pre-filter  refer  to  the  reference  guide
of  the  indoor  unit.  For  other  air  filter  types  refer  to  the
installation manual of the filter chamber.

2

Clean the air filter.

 Use a vacuum cleaner or wash with water.

If  the  air  filter  is  very  dirty,  use  a  soft  brush  and  neutral
detergent.

3

Dry the air filter in the shadow.

4

Re-attach the air filter.

5

Turn ON the power.

6

To  remove  warning  screens,  see  the  reference  guide  of  the
user interface.

7.2.2

To clean the air outlet

WARNING

Do  NOT  let  the  indoor  unit  get  wet. 

Possible

consequence: 

Electrical shock or fire.

Clean with a soft cloth. If it is difficult to remove stains, use water or
a neutral detergent.

7.3

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R32

Global warming potential (GWP) value: 675

Periodical  inspections  for  refrigerant  leaks  may  be  required
depending on the applicable legislation. Please contact your installer
for more information.

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

Please contact your installer for more information.

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

▪ The  refrigerant  inside  the  unit  is  mildly  flammable,  but

normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater,  or  a  cooker,  this  may  result  in  fire,  or  the
formation of a harmful gas.

▪ Turn  OFF  any  combustible  heating  devices,  ventilate

the room, and contact the dealer where you purchased
the unit.

▪ Do  NOT  use  the  unit  until  a  service  person  confirms

that the part from which the refrigerant leaked has been
repaired.

7.3.1

About the refrigerant leakage sensor

WARNING

The R32 refrigerant leakage sensor must be replaced after
every  detection  or  at  the  end  of  its  lifetime.  ONLY
authorised persons may replace the sensor.

NOTICE

Functionality  of  the  safety  measures  are  periodically
automatically  checked.  In  case  of  malfunction,  an  error
code will be displayed on the user interface.

NOTICE

The  R32  refrigerant  leakage  sensor  is  a  semiconductor
detector  which  may  incorrectly  detect  substances  other
than  R32  refrigerant.  Avoid  using  chemical  substances
(e.g.  organic  solvents,  hair  spray,  paint)  in  high
concentrations,  in  the  close  proximity  of  the  indoor  unit
because  this  may  cause  misdetection  of  the  R32
refrigerant leakage sensor.

INFORMATION

The  sensor  has  a  lifetime  of  10  years.  The  user  interface
displays  error  "

CH-05

"  6  months  before  the  end  of  the

sensor  lifetime  and  error  "

CH-02

"  after  the  end  of  the

sensor lifetime. For more information, refer to the reference
guide of the user interface and contact your dealer.

In case of detection when the unit is in standby

When  the  detection  occurs  when  the  unit  is  in  standby,  a  "false
detection check" will occur.

False detection check

1

The unit starts fan operation on the lowest setting.

2

The user interface displays error "

A0-13

", emits an alarm sound

and the status indicator blinks.

3

The  sensor  checks  if  a  refrigerant  leakage  or  misdetection
occurred.

▪ No  refrigerant  leakage  detected. 

Result: 

  The  system  resumes

normal operation after approximately 2 minutes.

▪ Refrigerant leakage detected. 

Result:

1

The user interface displays error "

A0-11

", emits an alarm sound

and the status indicator blinks.

Summary of Contents for VRV FXMA200AXVMB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXMA200AXVMB FXMA250AXVMB...

Page 2: ...laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpoklad...

Page 3: ...n accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 6...

Page 4: ...st before commissioning 19 15 2 To perform a test run 20 16 Configuration 20 16 1 Field setting 20 17 Technical data 22 17 1 Wiring diagram 22 17 1 1 Unified wiring diagram legend 22 1 About the docum...

Page 5: ...sure the installation of the duct does NOT exceed the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to insta...

Page 6: ...tructions for equipment using R32 refrigerant WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cl...

Page 7: ...nderstand the hazards involved Children SHALL NOT play with the appliance Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire D...

Page 8: ...ct your dealer WARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been carried out correctly by an installer CAUTION It is unhealthy to...

Page 9: ...MATERIAL The refrigerant inside this unit is mildly flammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process other th...

Page 10: ...ernal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appliance problems may happen For checking and adjusting the internal parts contact your dealer...

Page 11: ...ith benzine thinner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the...

Page 12: ...aware that the refrigerant inside the system is odourless WARNING The refrigerant inside the unit is mildly flammable but normally does NOT leak If the refrigerant leaks in the room and comes in conta...

Page 13: ...properly except for the above mentioned cases and none of the above mentioned malfunctions is evident investigate the system in accordance with the following procedures INFORMATION Refer to the refer...

Page 14: ...ing then additional insulation is required minimum 10 mm thickness polyethylene foam Protective guards Make sure to install protective guards field supply on the suction and discharge side to prevent...

Page 15: ...d the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install the canvas duct so vibrations are NOT transmi...

Page 16: ...nection of the drain hose might cause leaks and damage the installation space and surroundings a b a Drain pipe connection b Refrigerant pipes Drain piping connection 1 Pull out the drain plug 2 Insta...

Page 17: ...might be required 13 1 2 Refrigerant piping insulation Use polyethylene foam as insulation material with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resist...

Page 18: ...240 V 220 V Phase 1 Frequency 50 60 Hz Wire sizes 1 5 mm2 3 core wire H07RN F 60245 IEC 66 Transmission wiring For specification refer to the installation manual of the outdoor unit User interface ca...

Page 19: ...fer to the installation and operation manual of the user interface CAUTION In case shielded wire is used connect the shielding to the outdoor unit side only 15 Commissioning NOTICE General commissioni...

Page 20: ...essure To set a higher or lower external static pressure reset the initial setting with the user interface Settings for external static pressure can be achieved in 2 ways Using the airflow automatic a...

Page 21: ...unit thermistor 10 20 2 01 Not used indoor unit thermistor only 02 Used exclusively 03 Setting Thermostat differential changeover if remote sensor is used If the system contains a remote sensor set t...

Page 22: ...entication required 17 1 Wiring diagram 17 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring diagram on the unit Part numbering is by Arabic numbers in ascending or...

Page 23: ...Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor lo...

Page 24: ...3P688304 1 2022 03 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: